Indication LED description

The  schematic  shows  the  control  keyboard  and  the 
indication plate of a 6 zone BS-636 panel. Starting from the 
top left side  we can see 4 indicators marked 'General'.
The 'Disable' LED lights in every DISABLE condition.
The 'Test' LED lights in every TEST condition .The panel 
does not has test condition as specified in 11 of EN 54-2.
The  'Fault'  LED  lights  in  every  FAULT  condition.  Blinks 
when we have a FAULT  and the buzzer is silenced.
The  'Alarm' LED lights when we have an ALARM condition. 
Blinks when we have an ALARM and the buzzer is silenced. 
The next group of indicators is the 'Alarm' indication LEDs. 

These  indicators  light  when  a  corresponding  zone  issues  an  ALARM  condition.  Below  this  group  we  have  the 
'Fault/Disable' indication for each zone. When the panel monitors an open or short circuit conditions in a zone then the 
corresponding LED will blink. If a zone is disabled the corresponding LED will light.
Below the `General` indicator group we can find the indication group called `Fault`.  The 'Batt' LED and 'Power' LED in 
combination, show us faults concerning the power supply. These combination are shown in the panel below.

Batt Fault

Power Fault

Lack of

AC voltage

Battery

Overcharging

Battery

Discharged

Battery

Absent

Charger

Error

Lights

----

Lights

Lights

Lights

Blinks

Blinks

Lights

Blinks

Blinks

The  'CPU' LED lights to indicate a problem with the main processor unit (System fault).
The green 'Power' LED lights to indicate valid internal voltages and blinks when the mains AC power supply fails.
.
 The LEDs marked 'Siren1' and  'Siren2'  correspond to the siren outputs. If a siren out has a short circuit or open circuit then 
the corresponding LED will blink. If a siren is disabled the corresponding LED will light.

Control keyboard description/operation

The panel is controlled/ operated using the six numeric keys (1 to 6) found on the front panel. When a key is pressed a short 
tone is issued.

The panel has three access levels.

Access  level 1:

 has all the functions that can be done directly from the user without using a code. These operations are:

Buzzer silence / Buzzer reactivation

 

. If an alarm of fault  condition is issued then the internal buzzer will sound.  Pressing 

the 

"1"

 

key will silence the buzzer.

 

( The buzzer sounds periodically once every minute.) Pressing this key again will reactive 

the buzzer.

Viewing disabled sirens-zones/Lamp test

.

 Pressing the  

"2"

 key will have the following affect. If any sirens are  disabled 

then the panel will issue 3 short tones, by lighting the 

General Disable

’ 

LED, and the disabled sirens will be shown by 

lighting the corresponding  LEDs Siren1 and Siren2  of the disabled sirens. Then the LEDs will stop lighting and the panel 
will  issue  again  3  short  tone,  by  lighting  the 

Zone  Disable

’ 

LED,  and  the  disable  zones  will  be  shown  by  lighting  the 

corresponding  LEDs of the disabled zones. After a while these indicators are switched off and a lamp test is conducted by 
lighting the LEDs. The panel then returns to normal operation. The above tests can be conducted only if the panel is in 
quiescent state (No fault or alarm conditions). 

Access  level 2:

 Includes all the functions that the user can do and an access code is required. The code is

 

"34”

, it is the same for all panels 

and cannot be changed. The functions that can be implemented using this code are the following:

Siren Silence.

 When an alarm is issued and we want to silence the sirens then  we must enter the user code

( 34 )

 and then the keys number 

'5' 

and

 '5'

. The sirens are silenced but the internal buzzer continues to sound. The panel 

remains in normal operation. A new alarm from another zone will resound the sirens.

Panel Reset.

 When an alarm or fault condition has occurred and we want to reset the panel we must enter the user code 

(34)

 and then the keys number 

'5' 

and

  

'6’

. The panel lights all LEDs in sequence and then enters normal operation.

Zone enable/disable.

 If we want to disable the operation of specific zones then we must enter the user code

( 34 )

 and then the keys number 

'5' 

and

  

'4'

. The LED marked  'General disable' start to blink,  and if a zone is disabled the 

Page 2 from 9

921636000_09_023

Summary of Contents for BS-634

Page 1: ...ired battery for the panels is the type 986 12V 7Ah All functions and indications are according to European Norms 54 2 and EN 54 4 Top cover retaining screws Control Keyboard and indication leds Mount...

Page 2: ...ss level 1 has all the functions that can be done directly from the user without using a code These operations are Buzzer silence Buzzer reactivation If an alarm of fault condition is issued then the...

Page 3: ...inute The default setting of this relay is set to be activated from a general alarm and immediately with no delay In this programming mode if the keys 1 and 2 are pressed we can toggle the LEDs ON or...

Page 4: ...ross section cable of 1 5mm Page 4 from 9 Figure 2 Connecting 4 detector bases to zone 1 Each base can accept BS 655 BS 660 or BS 667 detectors A remote indication LED BS 572 is connected to one of th...

Page 5: ...lt condition issued by the panel If it is required that this output be activated by an alarm condition then we must set the MODE switch 2 to the ON position To meet the requirements paragraph 8 8 of E...

Page 6: ...power on During installation use grounded antistatic wrist band to protect this equiment form ESD The panel must be installed permanetly It is not allowed to connect the device directly to any socket...

Page 7: ...wer Zone disable and General disable LEDs blink If an alarm is manually given by either activating a BS 536 call point or by activating a smoke detector with smoke or simulated smoke particles the cor...

Page 8: ...d from VdS Also VdS controls the production under CPD number Page 8 from 9 BS 636 6 zone fire detection panel KOLINDROS PIERIAS GREECE Provided options Output to fire alarm device s 0786 CPD 21016 10...

Page 9: ...put is protected with a self reseting electronic fuse Output 24M One Aux relay and each Under no circumstances should voltages or currents outside limits be connected All relays output must be protect...

Reviews: