 4. Connecting 4 gas detectors to an olympia electronics conventional panel.

Apart from connecting the zone terminal blocks, the detectors must be powered
using the 24V terminal blocks.
The total number of detectors that can be connected to a panel depends on the
current that the panel can supply. 

Ζ

1

2

4

V

_

M

Figure

 5

Terminal

resistor

8,2Κ

 

Page

 

4 from

 

7

92137

500

0_09_007

Summary of Contents for BS-375/WP/A

Page 1: ...ars 60 seconds 45 seconds 1 5 L E L 1 5 L E L 4 5 L E L year Operation LED green Alarm LED red Fault LED yellow Selectable at 10 and 20 L E L 3VA IP65 EN 60079 29 1 50270 50271 o 10 to 60 C 1 atm 10 1...

Page 2: ...n the jumper is inserted the resistance is zero and an external resistor can be used When the jumper is not placed there is an internal resistor of 440 The device operates with 10 30VDC 7 5 21VAC ATTE...

Page 3: ...tton can be used S4 This operation refers to the special operation calibration function with reference gas Via S4 select the concentration of gas that will be used 20 or 50 L E L S5 This setting refer...

Page 4: ...Figure 4 Connecting 4 gas detectors to an olympia electronics conventional panel Apart from connecting the zone terminal blocks the detectors must be powered using the 24V terminal blocks The total n...

Page 5: ...le 3 System Calibration WARNING The calibration procedure of the detector must be done by qualified personnel that have previously read the user manual The special calibration function is not availabl...

Page 6: ...In its position install the accessory OL 11 1 of the calibration kit OL 11 figure 6 4 Install the part OL 11 2 on the part OL 11 1 figure 6 5 Select via the micro switch S4 figure 3 the concentration...

Page 7: ...repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or...