GENERAL

The  BS-375/WP/A  and  BS-376/WP/A  explosive 
gas  detectors  are  used  to  measure  the 
concentrations  in  %  L.E.L.  (Lower  Explosive 
L e v e l )   w h i l e   s i m u l t a n e o u s l y   p r o v i d i n g  
autonomous  notification/alarm  operations  in 
case  there  is  a  leak  of  liquid  on  natural  gas. 
They  are  used  in  commercial  and  small 
industrial  areas  such  as  professional  kitchens 
and burner rooms.

The  installation  must  be  done  by  trained 
p e r s o n n e l   t h a t   h a s   p r e v i o u s l y   r e a d   t h e  
instruction manual.

In case on an alarm or gas leak:

Keep  calm  and  follow  the  instruction  below 
independent of their order.

Turn off all burning flames and anything that is 

smoking.

Close  all  gas  appliances

  (

kitchens 

  -

  burners

 

cookers

 

etc

.)

- Close the central gas supply or canister.
-  Open  doors  and  windows  in  order  to  ventilate 
the area.
Avoid

 :

-Turning on/off the wall switches or the detector.
-

Using  a  mobile  phone  in  the  area  that  is 

suspected to have the gas leak.
If the alarm continues then evacuate the building 

92137

500

0_09_007

BS-

375

/

WP

/

A

  Waterproof ( IP65) LPG detector with relay

BS-

376

/

WP

/

A

  Waterproof natural gas - methane detector with relay

II 3G

Ex ec IIA T6 Gc

TECHNICAL CHARACTERISTICS

10-30V

 

DC / 7.5-21V

 

AC

catalytic 

0-50 

L.E.L.

5

 

years (*)

60 

seconds

<45 

seconds

 

±

1,5 L.E.L.

 

±

1,5 L.E.L.

 

±

4.5 L.E.L./year

Operation LED

 (

green

)

Alarm LED

 (

red

)

Fault LED

 (

yellow

)

Selectable at

 10% 

and

 20% 

L.E.L

3

VA

IP

65

EN 60079-29-1, ΕΝ 50270, ΕΝ 50271

o

-10

 to 60  C

atm 

±

1

0

%

10 

to 95% relative humidity

 (

with no condensation

)

2 years

 (*

*

)

180gr.

145 x 85 x 45 mm

ABS/PC, PC

Alarm relay (24VDC, 1A, N.C. & N.O.), latching/non-latching

Connection terminal to fire alarm panel

Fault relay

 

(24

VDC

1A

N

.

O

.

)

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

OPERATION VOLTAGE
MAXIMUM CONSUMPTION

L.E.L ALARM

SENSOR TYPE
MEASUREMENT RANGE
SENSOR LIFE SPAN
SENSOR STABILIZATION PERIOD
DURING STARTUP
RESPONSE TIME

 (Τ

90

)

REPEATABILITY

CHANGE

INDICATORS

OUTPUTS 

CONNECTIVITY

OPERATION AND STORAGE
CONDITIONS

EXTERNAL DIMENSIONS  

TYPICAL WEIGHT 
GUARANTEE

PRODUCED IN ACCORDANCE WITH

CONSTRUCTION MATERIAL

MAXIMUM DEVIATION

 (

after calibration

)

DEGREES OF COVER PROTECTION

Page

 1

 from

 

7

(*) =

 

(

Ideal conditions

When the detector is exposed to 

cleaning agents, silicons and generally 

         in commercial and light industrial environments

, it is recommended to be calibrated every year

         and 

its sensor to be replaced every 3 years!

         ATTENTION!! DO NOT USE LIQUID

 GAS

 (i.e. lighter

 gas

) FOR SENSOR 

TESTING

 BECAUSE 

IT

 

         

CAUSES PERMANENT DAMAGE. Use calibration gas up to 50% L.E.L. for this purpose.

 

(**) = does not cover the gas sensor, if it is exposed to  Si, H2S, Pb & halogenated hydrocarbon.

Summary of Contents for BS-375/WP/A

Page 1: ...ars 60 seconds 45 seconds 1 5 L E L 1 5 L E L 4 5 L E L year Operation LED green Alarm LED red Fault LED yellow Selectable at 10 and 20 L E L 3VA IP65 EN 60079 29 1 50270 50271 o 10 to 60 C 1 atm 10 1...

Page 2: ...n the jumper is inserted the resistance is zero and an external resistor can be used When the jumper is not placed there is an internal resistor of 440 The device operates with 10 30VDC 7 5 21VAC ATTE...

Page 3: ...tton can be used S4 This operation refers to the special operation calibration function with reference gas Via S4 select the concentration of gas that will be used 20 or 50 L E L S5 This setting refer...

Page 4: ...Figure 4 Connecting 4 gas detectors to an olympia electronics conventional panel Apart from connecting the zone terminal blocks the detectors must be powered using the 24V terminal blocks The total n...

Page 5: ...le 3 System Calibration WARNING The calibration procedure of the detector must be done by qualified personnel that have previously read the user manual The special calibration function is not availabl...

Page 6: ...In its position install the accessory OL 11 1 of the calibration kit OL 11 figure 6 4 Install the part OL 11 2 on the part OL 11 1 figure 6 5 Select via the micro switch S4 figure 3 the concentration...

Page 7: ...repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or...