It  is  suggested  to  conduct  the  calibration 

test at least once every 12 months.

-

During  the  calibration  procedure,  conduct 

a clean air calibration and then a reference 
gas calibration

.

To calibrate the device, remove the 4 retaining 
screws

 (

figure

 1) 

in order to gain access to the 

interior

.

Clean air calibration

Take the following steps:

1.

Ensure  that  the  environment  is  clean  and 

does not contain explosive gases.

2.

Select  using  the  switches

 

S

and

 

S

2  (

figure 

3

the special function

 «

Clean air calibration

»

3. 

Press  the  button

 

BT

2  (

figure  3

for  more 

t h a n   3   s e c o n d s   u n t i l   t h e   3   s y s t e m  
LEDs

(

green

,

red

 

and  yellow

start  to  blink  with 

a one second rate.

4.

Wait  4  seconds  until  the  procedure  is 

completed.

 

This  step  may  last  60  seconds 

more in some instances

.

When the procedure is finished, the yellow 
led  and  the  buzzer  operate  intermittently. 

 

(

intermittent brief activation every second

).

 

At this point there are two instances

:

-

The

 

green  led  is  lit

.

 

This  means  that  the 

clean air calibration has finished with success. 

 

Press and hold the button

 ΒΤ2 

for more than 1 

second  to  exit  calibration  mode  and  to  return 
the detector to normal operation

.

-

The  red  led

 

is  lit

.

 

The  clean  air  calibration 

procedure  did  not  finish  successfully.

 

Press 

and  hold  the  button  BT

for  more  than  1 

second  to  exit  calibration  mode  and  to  return 
to  normal  operation.

 

You  can  repeat  the 

process  by  following  the  steps  from  the 
beginning.

Calibration using a reference gas

The steps for calibrating using a reference gas 
are the following

:

1

Ensure that the environment is clean an free 

from explosive gases.

2.

Remove  the  gland  with  the  filter  located  on 

the sensor head

 (

figure

 1).

3

In  its  position  install  the  accessory

 

OL

-11-1 

of the calibration kit

 

OL

-11 (

figure

 

6

).

4

Install the part

 

OL

-11-2 

on the part

 

OL

-11-1 

(

figure

 

6

).

5

Select via the micro-switch

 

S

4 (

figure 3

the 

concentration  of  the  reference  calibration  gas 
that will be used

 (20% 

or

 50% 

L

.

E

.

L

.).

6

Select  via  the  micro-switches

 

S

and

 

S

(

figure

  3)

  the  special  operation

  «

Calibration 

with a reference gas

».

7

Press and hold the button

 

BT

2 (

figure

 3) 

for 

more than 3 seconds until the 3 system LEDs

 

(

g r e e n

,  

r e d   a n d   y e l l o w

)  

s t a r t   t o   b l i n k

 

(

intermittent  blink  once  a  second

)

 

and  then 

release the button.

8. 

Open  the  steady  pressure  valve 

(0.

3L

  / 

minute

)

 

of the reference gas canister

.

9

Wait 3 minutes until the procedure finishes

This  step  may  last  60  seconds  more  in 
some instances

.

W h i l e   w a i t i n g   f o r   t h e   p r o c e d u r e   t o  
complete  you  can  cancel  it  at  any  time  by 
pressing  the  Bt2  button  for  more  than  3 
seconds.

 

When the procedure is finished, the yellow led  
operate  intermittently 

(

intermittent  brief 

activation  every  second

). 

At  this  point 

close the flow valve on the gas canister. 

At this point there are two instances

:

-

The

 

green  led  is  lit

.

 

This  means  that  the 

reference  gas  calibration  procedure  has 
finished  with  success. 

 

Press  and  hold  the 

button

  ΒΤ2 

for  more  than  1  second  to  exit 

calibration  mode  and  to  return  the  detector  to 
normal operation

.

-

The  red  led

 

is  lit

.

 

The  reference  gas 

c a l i b r a t i o n   p r o c e d u r e   d i d   n o t   f i n i s h  
successfully.

 

Press  and  hold  the  button  BT

for  more  than  1  second  to  exit  calibration 
mode  and  to  return  to  normal  operation.

 

You 

can  repeat  the  process  by  following  the  steps 
from the beginning.
After  the  calibration  procedure  is  finished  and 
before  normal  operation  remove  the  part

 

OL

-

11-2, 

unscrew  the  part

 

OL

-11-1 

and  reinstall 

the gland with filter to the sensor head.

Page

 

6 from

 

7

Gas

Canister

Detector

Adapter

OL-11-1

Outlet

port

Figure 6

OL-11-2

Inlet

port

92137

500

0_09_007

Summary of Contents for BS-375/WP/A

Page 1: ...ars 60 seconds 45 seconds 1 5 L E L 1 5 L E L 4 5 L E L year Operation LED green Alarm LED red Fault LED yellow Selectable at 10 and 20 L E L 3VA IP65 EN 60079 29 1 50270 50271 o 10 to 60 C 1 atm 10 1...

Page 2: ...n the jumper is inserted the resistance is zero and an external resistor can be used When the jumper is not placed there is an internal resistor of 440 The device operates with 10 30VDC 7 5 21VAC ATTE...

Page 3: ...tton can be used S4 This operation refers to the special operation calibration function with reference gas Via S4 select the concentration of gas that will be used 20 or 50 L E L S5 This setting refer...

Page 4: ...Figure 4 Connecting 4 gas detectors to an olympia electronics conventional panel Apart from connecting the zone terminal blocks the detectors must be powered using the 24V terminal blocks The total n...

Page 5: ...le 3 System Calibration WARNING The calibration procedure of the detector must be done by qualified personnel that have previously read the user manual The special calibration function is not availabl...

Page 6: ...In its position install the accessory OL 11 1 of the calibration kit OL 11 figure 6 4 Install the part OL 11 2 on the part OL 11 1 figure 6 5 Select via the micro switch S4 figure 3 the concentration...

Page 7: ...repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or...

Reviews: