background image

PAGE 8

2.0 INSTALLATION INSTRUCTIONS

2.3 - Positioning the Appliance

The technical data sheet and the type of board on the stove contain the data referring to the stove that 
might differ from these standard regulations.

In case of combustible floors, being sensitive to a rise in temperature, non combustible floor protectors 
must be used. This floor protector must reach 50cm beyond the front of the stove, 30cm to either side 
(measured form inside the combustion chamber). The floor protector can be made of metal or glass. The 
given minimum distances from combustible or heat sensitive materials have to be kept by all means at the 
back, the front and sides.

Certain stoves can be installed without safety distances, which can be found on the technical data sheet 
and the type of board.

More information regarding min. safety distances from the connecting pipe can be found at the description 
of the connection.

15

Installing the stove

The floor on which the stove is installed must be even and 

horizontal. The stove may only be installed on an adequate 

load-bearing floor. The stove can be stood on a  metal floor 

sheet or glass sheet to protect the flooring.

If the flooring or carpet is inflammable, a stable and non-

combustible spark protection plate must be used. This 

must extend 50 cm to the front and 30 cm to each side 

beyond the edge of the combustion chamber opening. 

Under the stove no spark protection plate is required.

Assembly sequence

 

If intended, install the OEC.

 

The Ø150mm stovepipe connection can be installed at 

the top or rear. The stove is supplied ready for connec-

tion from above. If you wish to connect it at the rear, the 

following steps must be carried out to make the neces-

sary modifications:
-  Break out the cover in the back panel.
-  Replace the connector sleeve and the sealing cover. 

 

Decide where the stove is to be installed. There must be 

no objects made of combustible materials within a dis-

tance of 80 cm of the stove’s radiation area, measured 

from the combustion chamber’s inspection glass, nor 

may any be placed within this area subsequently.
Depending on the installation position of the stove in 

front of walls that need to be protected (flammable or 

load-bearing), the following distances from walls need 

to be observed in accordance with the position of the 

combustion chamber door to the wall / side panel or 

the back panel (see schematic diagram).

When not dealing with walls that need to be protect-

ed, you merely need to observe a minimum distance of 

approx. 5 cm to allow for proper heat dissipation.

 

Install the pipe lining (provided on site) in the chimney. 

The connection height can be individually specified for 

a top stovepipe connection, however should not exceed 

1.5 m from the connector sleeve. For the rear stovepipe 

connection heights please refer the “Technical Data“ 

chapter. No combustible material is permitted within a 

radius of 20 cm around the stove pipe.

 

Connect the stovepipe at both connection points with 

stove putty so that the stove pipe is permanently sealed.

 

Push the stove onto its planned position and orient it so 

that the stovepipe fits into the pipe lining.

The stovepipe connections must be tight. The stove-

pipe must not protrude into the chimney.
Bear in mind that on partition walls in accordance with 

test specification EN 13240 the temperature of 85°C 

can be reached, and with light wallpaper or similar 

combustible construction materials this can result in 

colour changes.

10

25

25

Stove installed straight in corner

131°

80

10

10

Stove installed diagonally in corner

Dimensions in cm

Dimensions in cm

15

Installing the stove

The floor on which the stove is installed must be even and 

horizontal. The stove may only be installed on an adequate 

load-bearing floor. The stove can be stood on a  metal floor 

sheet or glass sheet to protect the flooring.

If the flooring or carpet is inflammable, a stable and non-

combustible spark protection plate must be used. This 

must extend 50 cm to the front and 30 cm to each side 

beyond the edge of the combustion chamber opening. 

Under the stove no spark protection plate is required.

Assembly sequence

 

If intended, install the OEC.

 

The Ø150mm stovepipe connection can be installed at 

the top or rear. The stove is supplied ready for connec-

tion from above. If you wish to connect it at the rear, the 

following steps must be carried out to make the neces-

sary modifications:
-  Break out the cover in the back panel.
-  Replace the connector sleeve and the sealing cover. 

 

Decide where the stove is to be installed. There must be 

no objects made of combustible materials within a dis-

tance of 80 cm of the stove’s radiation area, measured 

from the combustion chamber’s inspection glass, nor 

may any be placed within this area subsequently.
Depending on the installation position of the stove in 

front of walls that need to be protected (flammable or 

load-bearing), the following distances from walls need 

to be observed in accordance with the position of the 

combustion chamber door to the wall / side panel or 

the back panel (see schematic diagram).

When not dealing with walls that need to be protect-

ed, you merely need to observe a minimum distance of 

approx. 5 cm to allow for proper heat dissipation.

 

Install the pipe lining (provided on site) in the chimney. 

The connection height can be individually specified for 

a top stovepipe connection, however should not exceed 

1.5 m from the connector sleeve. For the rear stovepipe 

connection heights please refer the “Technical Data“ 

chapter. No combustible material is permitted within a 

radius of 20 cm around the stove pipe.

 

Connect the stovepipe at both connection points with 

stove putty so that the stove pipe is permanently sealed.

 

Push the stove onto its planned position and orient it so 

that the stovepipe fits into the pipe lining.

The stovepipe connections must be tight. The stove-

pipe must not protrude into the chimney.
Bear in mind that on partition walls in accordance with 

test specification EN 13240 the temperature of 85°C 

can be reached, and with light wallpaper or similar 

combustible construction materials this can result in 

colour changes.

10

25

25

Stove installed straight in corner

131°

80

10

10

Stove installed diagonally in corner

Dimensions in cm

Dimensions in cm

Stove Installation straight in corner

Stove Installation diagonally in corner

The flue connections must be tight. The stove- pipe must not protrude into the chimney. Bear in mind that 
on partition walls in accordance with test specification EN 13240 the temperature of 85°C can be reached, 
and with light wallpaper or similar combustible construction materials this can result in colour changes.

Summary of Contents for PENMAN PULAR

Page 1: ...INSTRUCTION MANUAL OLSBERG PULAR COMPACT DIN EN 13240 DIN 18897 raumluftunabh ngig DIBt Bauaufsichtliche Zulassung 15a BV G INSTALLATION INSTRUCTIONS OLSBERG PULAR CYLINDRICAL STOVE...

Page 2: ...PAGE 2...

Page 3: ...10 3 1 General Information 3 2 Suitable Fuels 3 3 Reducing Emissions 3 4 Lighting the for the first time 3 5 After Use Maintining the perfect burn 3 6 Operating The Air Slide Valve 3 7 Operating the...

Page 4: ...e the rest of the fuel burns up in the second phase of the combustion process This process is characterized by strongly glowing embers with no or only smaller temporary flames Optimal and environmenta...

Page 5: ...Pa can lead to uncontrollable combustion process that can damage the appliance itself the connecting pipe and the chimney sweep or a competent expert about finding a solution In such cases we recommen...

Page 6: ...ch its surface to prevent damage of lacquering Use protective gloves for your own protection and for the sake of the intactness of the lacquering The doors of the stove should be kept slightly open du...

Page 7: ...ditions Authorization of the stove as independent of the air in the room and insulated air inlet from outside are among these conditions It is important to consult a competent chimney sweep or expert...

Page 8: ...eeve and the sealing cover Decide where the stove is to be installed There must be no objects made of combustible materials within a dis tance of 80 cm of the stove s radiation area measured from the...

Page 9: ...horizontal connecting valves Incase of stoves with a capacity of 6kW the minimum length of the vertical connecting pipe is 50cm We recommend the use of an insert with a double wall for connecting to t...

Page 10: ...uel according to heat demand The heating value of 1kg of dry wood is 4 4 5kW This means you can place about 2 4kg of wood into a stove of 8kW capacity every hour When burning wood if a lower capacity...

Page 11: ...ant to load more fuel and only if the previous amount has burned down to embers The condition of proper operation of the stove is the appropriate chimney draught feed pressure This is considerably dep...

Page 12: ...g lever for the fire grate With the help of the operating lever the fire grate can be opened or closed to move the ash from the combus tion chamber to the ash pan by pushing the fire grate back and fo...

Page 13: ...Regulation of combustion air Position of operating lever II Ignition position max heat output I Nominal heat output with billet wood I Nominal heat output with wood briquettes 0 Obtain glow As the se...

Page 14: ...Use only a small amount of fuel at first Use only a small amount of fuel when reloading Riddle Grate What are the causes There is no proper draught at heating up Chimney or stove pipe is not closed pr...

Page 15: ...re made of materials of excellent quality There s continuous control through the manufacturing procedures and the finished stove is subjected to stringent quality control 5 0 SPECIAL NOTES WHAT FREQUE...

Page 16: ...PAGE 16 APPENDIX 1 DIMENSIONAL DRAWINGS 147 147 1218 472 472...

Page 17: ...PAGE 17 BLANK...

Page 18: ...PAGE 18 BLANK...

Page 19: ......

Page 20: ...Brought to you by Imperial Point Express Trading Estate Stone Hill Road Farnworth Bolton BL4 9TN Tel 01204 868 550 Fax 01204 868 551 Email sales percydoughty com www visionfires co uk...

Reviews: