The SET RELAY BOARDS command
The basic Tocsin 700 panel comes equipped with three user programmable SPCO relays to be
used primarily for alarm outputs. Should more relays be required cards are available which can
be added to the panels expansion port. These cards add additional relays in blocks of 8 relays.
The relay add on cards can supplied either for DIN rail mounting in an external cabinet or can
be mounted in a Tocsin 700 accessory case alongside the main panel.
In either case the system must be configured for the extra relay cards before they can be used
when programming alarm outputs. Run the SET RELAY BOARDS command to input the
number of extra relay cards fitted to the system. Once set these extra relay outputs will be
available when setting alarm outputs in the SET ALARM1,2 and 3 menus.
Set Num. Boards
0
Use the jog wheel to input the number
of extra relay cards to be fitted. Up to
four additional cards can be added. If
set at zero then only alarm relays 1 to 3
(included on the main panel) will be
available in the ALARM1,2 or £ setup
In Out
In Out
8 Channel
Relay
Output Card
P/N 5111001
8 Channel
Relay
Output Card
P/N 5111001
Volt Free
Contacts
SPCO x 8
Additional relay boards fit to the
expansion connector. More
boards are then added in line as
indicated in the diagram below.
NOTE THAT LATER VERSION TOCSIN 700 MODELS USE THE ADDRESSABLE RELAY
OUTPUT CARDS IN PREFERENCE TO THIS OLDER VERSION.