The TEST ADD RELAYS2 command
The TEST RELAYS command
This function can be used to check relay operation when commissioning or testing addressable
relay output nodes.
This function can be used to check relay operation for relays 1 to 3 on the Tocsin 700 and relays 4
to 36 on any add-on relay cards that may be present.
1 of 3 ADD= 4201
RELAY TEST
RELAY = OFF C1
RELAY AL1
When this mode is selecting this display
is shown.
Rotate the jog wheel to select a relay to test.
The bottom line of the display shows
the relay output that relates to the
address shown on the top line of the display.
Press the jog wheel to change the relay status.
Note that the relay status set will remain
until you exit engineer mode.
It should also be noted that the relay action
(normally open or normally closed) is set on
the Tocsin 107 module software. If a Tocsin 107
module is set as normally closed then switching it
on here to test it will energise it to be normally
open and vice versa.
Select the mode and the following
display is shown. Pressing the
jog wheel will energise each relay
output in turn AL1 to AL3 and also
the fault relay, Sounder and
Beacon Output
OLIVER
IGD
OLIVER
IGD