This product must be earthed in accordance with local safety regulations.
The Control Panel leaves the factory configured for the supply voltage stated on the customers order.
Standard voltage and frequency range is:-
AC Mains Powered
85 to 264 VAC 40 to 400 Hz
DC Low Voltage Powered
18 to 30V DC
Should the control panel be used in conjunction with portable generating equipment, care should be taken to ensure that
the electrical supply is within the tolerance band described above. The control panel may be stored at temperatures
0
0
between 0 C and 55 C. If stored at low temperatures and then brought into a warmer environment, condensation may
form on some components. In such a situation , this condensation should be allowed to evaporate prior to use of the
equipment. If stored at high temperature, care should be taken to ensure that humidity condensation does not enter
critical electrical components, for example the power supply. The Control Panel is designed to operate within
o
o
specification for ambient temperature between 0 C and 55 C, relative humidity up to 95% ( non-condensing ).
!Warning !
Do not use a Control Panel for protection applications that has not been calibrated. If calibration seals are missing from
the control panel or have been tampered with or broken, then the control panel must be re-calibrated and sealed by a
trained engineer.
See declaration CE-700-03
Page 3 of 52
Power Source
85 to 264 VAC ( 18 to 30 VDC Option)
Power Consumption
60 Watts (basic) 150 Watts (700+)
Display
2 x 16 backlight LCD
Operating Temperature
0°c to 55°c
Operating Humidity
Up to 95% non-condensing
Resolution
0.00% or ppm Range Dependant
Update Rate
1 Second
Size (mm)
255 (H) x 265 (W) x 100 (D)
Protection Standard IP54. With seal kit option fitted IP55
Inputs
Up to 4 or up to 8 x 4-20mA loops
Additional 8 analogue 4-20mA loops
Inputs (Optional)
2 x RS485 data highways for up to 64 detectors (700+)
3 x configurable SPCO relays (7 Amp non conductive load)
1 x fault SPCO relays (7 Amp non conductive load)
1 x solid state audio/sounder 24VDC
Outputs (Standard)
1 x solid state visual/flasher 24VDC
Outputs (Optional)
Up To 32 x configurable SPCO relays 7 Amp non inductive load
Up To 16 x Analogue Outputs (4 per additional card)
Up To 32 x Addressable Relay Outputs
Optional Equipment
Battery backup module 7AH
255 (H) x 265 (W) x 100 (D)
CE Declaration
BS EN61000-6-4 EMC Compatibility 'Emissions'
Weight
4.6 KG
BS EN 61000-6-2:2001 EMC Compatibility 'Immunity'
BS EN 61010-1: 2001 Safety requirements, electrical equipment
Who should read this manual.
This manual is intended for use by trained installers of gas detection systems who are technically competent and
have all necessary tools to undertake installation and maintenance on this type of equipment.
Failure to install and maintain the equipment properly can render the detector ineffective.
You should not undertake any of the procedures in this manual if you do not have access to the correct equipment,
have not undertaken training on this or similar equipment or are not technically qualified to install this equipment.
Calibration gases and test equipment is available from IGD.