7.

 

AUTOMATIC MODE 

 

 

 Selectable either on the remote or on the display-unit pressing the key for at least 5 seconds (in the latter case 

only  with  the  machine  previously  on  STANDBY,  no  ongoing  malfunctions  and  after  DIAGNOSTICS, 

specified below). In this mode, also signalled locally on the display-unit when LED DL4 turns on, either the 

COOLING  or  FAN  function  is  selected  automatically  depending  on  the  constantly  monitored  room 

temperature: 

 

i.

 

 -If Tamb>23°C the fan works at minimum speed;  

ii.

 

-If Tamb>23°C the system works in the cooling mode with fan speed proportional to the extent the 

this temperature differs:  

iii.

 

if 23°C<Tamb<25°C minimum speed is selected,  

iv.

 

if  25°C<Tamb<27°C  medium  speed  is  selected,  if    Tamb>27°C  maximum  speed.  After  each 

variation, fan speed remains constant for at least 3 minutes to avoid annoying hunting. 

 

 

All the  various sub programmes of  the general automatic  function  will  work in the  same  way and  have the 

same alarms defined in the single operating modes. 

 
 
 
 
 

8.

 

PROGRAMMING TIMES 

 

 

 Programming  entails  activating  two  operating  intervals  in  the  24-hour  period,  signalling  when  the  function 

starts on the display-unit with LED DL3. The remote control communicates the “current” time to the board in 

question  at  each  transmission.  The  latter  stores  the  current  time  in  the  eeprom  every  10  minutes  so  in  the 

event  of  a  blackout  (besides  its  actual  duration)  machine  activation  times  are  no  more  than  10  minutes. 

Machine functioning mode will be that corresponding to the activation mode. 

 
 

9.

 

SPECIAL FUNCTIONS 

 

 

 - DIAGNOSTICS: this is started with the machine on STANDBY, pressing the key on the display-unit for at 

least 5 seconds. The corresponding LEDs blink for 5 seconds after which the indication “AUTOMATIC” is 

activated  (continuing  until  the  ongoing  phase  finishes)  and  simultaneously  the  fan  first  works  at  minimum 

speed, then at medium speed and lastly at maximum speed 3 seconds each time. The compressor is started at 

the end of fan speed scanning (without observing any 3 minute pause and for any temperature measured by 

Tamb) for a time equal to Tdiag with fan fixed at maximum speed. At the end of this phase, the unit goes to 

the AUTOMATIC mode (maintaining the indication already given) as described above. 

 

 In the case of a blackout the unit must store the previous mode in the eeprom and resume the function that 

was  interrupted  the  instant  power  returns  (except  for  the  DIAGNOSTICS  function,  which,  in  the  case  of  a 

blackout, the machine most set itself on STANDBY). 

 
 
 
 

Summary of Contents for ISSIMO 11

Page 1: ...remote control range distance angle m 8 80 Dimensions Width x Height x Depth mm 520x485x550 Weight without packaging Kg 36 Noise sound power db A min max 34 43 Enclosure protection rating IP20 Refrigerant load Type Kg R410A Max operating pressure MPa 5 2 Power lead No poles x sect mm2 3 x 1 5 Fuse 10AT Indoor temperature Outdoor temperature Maximum operating temperature in cooling DB 35 C WB 24 C ...

Page 2: ...ard by a buzzer sounding briefly both when enabling and disabling all functions The settings to be made with the remote but not mentioned must be ignored 1 ELECTRICAL ELECTRONIC COMPONENTS Vane rotary compressor with a maximum input power of 1 3kW Inom max 6 A Isp max 25A 4 speed centrifugal fan motor with a maximum input power of 200W IR remote control with Olimpia Splendid serial protocol Unico ...

Page 3: ...ay unit in the latter case the key performs this function only when the machine is working and there are no ongoing malfunctions When the corresponding LED turns on DL1 it means this mode is active and all the outputs are off In this condition by pressing the STANDBY key again on the remote or the key on the display all the previously selected functions are reset operating mode set point fan speed...

Page 4: ...value Scala_m hysteresis Hy and scale point steps Step can be set during programming Activation of the compressor must be after a minimum Rest_time 180sec after powering of the circuit or after a previous compressor switch off All the malfunctions that are expected for the machine are enabled in this status 5 DEHUMIDIFIER MODE Selectable only with the remote control It works very much like cooling...

Page 5: ...lay unit with LED DL3 The remote control communicates the current time to the board in question at each transmission The latter stores the current time in the eeprom every 10 minutes so in the event of a blackout besides its actual duration machine activation times are no more than 10 minutes Machine functioning mode will be that corresponding to the activation mode 9 SPECIAL FUNCTIONS DIAGNOSTICS...

Page 6: ...1 second ON 1 sec OFF WIRING DIAGRAM A1 Electronic power board A2 Electronic command board B1 Thermostat probe F1 Compressor thermal protection K1 Relay for compressor K2 Relay for fan MED K3 Relay for fan MAX K4 Relay for fan MIN M1 Compressor M2 Fan M3 Condensate discharge pump S1 Safety micro switch S2 Pump micro switch T1 Transformer X1 General power supply terminal board X2 4 pole connector X...

Page 7: ...ISS0011R10_A_EN doc ...

Reviews: