PARAMETERS TABLE 
 

Mnemonic 

Value 

Description 

Expected range 

 

 

 

 

Scale_m 

18°C  

Minimum scale 

10…32°C  

 

 

 

 

Tset 

22°C  

Setpoint 

10…38°C  

 

 

 

 

Hy 

2°K  

Hysteresis 

0.5…10°K  

 

 

 

 

Adj 

0°K  

Ambient probe input calibration 

-15…+15°K  

 

 

 

 

tmin 

22°C  

Anti-ice formation temperature 

10…30°C  

 

 

 

 

tmax 

32°C  

Anti explosion temperature 

25…50°C  

 

 

 

 

Tp_on 

20 min. 

Anti-ice programme ON time 

3…60 min. 

 

 

 

 

Tp_off 

3 min. 

Anti-ice programme OFF time 

3…15 min. 

 

 

 

 

Rest_time 

180 sec. 

Compressor start-up delay 

0…255 sec. 

 

 

 

 

Tdiag 

20 min. 

Diagnostic time with compressor ON 

0…60 min 

 

 

 

 

Step 

1°K  

Setpoint adjustment step 

0.5…5°K  

 

 

 

 

Tsf 

250h 

Filter Dirty alarm activation time 

250-1000 

 
 
 

2.

 

STANDBY MODE 

 

 

 Selectable by pressing the corresponding key on the remote or locally on the display-unit (in the latter case 

the  key  performs  this  function  only  when  the  machine  is  working  and  there  are  no  ongoing  malfunctions). 

When the corresponding LED turns on (DL1) it means this mode is active and all the outputs are off. In this 

condition, by pressing the STANDBY key again on the remote or the key on the display, all the previously 

selected functions are reset (operating mode, set-point, fan speed, activation timer, etc.) and the timed settings 

for  the  various  programmes  (except  for  compressor  rest  time)  are  reinitialized.  Machine  functioning  mode 

will be that corresponding to the activation mode. Triggering of the ‘Probe KO’ malfunction is enabled in this 

status. 

 
 
 

3.

 

FAN MODE 

 

 

Selectable only with the remote control. The fan is always powered in this mode and its speed can be selected 

at any time with the key on the remote control. All the malfunctions that can be expected for the machine are 

enabled in this status. 

 
 

Summary of Contents for ISSIMO 11

Page 1: ...remote control range distance angle m 8 80 Dimensions Width x Height x Depth mm 520x485x550 Weight without packaging Kg 36 Noise sound power db A min max 34 43 Enclosure protection rating IP20 Refrigerant load Type Kg R410A Max operating pressure MPa 5 2 Power lead No poles x sect mm2 3 x 1 5 Fuse 10AT Indoor temperature Outdoor temperature Maximum operating temperature in cooling DB 35 C WB 24 C ...

Page 2: ...ard by a buzzer sounding briefly both when enabling and disabling all functions The settings to be made with the remote but not mentioned must be ignored 1 ELECTRICAL ELECTRONIC COMPONENTS Vane rotary compressor with a maximum input power of 1 3kW Inom max 6 A Isp max 25A 4 speed centrifugal fan motor with a maximum input power of 200W IR remote control with Olimpia Splendid serial protocol Unico ...

Page 3: ...ay unit in the latter case the key performs this function only when the machine is working and there are no ongoing malfunctions When the corresponding LED turns on DL1 it means this mode is active and all the outputs are off In this condition by pressing the STANDBY key again on the remote or the key on the display all the previously selected functions are reset operating mode set point fan speed...

Page 4: ...value Scala_m hysteresis Hy and scale point steps Step can be set during programming Activation of the compressor must be after a minimum Rest_time 180sec after powering of the circuit or after a previous compressor switch off All the malfunctions that are expected for the machine are enabled in this status 5 DEHUMIDIFIER MODE Selectable only with the remote control It works very much like cooling...

Page 5: ...lay unit with LED DL3 The remote control communicates the current time to the board in question at each transmission The latter stores the current time in the eeprom every 10 minutes so in the event of a blackout besides its actual duration machine activation times are no more than 10 minutes Machine functioning mode will be that corresponding to the activation mode 9 SPECIAL FUNCTIONS DIAGNOSTICS...

Page 6: ...1 second ON 1 sec OFF WIRING DIAGRAM A1 Electronic power board A2 Electronic command board B1 Thermostat probe F1 Compressor thermal protection K1 Relay for compressor K2 Relay for fan MED K3 Relay for fan MAX K4 Relay for fan MIN M1 Compressor M2 Fan M3 Condensate discharge pump S1 Safety micro switch S2 Pump micro switch T1 Transformer X1 General power supply terminal board X2 4 pole connector X...

Page 7: ...ISS0011R10_A_EN doc ...

Reviews: