PROCOOL 16 E
ENGLISH
EN - 5
0.4 - WARNINGS FOR R290 REFRIGERANT GAS
1. THE APPLIANCE CONTAINS R32 GAS (FLAMMABILITY CLASSIFICATION
A2L).
2. THE APPLIANCE MUST BE STORED IN A WELL-VENTILATED AREA WHERE
THE ROOM SIZE CORRESPONDS TO THE ROOM AREA AS SPECIFIED FOR
OPERATION.
3. INSTALLED STORED STORED IN A ROOM WITH SURFACE HIGHER THAN
THE ONE INDICATED IN THE CHART.
Quantity of R290 gas in Kg
(see data label on the appliance)
Minimum size of the site
for use and storage
m
2
0,580
4
4. THIS APPLIANCE CONTAINS A QUANTITY OF REFRIGERANT GAS R290
EQUAL TO THE ONE INDICATED IN THE DATA LABEL LOCATED ON THE
APPLIANCE.
5. THE APPLIANCE SHOULD BE STORED IN A ROOM WITHOUT
CONTINUOUSLY OPERATING IGNITION SOURCES (FOR EXAMPLE: OPEN
FLAMES, AN OPERATING GAS APPLIANCE OR AN OPERATING ELECTRIC
HEATER).
6. Do not pierce or burn.
7. Be aware that the refrigerants may not contain an odour.
8.
R32 is a refrigerant gas in compliance with the european directives on
environment. do not pierce any part of the refrigerant circuit.
9. Do not use means to accelerate the defrosting process or to clean, other
than those recommended by the manufacturer.
10. Do not use tools different from those recommended by the manufacturer
when defrosting and cleaning the appliance.
11. If the appliance is installed, used or stored in a non-ventilated area, the room
must be designed to prevent the accumulation of refrigerant leaks with
the consequent fire or explosion hazard due to the refrigerant combustion
caused by electrical heaters, stoves or others sources of ignition.
12. Compliance with national gas regulations shall be observed.
13. Keep ventilation openings clear of obstruction.
14. The appliance shall be stored so as to prevent mechanical damage from
occurring.
15. To avoid danger, do not attempt to repair or access the refrigerant in any
way. Contact the manufacture or a service agent for assistance.