Bi2 WALL TR 1000/1200/1400
EN - 23
ENGLISH
It is not possible to connect the parallel input the one of other
circuit boards; use separate contacts.
To connect the presence sensor, it is necessary to use a double-insulated cable with
a minimum section of 2x0,5 mm2 and maximum length of 20 m. Keep this connection
separated from the power supply line of the appliance.
5.1.2 - Hot/cold generator switching on consent contact
The screw connector (C) on the black and grey cables of the thermoelectric head is a
free contact (closed = valve open, 230 V max, 1 A max) to give consent for switching
on of the hot/cold generator.
5.2 - CONNECTION WITH WIRED REMOTE CONTROL B0736 OR
THIRD PARTIES MODBUS
-
Connect the cables coming from the “
A B
” connection
of the B0736 command with the respective wires on
the mammoth connected to the panel lid, taking care
to respect the polarity, yellow cord “
A
” and orange cord
“
B
”, connecting the farthest unit with the 120 Ohm
resistor supplied with the appliance.
-
Enable Remote configuration (paragraph “5.4”, con
-
figuration parameter “CF”).
- All the commands “
” shall be dis-
abled and the message “rE” will appear on the display
every time they are activated.
-
The indicator “
” shows the chosen mode of oper-
ation, the indicators “
”, “
A
”, “
” and “
” and
the set fan speeds.
- As regards the functionalities and settings, see the instructions of command
B0736.
5.3 - CONNECTION WITH SIOS CONTROL
-
Connect the cables coming from the “
A B
” connection of SIOS CONTROL with
the respective wires on the mammoth connected to the panel lid, taking care
to respect the polarity, connecting the farthest unit with the 120 Ohm resistor
supplied with the appliance.
Summary of Contents for Bi2 WALL TR 1000
Page 2: ......
Page 291: ...Bi2 WALL TR 1000 1200 1400 EL 3 0 0 1 0 2...
Page 292: ...EL 4 0 3 1 2 3 4 5 6 7 8...
Page 293: ...Bi2 WALL TR 1000 1200 1400 EL 5 0 4 1 2 3 4 5 2 21m 6 7 8 9...
Page 294: ...EL 6 10 11 12 13 3mm 14 3 C 70 C PH 6 5 7 5 15 16 17 18 19 20 21 22...
Page 295: ...Bi2 WALL TR 1000 1200 1400 EL 7 23 24 25 26 27 28 29 30 1 2 3 4 5...
Page 296: ...EL 8 6 1 1 7 8 9 10 11 12 13 14 80 15 16 17...
Page 297: ...Bi2 WALL TR 1000 1200 1400 EL 9 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32...
Page 298: ...EL 10 0 5 1 2 3 4 5 0 6 fancoil fancoil 1 2 0 7 fan coil...
Page 301: ...Bi2 WALL TR 1000 1200 1400 EL 13 e f g h i 3 3 1 a b c 3 2 3 2 1...
Page 304: ...1 1a 1a 1 9 X Y 8 EL 16 c 1a 1 3 2 4 8 9 a 4 X b 2 Y...
Page 305: ...Bi2 WALL TR 1000 1200 1400 A A 1a A 1 1a V V 10 EL 17 3 2 5 10 a 1 1 b c V...
Page 308: ...12b 12 12a 12a 14 EL 20 5 3G0 75 20mm 12a 12b 14 30 mA CEIEN 3mm...
Page 317: ...Bi2 WALL TR 1000 1200 1400 19 EL 29 7 4 1 19 a b c 7 4 2 1 5V AAA LR03 19...
Page 318: ...8m 20 EL 30 7 4 3 8 20 7 5 a T2 2 b B1 stand by 5 C AF 7 6 a T3 10 A5 b A5 A5...
Page 320: ...EL 32 a B2 D10 D11 b B6 7 8 1 a T2 A4 b a B6 D6 7 8 2 AUTO a T2 A4 b a B6 D5 7 9 a T2 A1 b T2...
Page 322: ...EL 34 7 12 7 12 1 Air sampling 1 7 12 2 T1 5 BL 7 12 3 A5 20 C 5 30 C 30 C 30...
Page 326: ...EL 38 d 7 e 7 f 7 g 7 8 2 a 8 10 b c d a b 9 a b c 9 1...
Page 327: ...Bi2 WALL TR 1000 1200 1400 EL 39 a b a a 9 2 2 3 silent 220 V...
Page 328: ...EL 40 60...
Page 449: ...26A00054A 2...