background image

SiOS CONTROL

7

6

8

1

3

4

5

2

60 

mm

70 mm

120 mm

ENGLISH

EN- 9

3.2 - B0858 - Display and keys of the main control unit

1

 

USB port

2

 Display

3

 

Key to access “system 

errors” (not plant 

errors)

4

 

Key to access

 

the emergency

 

STANDBY/ON 

command

5

 

Key to return to the previous page

6

 

Confirmation key

7

 

Key to scroll the screen upwards

8

 

Key to scroll the screen downwards

Key combinations

7 + 8

  Press these keys simultaneously to access the page of the “

menu impianto

” 

(“

system menu

”) (password 0000). Reserved for Olimpia Splendid.

3 + 6

.  Press these keys simultaneously to access the page of the “

menu impianto

” 

(“

system menu

”) (without password)

3.3 - B0859 - Expansion unit kit

•  Expansion module to be used for mixed water 

zones.

•  One single expansion controls up to 4 rooms.

•  B0859 unit addressed from ADDR001 to 

ADDR007 

 

(to be addressed with SWITCH - see diagram “A”).

Summary of Contents for B0858

Page 1: ...SiOS CONTROL MANUALE INSTALLAZIONE E USO IT USE AND INSTALLATION MANUAL EN ...

Page 2: ......

Page 3: ...menti elettrici 16 6 3 Selezione software 16 7 WEBSERVER 16 7 1 Introduzione rete TCP IP 16 7 2 Collegamento B0858 ad una rete solo per web server 18 7 3 Collegamento B0858 ad un PC 18 8 USO DI WEBSERVER 19 9 CLOUD 23 9 1 Introduzione 23 9 2 Configurazione rete 23 9 3 Configurazione cloud 24 10 APP 25 10 1 Introduzione 25 10 2 Impostazione stato impianto 26 10 3 Impostazione modo impianto 27 10 4 ...

Page 4: ...areilSERVICE aziendale interno SERVIZIO ASSISTENZA TECNICA CLIENTI Indice Iparagrafiprecedutidaquestosimbolocontengonoinformazioni e prescrizioni molto importanti particolarmente per quanto riguarda la sicurezza Il mancato rispetto può comportare pericolo per l incolumità degli operatori perdita della garanzia contrattuale declinazione di responsabilità da parte della ditta costruttrice Mano alzat...

Page 5: ...tutti i componenti attenendosi ai rispettivi manuali di installazione ATTENZIONE Segnala che potrebbero esserci delle informazioni aggiuntive su manuali allegati Indica che sono disponibili informazioni nel manuale d uso o nel manuale di installazione 0 4 AVVERTENZE GENERALI 1 Documento riservato ai termini di legge con divieto di riproduzione o di trasmissione a terzi senza esplicita autorizzazio...

Page 6: ...ermo restando le caratteristiche essenziali descritte nel presente manuale 6 Prima di alimentare elettronicamente i componenti e il sistema accertarsi che i dati di targa siano rispondenti a quelli della rete distribuzione elettrica 7 Installare e collegare i componenti secondo le istruzioni del costruttore Un errata installazione può causare danni a persone animali o cose nei confronti dei quali ...

Page 7: ...manutenzione sugli apparecchi 12 Per un corretto uso dei componenti del sistema NON SI DEVE a Lasciarli esposti ad agenti atmosferici pioggia sole ecc b Manipolarli con mani bagnate o umide 13 Installare programmare e utilizzare i componenti del sistema solamente nel rispetto delle istruzioni fornite nelpresentemanuale Ilcostruttoresconsigliaqualsiasi altro tipo di utilizzo in quanto potrebbe prov...

Page 8: ...mente tramite due reti filate RS485 Alle seriali RS485 si aggiungono uscite relè ingressi uscite analogiche una porta Ethernet per il collegamento ad un router e ad un PC una porta USB per aggiornamento software B0858 dispone anche di un piccolo display sufficiente per Configurare la rete TCP IP Avviare un aggiornamento software Accendere e spegnere l impianto in caso di emergenza In B0858 risiede...

Page 9: ...SCHEMA ATTENZIONE Gli alimentatori necessari per il funzionamento di alcuni componenti di SIOS CONTROL non sono inclusi nella fornitura ènecessarioimpiegaredispositivicommerciali del tipo a doppio isolamento 3 COMPONENTI RISERVATO AL PERSONALE TECNICO 3 1 B0858 SIOS CONTROL Unità di controllo centrale Morsetto J1 G ingresso alimentazione 24VAC 30VA oppure 28 36VDC 30W G0 ingresso alimentazione Mor...

Page 10: ...tto split idronici CI2 Morsetto J3 A B MODBUS RTU zona miscelata Morsetto J4 A B MODBUS RTU zona diretta da abbinare a convertitore B0863 Morsetto J6 collegamento rete Ethernet RJ45 Morsetto J8 ID1 GND ingresso finecorsa valvola se icona BAGNO e termostato in alternativa a sonda B0860 B0861 Morsetto J10 NO1 C1 2 uscita relè termoarredo se icona è BAGNO e indirizzo B0860 B0861 è ADDR011 uscita relè...

Page 11: ...a videata verso l alto 8 Tasto per scorrere la videata verso il basso Combinazione di tasti 7 8 Premere contemporaneamente i tasti per accedere alla pagina del menu impianto password 0000 Riservato Olimpia Splendid 3 6 Premere contemporaneamente i tasti per accedere alla pagina del menu di sistema senza password 3 3 B0859 Kit unità di espansione Modulo di espansione da impiegarsi per zone acqua mi...

Page 12: ...are per espansioni da ADDR003 e ADDR007 Morsetto J10 NO1 C1 2 uscita valvola di zona NO2 C1 2 uscita valvola di zona NO3 C3 4 5 uscita valvola di zona Morsetto J11 NO4 C3 4 5 uscita valvola di zona NO5 uscita circolatore deumidificatore o ON OFF deumidificatore B0859 ADDR001 e 002 uscita ON OFF deumidificatore B0859 da ADDR003 a 007 Morsetto J12 NO6 C6 uscita circolatore zona miscelata B0859 ADDR0...

Page 13: ...idità B0860 e B0861 richiedono l alimentazione elettrica a 230V 50 60 Hz B0860 e B0861 devono essere collegati alla rete MODBUS RTU tramite il connettore J3 dell unità B0858 B0861 versione da incasso Compatibile con scatola a muro tipo 501 B0860 versione da parete Compatibile con scatola a muro tipo 803 DISPLAY 1 Temperatura C Umidità relativa ICONE FIAMMA riscaldamento pavimento radiante attivo F...

Page 14: ...Da indirizzarsi ADDR 15 16 17 18 se collegato B0859 ADDR001 Da indirizzarsi ADDR 19 20 21 22 se collegato B0859 ADDR002 Da indirizzarsi ADDR 23 24 25 26 se collegato B0859 ADDR003 Da indirizzarsi ADDR 27 28 29 30 se collegato B0859 ADDR004 Da indirizzarsi ADDR 31 32 33 34 se collegato B0859 ADDR005 Da indirizzarsi ADDR 35 36 37 38 se collegato B0859 ADDR006 Da indirizzarsi ADDR 39 40 41 42 se coll...

Page 15: ... termoarredo split idronici unità di zona miscelata pavimento radiante deumidificatore altri ventilazione meccanica controllata VMC L edificio più grande e complesso comprende ZONA DIRETTA 200 unità ventilconvettori Bi2 e comandi parete Bi2 1 pompa di calore SHERPA o AQUADUE o TOWER o monoblocco 4 termoarredo 4 termostati temperatura umidità 4 ventilconvettori da parete Ci2 1 uscita circolatore zo...

Page 16: ...itore segnale RTU ASCII 8 B0860 B0861 Kit sonda ambiente da parete incasso T H 1 B0859 Kit unità di espansione 1 B0862 Kit sonda temperatura acqua 2 Alimentatore 24VAC Non fornito 1 Alimentatore 18VAC Non fornito Impianto composto da ZONA ACQUA DIRETTA POMPA CALORE FINO A 50 FANCOIL 4 ZONE BAGNO 1 CIRCOLATORE QUANTITÀ CODICE DESCRIZIONE 1 B0858 SIOS CONTROL unità di controllo centrale 1 B0863 Kit ...

Page 17: ...ERPA o SHERPAAQUADUE o TOWER con indirizzo 201 Solo i modelli pompe di calore S2 prevedono bus RTU Accedere a MENU SERVICE password 0829 parametro ADDR247 impostare indirizzo Accedere a MENU SERVICE password 0829 parametro ADDR220 impostare gestione remota Indirizzare i termostati B0860 e B0861 collegati a B0858 con indirizzo da 11 a 14 Premere i tasti STANDBY VENTILATORE per accedere all indirizz...

Page 18: ...to idoneo alla trasmissione dati tipo LiYCY o equivalente Posizionare il cavo di comunicazione in canaline dedicate e separate da linee di potenza Prevedere idonei alimentatori di bassissima tensione di sicurezza per B0858 B0859 e B0863 Prevedere alimentazione 230VAC per i termostati B0860 e B0861 Prestare attenzione alle uscite analogiche di B0858 che necessitano di un relè con bobina 10VDC 6 3 S...

Page 19: ...istra ogni UNO rappresenta la parte dell indirizzo IP che non potrà cambiare tutti gli host della sottorete domestica dovranno avere identica quella parte di indirizzo IP rappresentata da 1 nella subnet mask Gli ZERI rappresentano i bit che invece possono cambiare DEFAULT GATEWAY Il default gateway rappresenta l indirizzo IP del dispositivo che consente di uscire dalla sottorete di comunicare con ...

Page 20: ...agina di configurazione del Router per visualizzare le sue impostazioni IP e SUBNET MASK In generale non è necessario apportare modifiche alle impostazioni Router Ma è importante che B0858 sia configurato in modo da essere compatibile con tale rete 7 3 Collegamento B0858 ad un PC Per configurare SiOS CONTROL collegare un PC o un display micro browser all unità di controllo centrale B0858 uscita J6...

Page 21: ... di default L indirizzo IP è visualizzato sul display Per modificare l impostazione di B0858 dalla sua tastiera premere contemporaneamente il tasto 3 e il tasto 6 per accedere alla pagina del menu di sistema Per approfondire il funzionamento di una rete TCP IP fare riferimento ai paragrafi seguenti Per configurare l impianto fare riferimento al MANUALE CONFIGURAZIONE 8 USO DI WEBSERVER Dopo aver c...

Page 22: ...unto esclamativo in allarme Pagina Impostazioni generali con edificio in modo raffreddamento grafica di colore blu Stato impianto STANDBY Questa configurazione dell edificio predomina sull ON dei singoli ambienti e terminali fancoil CI2 pavimento radiante pompa di calore Stato impianto ON Questa configurazione dell edificio accende tutti gli ambienti e tutti i terminali ma non predomina su singoli...

Page 23: ...nzia che negli ambienti STUDIO e CAMERA3 a differenza dell INGRESSO è visualizzata la temperatura di SET POINT ma non è visualizzata la temperatura ambiente opzione dell installatore Pagina riferita ad un singolo ambiente Pagina Sinottico timer Pagina Impostazione timer ...

Page 24: ... Pompa di calore Temperature rilevate Pagina Pompa di calore Settaggi Pagina Pompa di calore Modalità A seconda del modello di pompa calore alcune delle funzioni e dei valori qui riportati potrebbero non essere disponibili ...

Page 25: ...ntrale B0858 premere prima il tasto 3 quindi il tasto 6 per accedere alla pagina del menu di sistema Entrare nel sottomenù SETTING e poi selezionare TCP IP SETTING ENABLE impostare DHCP AUTO IP non modificare MASK non modificare GW non modificare DNS non modificare Da questo momento in poi la unità di controllo centrale B0858 è pronta per essere collegata in cloud ATTENZIONE Nel caso di reti diver...

Page 26: ...automatic geolocation disabilitata address latitude longitude 3 Da ADMINISTRATION accedere alla pagina LINES premere NEW Compilare tutti i campi richiesti line code non compilare premere REGISTER LINE line type c Pco MAC da menù INFO di B0858 UID da menù INFO di B0858 Tera da menù INFO di B0858 Dopo aver creato la LINEA il cloud è pronto a caricare il nuovo impianto SiOS CONTROL Il caricamento del...

Page 27: ...APP 10 1 Introduzione L app è scaricabile dal web store Olimpia Splendid sia per Android che IOS sia per mobile phone tablet ed iPad SiOS CONTROL Sia il PORTALE che l APP sono costantemente e frequentemente sincronizzati con web server PORTALE APP e WEB SERVER non sono mutuamente esclusivi possono essere tutti impiegati sullo stesso impianto Il sistema contempla ed è in grado di gestire anche l ev...

Page 28: ...postazione stato impianto Selezionare lo stato del proprio impianto di riscaldamento o raffreddamento Stato impianto STANDBY Questa configurazione spegne l impianto Stato impianto ON Questa configurazione accende l impianto ...

Page 29: ...Impostazione modo impianto Selezionare il modo del proprio impianto Modo impianto raffreddamento Modo impianto riscaldamento Modo impianto raffreddamento e riscaldamento OFF produzione di sola acqua sanitaria per gli impianti abilitati ...

Page 30: ...icona IMPOSTA per accedere alle impostazioni delle singole stanze 10 4 Allarmi Per segnalare la presenza di un allarme si visualizzerà l icona con un triangolo Cliccare sull icona per visualizzare i dettagli dello stato di allarme ...

Page 31: ... 6 3 Software selection 16 7 WEBSERVER 16 7 1 Introduction to TCP IP network 16 7 2 Connection of B0858 to a network only for web server 18 7 3 B0858 connection to a PC 18 8 USO DI WEBSERVER 19 9 CLOUD 23 9 1 Introduction 23 9 2 Network configuration 23 9 3 Cloud configuration 24 10 APP 25 10 1 Introduction 25 10 2 Plant status setting 26 10 3 Plant mode setting 27 10 4 Alarms 28 Some instructions...

Page 32: ...d inform the SERVICE department in the company CUSTOMER TECHNICAL SERVICE Index Paragraphs marked with this symbol contain very important informationandrecommendations particularlyasregardssafety Failure to comply with them may result in danger of injury to the operators loss of the warranty refusal of liability by the manufacturer Raised hand Refers to actions that absolutely must not be performe...

Page 33: ...t handle all the components respecting the respective installation manuals ATTENTION Indicates that there may be additional information in attached manuals Indicates that information is available in the user manual or in the installation manual 0 4 GENERAL WARNINGS 1 This document is restricted in use to the terms of the law and may not be copied or transferred to third parties without the express...

Page 34: ...ronically powering the components and the system make sure the label data correspond to those of the electricity distribution network 7 Install and connect the components according to the manufacturer s instructions An incorrect installation can cause damage to people animals or property for which the manufacturer accepts no responsibility 8 Failing to comply with the instructions contained in thi...

Page 35: ...appliances 12 For correct use of the components of the system NEVER a Leave it expose to atmospheric agents rain sun etc b Touch it with wet or damp hands 13 Install program and use the components of the system respectingtheinstructionssuppliedinthismanual Any other use is not recommended by the manufacturer and may cause fire electric shock or injury 14 The system must be used only according to t...

Page 36: ...wired networks RS485 In addition to RS485 serial ports there are relay outputs analogical inputs outputs an Ethernet port for connection to a router and to a PC and an USB port for software update B0858 is also equipped with a small display sufficient to Configure the TCP IP network Start a software update Switch on and off the system in case of emergency In B0858 is located the whole command and ...

Page 37: ...ONTROL_SCHEMA WARNING Thepowersupplyunitsnecessaryforoperationofsome components of SIOS CONTROL are not included in the scope of supply it is necessary to use commercial devices of the double insulation type 3 COMPONENTS RESERVED FOR TECHNICAL PERSONNEL 3 1 B0858 SIOS CONTROL Main control unit Terminal J1 G 24VAC 30VA power input or 28 36VDC 30W G0 power input Terminal J2 U2 GND external air tempe...

Page 38: ...onic splits CI2 contact Terminal J3 A B MODBUS RTU mixed zone Terminal J4 A B MODBUS RTU direct zone to be combined with B0863 converter Terminal J6 Ethernet RJ45 network connection Terminal J8 ID1 GND ingresso valve limit switch input if BATHROOM icon and thermostat alternatively to probe B0860 B0861 Terminal J10 NO1 C1 2 decorative radiator relay output if icon is BATHROOM and address B0860 B086...

Page 39: ...en upwards 8 Key to scroll the screen downwards Key combinations 7 8 Press these keys simultaneously to access the page of the menu impianto system menu password 0000 Reserved for Olimpia Splendid 3 6 Press these keys simultaneously to access the page of the menu impianto system menu without password 3 3 B0859 Expansion unit kit Expansion module to be used for mixed water zones One single expansio...

Page 40: ...or expansions from ADDR003 and ADDR007 Terminal J10 NO1 C1 2 zone valve output NO2 C1 2 zone valve output NO3 C3 4 5 zone valve output Terminal J11 NO4 C3 4 5 zone valve output NO5 dehumidifier circulator or dehumidifier ON OFF output B0859 ADDR001 and 002 dehumidifier ON OFF output B0859 from ADDR003 to 007 Terminal J12 NO6 C6 mixed zone circulator output B0859 ADDR001 and 002 dehumidifier ON OFF...

Page 41: ...idity B0860 and B0861 require a 230V 50 60 Hz power supply B0860 and B0861 must be connected to the MODBUS RTU by means of the connector J3 of the unit B0858 B0861 built in version Compatible with wall box type 501 B0860 wall version Compatible with wall box type 803 DISPLAY 1 Temperature C Relative humidity ICONS FLAME radiant floor heating active SNOWFLAKE radiant floor cooling active CIRCULATOR...

Page 42: ... addressed ADDR 15 16 17 18 if connected B0859 ADDR001 To be addressed ADDR 19 20 21 22 if connected B0859 ADDR002 To be addressed ADDR 23 24 25 26 if connected B0859 ADDR003 To be addressed ADDR 27 28 29 30 if connected B0859 ADDR004 To be addressed ADDR 31 32 33 34 if connected B0859 ADDR005 To be addressed ADDR 35 36 37 38 if connected B0859 ADDR006 To be addressed ADDR 39 40 41 42 if connected...

Page 43: ... decorative radiator hydronic splits unit of mixed zone radiant floor dehumidifier others controlled mechanical ventilation CMV The largest and most complex building includes DIRECT ZONE 200 Bi2 fan coils units and wall commands Bi2 1 SHERPA or AQUADUE or TOWER or monoblock heat pump 4 decorative radiator 4 temperature humidity thermostats 4 wall fan coils Ci2 1 direct zone circulator outlet 1 ext...

Page 44: ...converter kit 8 B0860 B0861 Wall built in T H room probe kit 1 B0859 Expansion unit kit 1 B0862 Water temperature probe kit 2 Supply unit 24VAC Not supplied 1 Supply unit 18VAC Not supplied System composed of DIRECT WATER ZONE HEAT PUMP UP TO 50 FANCOILS 4 BATHROOM ZONES 1 CIRCULATOR QUANTITY CODE DESCRIPTION 1 B0858 SIOS CONTROL main control unit 1 B0863 RTU ASCII signal converter kit 4 B0860 B08...

Page 45: ... pump SHERPA or SHERPA AQUADUE or TOWER with address 201 Only S2 heat pumps envisage bus RTU Access MENU SERVICE password 0829 parameter ADDR247 set address Access MENU SERVICE password 0829 parameter ADDR220 set remote control Address the thermostats B0860 and B0861 connected to B0858 with address from 11 to 14 Press the keys STANDBY FAN to access addressing password 22 Address the expansions B08...

Page 46: ...ble for data transmission LiYCY type or equivalent Position the communication cable in specific conduits separated by power lines Envisage suitable power supply units with Safety Extra Low Voltage for B0858 B0859 and B0863 Envisage power supply 230VAC for thermostats B0860 and B0861 Pay attention to the analogical outputs of B0858 which require a relay with coil 10VDC 6 3 Software selection From B...

Page 47: ...ary form From the left every ONE represents the part of the IP address which won t be able to change all the hosts of the home subnetwork shall have that part of the IP address represented by 1 in the subnet mask identical The ZEROS represent the bits which can change DEFAULT GATEWAY The default gateway represents the IP address of the device which allows to exit from the subnetwork and to dialogu...

Page 48: ...uration page of the Router to display its IP and SUBNET MASK settings In general it is not necessary to change the settings of the Router It is instead important that B0858 is configured so that it is compatible with such network 7 3 B0858 connection to a PC To configure SiOS CONTROL connect a PC or a display micro browser to the main control unit B0858 J6 output using an Ethernet cable RJ45 From ...

Page 49: ...with a base configuration and default IP The IP address is shown on the display To change the setting of B0858 from its keyboard press key 3 and key 6 simultaneously to access the page of the system menu To explore operation of a TCP IP network please refer to the following paragraphs To configure the system please refer to the CONFIGURATION MANUAL 8 USE OF THE WEBSERVER After configuring the syst...

Page 50: ...ling in blue in alarm mode with exclamation mark Page General settings with building in cooling mode blue graphics System status STANDBY This configuration of the building prevails over the ON of the single rooms and terminals fancoil CI2 radiant floor heat pump System status ON This building configuration switches on all of the rooms and terminals but does not prevail over the single rooms and te...

Page 51: ...ighlighted that in rooms STUDIO and CAMERA3 unlike in INGRESSO is displayed the SET POINT temperature but room temperature is not displayed option of the installer Page referred to a single room Sinottico timer Timer synoptic page Impostazione timer Timer setting page ...

Page 52: ...lore Heat pump page Detected temperatures Pompa di calore Heat pump page Settings Pompa di calore Heat pump page Mode Depending on the heat pump model some of the functions and of the values indicated here may not be available ...

Page 53: ...d of the main control unit B0858 press key 3 first and then key 6 to access the page of the menu di sistema system menu Enter the submenu SETTING and then select TCP IP SETTING ENABLE set DHCP AUTO IP do not change MASK do not change GW do not change DNS do not change From this moment on the main control unit B0858 is ready to be connected in cloud WARNING In case of networks different from home n...

Page 54: ...zone community plant picture automatic geolocation disabled address latitude longitude 3 From ADMINISTRATION access the page LINES press NEW Compile all the required fields line code do not compile press REGISTER LINE line type c Pco MAC from menu INFO of B0858 UID from menu INFO of B0858 Tera from menu INFO of B0858 After creating the LINE the cloud is ready to load the new SiOS CONTROL plant Loa...

Page 55: ...s 10 APP 10 1 Introduction The app can be downloaded from Olimpia Splendid s web store both for Android and IOS mobile phone tablet and iPad SiOS CONTROL Both the PORTAL and the APP are constantly and frequently synchronized with web server PORTAL APP and WEB SERVER are not mutually exclusive they can all be used on the same plant The system envisages and is also able to manage a possible simultan...

Page 56: ...SH EN 26 10 2 Plant status setting Select the status of Your heating or cooling system Plant status STANDBY This configuration switches off the plant Plant status ON This configuration switches on the plant ...

Page 57: ... CONTROL ENGLISH EN 27 10 3 Plant mode setting Select the mode of Your plant Plant mode cooling Plant mode heating Plant mode cooling and heating OFF only production of domestic hot water for enabled plants ...

Page 58: ...elect the icon IMPOSTA SET to access the settings of the single rooms 10 4 Alarms To highlight the presence of an alarm the icon with a triangle will appear Click on the icon to display the details of the alarm status ...

Page 59: ...io locale di smaltimento rifiuti o il negozio in qui è stato acquistato il prodotto Questa disposizione è valida solamente negli stati membri dell UE DISPOSAL This symbol on the product or its packaging indicates that the appliance cannot be treated as normal domestic trash but must be handed in at a collection point for recycling electric and electronic appliances Your contribution to the correct...

Page 60: ...261796B 1 ...

Reviews: