OLIJU IMTP 2.2 Operation And Maintenance Handbook Download Page 8

IMTP 2.2 - ITTP 2.2/4/5.5/7.5 

    

ENG

 

 

§

 

Optional  4  -  only  for  IMTP-ITTP2.2: 

flow  switch  connection

  to  detect  the  minimum  flow  stop  in 

mechanical mode: connect the two terminals of the flow switch on +15V (1 of J8, fig. 5) and PS2 (3 of J8, 
fig.5) on the Logic board; the two contact can be inverted; 

§

 

Optional 5: for IMTP-ITTP2.2 there is relay output contact (1, 4 of J11 fig.5, MOT.ON-COM) 2Ampere Ð 
250Vac  max.  that  close  when  the  motor  is  working;  for  ITTP4.0-5.5-7.5  between  contacts  MOTOR  ON 
and ÒÐÒ of J10 (fig.8) there is a 12Vdc 200mA max. signal when the Motor is working; 

§

 

Optional  6:  for  IMTP-ITTP2.2  there  is  relay  output  contact  (2,  4  of  J11,  ALARM-COM,  fig.5)  2Ampere  Ð 
250Vac max. that close when there is an Alarm condition; for ITTP4.0-5.5-7.5 between contacts ALARM 
and ÒÐÒ of J10 (fig.8) there is a 12Vdc 200mA max. signal when there is an Alarm; 

§

 

Optional 7: for IMTP-ITTP2.2 you can supply a 12Vdc - 200mA max. external Fan, connecting it  between 
5,  6  of  J8  (FAN-GND,  fig.5);  for  ITTP4-5.5-7.5  you  can  supply  a  12Vdc  -  200mA  max.  external  Fan, 
connecting it between contacts VENT and ÒÐÒ of J10 (fig. 8); 

§

 

Connect  the  two 

line  wires

  and  ground  on  L,  N,  GND  for  single-phase  Inverter  IMTP2.2  (fig.  6)  or  the 

three line wires and ground on L1, L2, L3, GND for ITTP2.2 /../7.5 (fig. 7, 9); use the up-level connector 
extension for ITTP4.0W, ITTP5.5W, ITTP7.5W; 

§

 

Reconnect  J1  and  J2  connectors  for  IMTP-ITTP2.2  (fig.5)  and  J9  for  ITTP4/../7.5  (fig.8)  if  previously 
disconnected, making sure they are firmly fixed; donÕt forget the clamp on J9 for ITTP4/../7.5 (fig. 8); 

·

        Replace and close the box using the previously removed screws; 

·

        Connect the power supply plug to the electric line. 

 
Before a possible reopening of the inverter box, after functioning, switch off the voltage supply 
and  wait  at  least  1  minute  to  be  sure  that  the  capacitors  are  completely  discharged  (danger: 
contact with electric high voltage parts). 
 

 

 
 
 

5.6  Pressure transducer connection, on different types  

Table 3: pressure trasducer connections for IMP2.2-ITTP2.2 

Table 4: pressure transducer connections for ITTP4/../7.5 

 

Standard pressure transducers K16 and K25 in use are 8Ð30 Vdc Voltage supply and 4Ð20 mA output. 

 

TRASDUCER TYPE 

CONNECTIONS ON IMP-ITTP2.2 LOGIC BOARD 

Supply 

Output 

Connections on J8 

8 Р30 Vdc 

4 Р20 mA 

1 (+15V) 

 Positive supply of the pressure transducer (brown wire for K16 or K25) 

2 (PS1)

   Negative supply of the pressure transducer (white wire for K16 or K25)

 

TRASDUCER TYPE 

CONNECTIONS ON ITTP4/../7.5 LOGIC BOARD 

Supply 

Output 

Connections  

SW3-1 

SW3-2 

15 Vdc 

0 Р5 Vdc 

J6-1 (+15) 

 Positive voltage supply 

J6-3 (S) 

 transducer signal 

J6-6 (-)

   negative Voltage supply 

OFF 

OFF 

5Vdc 

0 Р5 Vdc 

J6-2 (+5) 

 Positive voltage supply 

J6-3 (S)

  transducer signal 

J6-6 (

-)

   negative voltage supply 

OFF 

OFF 

8 Р30 Vdc 

4 Р20 mA 

J6-1 (+) 

  Positive supply of the pressure transducer 

(brown wire for K16 or K25) 

J8-1 (S)

   Negative supply of the pressure transducer 

(white wire for K16 or K25) 

ON 

ON 

Summary of Contents for IMTP 2.2

Page 1: ...Motor Pump Inverter Type IMTP 2 2 M RS ITTP 2 2 M RS ITTP 4 M W RS ITTP 5 5 M W RS ITTP 7 5 W RS ENG Operation and maintenance handbook...

Page 2: ...5 Electric connection to Line and Motor 7 5 6 Pressure transducer connection on different types 8 5 7 Connections on the electronic board 9 6 STARTING AND PROGRAMMING 12 6 1 First Inverter Using Self...

Page 3: ...0mA or 0 5V output The control logic works with an output of 5 or 15V switchable that supplies the pressure transducer MINIMUM FLOW WORKING PROTECTION to prevent a closed delivery working the control...

Page 4: ...ty regulations could endangers others and damage the devices which can lead to loss of warranty The results of the non observance of the security rules can be Malfunctioning of the system Danger to ot...

Page 5: ...to remove the paint from the contact surface It is necessary to avoid ground loop that is like an antenna for EMC emission Power supply must be admitted on working condition don t lift or carry the m...

Page 6: ...ic system Before working be certain all the circuit is without voltage also the connections voltage clear Disconnect the inverter from the power supply before working on electrical or mechanical parts...

Page 7: ...wo cables connectors from the logic board J1 26 poles e J2 4 poles for IMTP2 2 ITTP2 2 Figure 5 or J5 26 poles for ITTP4 7 5 Figure 8 Connect the 3 motor terminals U V W on the power board on IMTP2 2...

Page 8: ...nnectors for IMTP ITTP2 2 fig 5 and J9 for ITTP4 7 5 fig 8 if previously disconnected making sure they are firmly fixed don t forget the clamp on J9 for ITTP4 7 5 fig 8 Replace and close the box using...

Page 9: ...9 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG 5 7 Connections on the electronic board Figure 5 Logic board of IMTP2 2 ITTP 2 2...

Page 10: ...10 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 6 Power board of IMTP 2 2 Figure 7 Power board of ITTP 2 2...

Page 11: ...11 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 8 Logic board of ITTP 4 7 5 Figure 9 Power board of ITTP 4 7 5...

Page 12: ...pump is fully of water and close completely the outlet of the pump Pressing START for the Self Regulation Check for the registration of the curve of the pump for the regulation of the stop for closed...

Page 13: ...after the variation press ENTER Decrease the reference pressure during functioning ESC To exit to the function and automatically saving START Pump start STOP Pump stop If pressed with the key during...

Page 14: ...iangle see 5 3 Set the rotation direction 0 1 Default 0 Regulation of the minimum flow power for the motor stop in closed output condition Regulation of the dry working power stop default 80 Pump data...

Page 15: ...flow stop Default 12 second 15 second for ITTP4 7 5 4 Re start delay time after minimum flow stop Default 1 second 5 Dry working stop delay time for pump filling Default 40 seconds 6 When cos go down...

Page 16: ...faulty current control Automatic re start final stop after 10 consecutive events 13 Input Voltage under limit Input voltage under the minimum working limit Automatic re start final stop after 10 cons...

Page 17: ...output power to the motor then stop the motor and the inverter show Over Temperature IGBT alarm Inverter Temperature alarm Temperature of the electronic board of the inverter is too high and the inve...

Page 18: ...at pump haven t any defect fault seal impellers etc that can cause a big power absorbing also without water in dry condition 13 A group of two or more inverters cannot communicate between each other i...

Page 19: ...ctives and to national law following the technical standards Machines 98 37 CE Low Voltage 73 23 CE e successive modifiche and subsequent amendments IEC EN 61000 6 1 CEI EN 61000 6 4 ETSI EN 301 489 1...

Page 20: ...na Ind Esmoriz Sector C 8 36 13 86 O GPS OLIJU Manufacturing 40 57 27 11 N PORTUGAL PORTUGAL 4520 475 Rio Me o Zona Industrial de Rio Me o Avenida Santiago N 43 40 57 37 20 N 8 35 50 10 O GPS OLIJU Co...

Reviews: