OLIJU IMTP 2.2 Operation And Maintenance Handbook Download Page 7

IMTP 2.2 - ITTP 2.2/4/5.5/7.5 

    

ENG

 

 

 

The 

three-phase 

inverters 

ITTP2.2

 

and 

ITTP5.5/7.5

 must be installed on asynchronous 

three-phase  motor  with  200-460  Vac  50/60  Hz 
voltage supply. The phases must be connected 
in  star  mode  if  the  motor  is  230V    /  400  V   
(most common case, as in Fig 4). 

 

Figure 4 – Star motor phases connection 

 
The  unit  is  equipped  with  output  over-current 
protection;  it  is  not  necessary  to  install  any 
additional safety device between the inverter and the pump in order to protect the motor in case of failure. 

 

 
 

5.5   Electric connection to Line and Motor 

 

Supply for IMTP2.2 device is a single-phase voltage 100-240Vac, 50/60Hz.  
Supply for ITTP2.2 and ITTP5.5/7.5 device is a three-phase voltage 200-460Vac, 50/60Hz.  
The plant to which the inverter is connected must be conforms to safety regulations in use:  
¥ Differential automatic switch: I  n = 30mA recommended type A or B (specific for Inverters load) 
¥ Magnetic-thermal automatic switch with intervention current proportionate to the power of 
the pump installed (see Table 1) 
 ¥ Ground connection with total resistance less than 100 ½ 

 

Pump power (kW) 

Magnetic-Thermal protection (A) 

0.37 (0.5 Hp) 

0.75 (1 Hp) 

1.5 (2 Hp) 

12 

2.2 (3 Hp) 

16 

3 (4 Hp) 

20 

4 (5.5 Hp) 

25 

5.5 (7.5 Hp) 

32 

7.5 (10 Hp) 

40 

Table 2: Magnetic-Thermal protection 

 

To make 

electrical connections

 observe the following instructions (reference to Figure from 5 to 9):  

 

·

 

Open the inverter box unscrewing the 4 screws on the cover; 

·

 

Wait at least two minutes before work on the Inverter to ensure that the capacitors are fully discharges;  

·

 

Fix the bottom of the inverter box to terminal motor case with the 4 screws; 

·

 

If is necessary, disconnect the two cables connectors from the logic board J1 (26 poles) e J2 (4 poles) for 
IMTP2.2-ITTP2.2 (Figure 5) or J5 (26 poles) for ITTP4/../ 7.5 (Figure 8); 

·

 

Connect the 3 

motor terminals

 U, V, W on the power board on IMTP2.2 / ITTP2.2 /../7.5 (fig. 6, 7, 9); use 

the up-level connector extension for ITTP4.0W, ITTP5.5W, ITTP7.5W; 

·

 

Connect the 

pressure transducer

 terminals on the logic board (see paragraph 5.6); 

·

 

Optional  1  - 

enable  contact

:  If  possible  connect  the  float  switches  or  probe  level  (with  NC  contact) 

between terminals EN (enable, pole 8 of J9) and GND (common, pole 8 of J9) on the logic board of IMTP-
ITTP2.2 (figure 5) or between EN (pole 1 of J11) and C (pole 2 of J11) on the logic board of ITTP5.5/7.5 
(figure 8), replacing the wire connected by the constructor;  

§

 

Optional 2: 

MASTER – SLAVE Operating Mode on RS485 serial bus

: in a group of pumps controlled by 

inverters connect the two wires of RS485 at the terminal J10 of the logic board on IMTP-ITTP2.2 or on J2 
of the logic board of ITTP4/../7.5, respecting the polarity A or B;  

§

 

Optional  3:  Auxiliary  ON/OFF  Pump  contact:  for  IMTP2.2  and  ITTP2.2  version,  there  is  a  relay  output 
contact (3, 4 of J11, AUX-COM, fig.5) that close when the pressure is less than the reference value and 
the  motor  velocity  arrive  to  the  maximum  velocity,  then  re-open  when  the  pressure  is  higher  than  the 
reference value  and the flow  arrive to the minimum stop value; this relay contact is 2 Ampere - 250Vac 
maximum, useful to drive a contactor for a second ON-OFF pump, and work only when the control group 
mode  is  in  Pressure  mode;  Warning:  connect  only  contactors  or  relay  coils  with  maximum  voltage  of 
250Vac;  

For  ITTP4.0/../7.5  this  output  is  12VDC-100mA  on  the  poles  marked with  AUX  and  "-"  on  J10 

(fig.  8)  which  can  be  connected  to  12Vdc  coil  of  a  relay,  to  control  a  second  ON  /  OFF  pump,  with  the 
same logic insertion and removal models described above to 2.2 kW;

 

Summary of Contents for IMTP 2.2

Page 1: ...Motor Pump Inverter Type IMTP 2 2 M RS ITTP 2 2 M RS ITTP 4 M W RS ITTP 5 5 M W RS ITTP 7 5 W RS ENG Operation and maintenance handbook...

Page 2: ...5 Electric connection to Line and Motor 7 5 6 Pressure transducer connection on different types 8 5 7 Connections on the electronic board 9 6 STARTING AND PROGRAMMING 12 6 1 First Inverter Using Self...

Page 3: ...0mA or 0 5V output The control logic works with an output of 5 or 15V switchable that supplies the pressure transducer MINIMUM FLOW WORKING PROTECTION to prevent a closed delivery working the control...

Page 4: ...ty regulations could endangers others and damage the devices which can lead to loss of warranty The results of the non observance of the security rules can be Malfunctioning of the system Danger to ot...

Page 5: ...to remove the paint from the contact surface It is necessary to avoid ground loop that is like an antenna for EMC emission Power supply must be admitted on working condition don t lift or carry the m...

Page 6: ...ic system Before working be certain all the circuit is without voltage also the connections voltage clear Disconnect the inverter from the power supply before working on electrical or mechanical parts...

Page 7: ...wo cables connectors from the logic board J1 26 poles e J2 4 poles for IMTP2 2 ITTP2 2 Figure 5 or J5 26 poles for ITTP4 7 5 Figure 8 Connect the 3 motor terminals U V W on the power board on IMTP2 2...

Page 8: ...nnectors for IMTP ITTP2 2 fig 5 and J9 for ITTP4 7 5 fig 8 if previously disconnected making sure they are firmly fixed don t forget the clamp on J9 for ITTP4 7 5 fig 8 Replace and close the box using...

Page 9: ...9 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG 5 7 Connections on the electronic board Figure 5 Logic board of IMTP2 2 ITTP 2 2...

Page 10: ...10 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 6 Power board of IMTP 2 2 Figure 7 Power board of ITTP 2 2...

Page 11: ...11 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 8 Logic board of ITTP 4 7 5 Figure 9 Power board of ITTP 4 7 5...

Page 12: ...pump is fully of water and close completely the outlet of the pump Pressing START for the Self Regulation Check for the registration of the curve of the pump for the regulation of the stop for closed...

Page 13: ...after the variation press ENTER Decrease the reference pressure during functioning ESC To exit to the function and automatically saving START Pump start STOP Pump stop If pressed with the key during...

Page 14: ...iangle see 5 3 Set the rotation direction 0 1 Default 0 Regulation of the minimum flow power for the motor stop in closed output condition Regulation of the dry working power stop default 80 Pump data...

Page 15: ...flow stop Default 12 second 15 second for ITTP4 7 5 4 Re start delay time after minimum flow stop Default 1 second 5 Dry working stop delay time for pump filling Default 40 seconds 6 When cos go down...

Page 16: ...faulty current control Automatic re start final stop after 10 consecutive events 13 Input Voltage under limit Input voltage under the minimum working limit Automatic re start final stop after 10 cons...

Page 17: ...output power to the motor then stop the motor and the inverter show Over Temperature IGBT alarm Inverter Temperature alarm Temperature of the electronic board of the inverter is too high and the inve...

Page 18: ...at pump haven t any defect fault seal impellers etc that can cause a big power absorbing also without water in dry condition 13 A group of two or more inverters cannot communicate between each other i...

Page 19: ...ctives and to national law following the technical standards Machines 98 37 CE Low Voltage 73 23 CE e successive modifiche and subsequent amendments IEC EN 61000 6 1 CEI EN 61000 6 4 ETSI EN 301 489 1...

Page 20: ...na Ind Esmoriz Sector C 8 36 13 86 O GPS OLIJU Manufacturing 40 57 27 11 N PORTUGAL PORTUGAL 4520 475 Rio Me o Zona Industrial de Rio Me o Avenida Santiago N 43 40 57 37 20 N 8 35 50 10 O GPS OLIJU Co...

Reviews: