12
OLCT10N
Manual
End of line resistance
For the last detector of each, set switch
n° 8 (EOL RESISTOR/RESISTANCE
F.D.L) to ON.
006
Figure 5
:
End of line resistor switch
in position “ON”.
Scope of use
The sensors have certain limitations; it is essential to fully recognize these
limitations
Presence of specific components
High concentrations of organic solvents (e.g. alcohols, aromatic solvents, etc.) or
exposure to quantities of gas greater than the specified range of measurement
can damage the electrochemical sensors. Inspection or calibration is then
recommended.
Operation under low oxygen levels
If an electrochemical detector sensor is used in an atmosphere comprising less
than 1% oxygen for over one hour, the measurement may be an
underestimate.