25
I
I
X
X
.
.
S
S
P
P
E
E
C
C
I
I
F
F
I
I
C
C
A
A
T
T
I
I
O
O
N
N
S
S
Sensor
OLCT80(D)
Manufacturer
ISC/OLDHAM SA
Type
Detector - transmitter
Gases detected
Explosive, toxic and oxygen
Detection principles
Catalytic
Electrochemical
Infrared (IR)
Semi-conductor (SC)
Range
see table
Sensor block
Pre-calibrated
Material
Stainless steel 316L
Casing
Aluminium
Display
Backlit 4-digit LCD display for measurement and one alphanumerical
line for texts, pictograms - 4 indicator lamps: one green power lamp,
one yellow fault lamp, two red lamps for alarms 1 and 2
Power supply to sensor terminals
Two independent inputs: 16 to 28 VDC (catalytic / IR / SC sensors)
12 to 30VDC (electrochemical sensor)
Maximum power with digital link
0.2 W (electrochemical sensor) -1.3 W ( catalytic / SC ) -5.3 W (IR)
with I output at 25 mA
0.9 W (electrochemical sensor) -2 W ( catalytic / SC ) -6 W (IR)
with I output at 25 mA and relays
activated
2.4 W (electrochemical sensor) - 3.5 W ( catalytic / SC ) -7.5 W (IR)
Inputs
Two analogue inputs 4-20 mA (load resistance 120 ohms)
Outputs:
Logic (relay contacts)
3 potential-free relays
analogue
Current source encoded from 0 to 25 mA (non-isolated)
4 to 20 mA linear current reserved for measurement
0 mA indicates an electronic fault or no power supply
An output of 1.5 mA indicates an optical fault, Temperature outside limit
A 2 mA output indicates calibration mode
An output greater than 23 mA indicates a range overrun
digital
Two independent opto-isolated RS485 ports
Alarms
2 programmable thresholds per channel
Relays
type
1 pole
number
3 (2 alarm + 1 fault)
contact
RCT changer-over
breaking capacity
2A / 250 VAC / 30 VDC
wiring / connection
Basic version, 6 inputs: 4 M20 and 2 M25
On request: 3 additional, 2 M20 and 1 M25
Load resistance on the 4 / 20 mA
500 Ohms
Loop resistance (on ISC/OLDHAM
central unit)
Under central unit 21 VDC: 128 ohms ( electrochemical sensor ) - 32
ohms ( catalytic / SC ) - 16 ohms (IR)
Fastening lug
See drawings
Protection factor
IP 66
Operating temperatures
- 25 °C to +55 °C ( electronics, see table for detection cells )
Note
: Performance levels are reduced at higher temperatures (max. 70°C):
contact us for details.
Dimensions
See drawings
Weight
OLCT 80: 3.5 kg
ATEX certification
Conforms to Directive
94/9/EC, see ATEX
paragraph
Electromagnetic compatibility
Complies with EN 50270