28
3.4.5.
PC Communication
Switch Position 5
PC communication allows configuration of the system WinPro® by means of
the software ConfigPro.
3.5.
Single Mode
The single mode is indicated by blinking of the yellow LED for ‘single mode’.
During this status, redundancy or comparison of the two controllers with each
other is disturbed. Even though measuring will still correctly be carried out by
the unit and all safety functions are maintained (safe relay connection), the com-
plete channel indication may fail. In this case, all LEDs for ‘fault’ are blinking
(see 3.7. Measures against Faults).
3.6.
System Failure
Blinking of the yellow LED for ‘system failure’ indicates malfunct-ion of the
whole system. Safety functions can no longer be maintained (see 3.7. Measures
against Faults).