6
MX 32
Instruction Manual
Ref.
Function
See page
A.
Configuration jumper (J03) for
Fault*
relay settings.
■ Up position:
Fault
relay contact closed in alarm mode.
■ Down position:
Fault
relay contact open in alarm mode.
B.
F7 Fuse (5x20, 250 V AC - 2 A T) with 24V DC power supply.
C.
F9 Fuse:
■ 5x20, 250 V AC - 160 mA T with 230 VAC power supply.
■ 5x20, 250 V AC - 315 mA T with 115 VAC power supply.
D.
F8 Fuse:
■
5x20, 250 V AC - 160 mA T with 230 VAC power supply.
■
5x20, 250 V AC - 315 mA T with 115 VAC power supply.
E.
Sector power supply terminal (230 V AC or 110 V AC upon request) with
the following identifications: P (phase), N (neutral) and
(ground).
F.
Power terminal block 24 V DC (0, + 24V).
G.
Fault
relay terminal block. Contacts RCT, 250 V AC
– 2 A. Contact
status not in alarm mode as defined by J03 (ref. A).
H.
Terminal block connection for channel #1 sensor.
I.
Relay terminal block
RL 1 - Channel 1
. Contacts RCT, 250 V AC
– 2 A.
Contact status not in alarm mode as defined by J10 (ref. X).
J.
Secondary ground connection.
K.
Relay terminal block
RL 2 - Channel 1
. Contacts RCT, 250 V AC
– 2 A.
Contact status not in alarm mode as defined by J05 (ref. V).
L.
Terminal block connection for channel #2 sensor.
M.
Relay terminal block
RL 1 - Channel 2
. Contacts RCT, 250 V AC
– 2 A.
Contact status not in alarm mode as defined by J08 (ref. W).
N.
Relay terminal block
RL 2 - Channel 2
. Contacts RCT, 250 V AC
– 2 A.
Contact status not in alarm mode as defined by J07 (ref. U).
O.
Zero settings (P4) for channel #2.
P.
Sensitivity settings (P6) for channel #2.
Q.
Sensitivity settings (P5) for channel #1.
R.
Zero settings (P3) for channel #1.
S.
Programming circuit (Explo 340 mA or 4-20 mA) for channel #1.
-
T.
Programming circuit (Explo 340 mA or 4-20 mA) for channel #2.
-
U.
Configuration jumper (J07) for
Alarm 2*
, channel #2 relay.
■
Up position: relay contact closed in alarm mode.
■
Down position: relay contact open in alarm mode.
-
V.
Configuration jumper (J05) for
Alarm 2*
, channel #1 relay.
■
Up position: relay contact closed in alarm mode.
■
Down position: relay contact open in alarm mode.
-
W.
Configuration jumper (J08) for
Alarm 1*
, channel #2 relay.
■
Up position: relay contact closed in alarm mode.
■
Down position: relay contact open in alarm mode.
-
X.
Configuration jumper (J10) for
Alarm 1*
, channel #1 relay.
■
Up position: relay contact closed in alarm mode.
■
Down position: relay contact open in alarm mode.
Y.
F13 Fuse (5x20, 250 V AC
– 630 mA T).
-
Z.
F11 Fuse (5x20, 250 V AC
– 630 mA T).
-
*
alarm relays are configured as energized at the factory. This means that they are supplied with
power when not in alarm.