AirAware
7
Mounting & Installation
The mounting height of the AirAware is dependent on the gas being
monitored and the source of the gas. General mounting guidelines are as
follows:
Gas
Heavier Than Air
Similar To Air
Lighter Than Air
Will collect in low
lying areas 3' (1m)
above floor
Breathing zone
monitoring recom-
mended 3'-6' (1-2m)
above floor
Will collect in high
areas 3' (1m) below
ceiling
Ammonia (NH3)
Carbon Monoxide (CO)
Chlorine (Cl2)
Hydrogen Chloride (HCl)
Hydrogen Sulfide (H2S)
Nitric Oxide (NO)
Nitrogen Dioxide (NO2)
Oxygen (O2)
Sulfur Dioxide (SO2)
With 5 conduit-type knockouts located around the outside edges as well as a
back plate knockout for flush mounting, the AirAware offers maximum
mounting flexibility. There is even provision for mounting on electrical outlets
with 2” and 4” (North American) centers.