AirAware
17
Alarm Conditions for Different Configurations
Monitor
Control
Transmit
Control/transmit
Low Alarm
Flashing
“LOW”
indicator
Low Alarm
Audible Alarm*
Flashing
“LOW”
indicator
Low Alarm
relay switched
Low Alarm
relay switched
mA signal
proportional
to display
Flashing “LOW”
indicator
Low Alarm relay
switched
mA signal propor-
tional to display
High Alarm
Flashing
“HIGH”
indicator
High Alarm
Audible Alarm*
Flashing
“HIGH”
indicator
High Alarm
relay switched
Flashing
“HIGH”
indicator
mA signal
proportional
to display
Flashing “HIGH”
indicator
High Alarm relay
switched
mA signal
proportional to
display
Zero Failure
Flashing
Display
Pulsing Audio
Alarm*
Flashing
Display
Pulsing Audio
Alarm*
Flashing
Display
Pulsing Audio
Alarm*
mA signal at
old value
Flashing Display
Pulsing Audio
Alarm*
mA signal at old
value
Instrument
Failure
Flashing
Display
Pulsing Audio
Alarm*
Flashing
Display
Pulsing Audio
Alarm*
Flashing
Display
Pulsing Audio
Alarm*
mA signal at 0
mA
Flashing Display
Pulsing Audio
Alarm*
mA signal at 0 mA
No Sensor
Installed
Flashing
Display
Pulsing Audio
Alarm*
Flashing
Display
Pulsing Audio
Alarm*
mA signal at 0
mA
Pulsing Audio
Alarm*
mA signal at 0 mA
Pulsing Audio
Alarm*
Open mA
Loop
mA signal at 0
mA
Pulsing Audio
Alarm*
mA signal at 0 mA
Pulsing Audio
Alarm*
Shorted mA
Loop
mA signal at 0
mA
Pulsing Audio
Alarm*
mA signal at 0 mA
Pulsing Audio
Alarm*