© 2015 OJ Electronics A/S
23
replacing a faulty room controller/sensor
1.
Identify the sensor/controller to be replaced from the flashing output LED.
2. Switch OFF power to the master.
3. Replace the sensor/controller.
4. Switch ON power to the master.
5. Set the master to learning mode by switching DIP-3 to ON.
6. If the sensor/controller is wireless, press the learning mode button on the sensor/controller.
See “Installation” under “Waterline Room Sensors - Type WLTx”.
If the sensor/controller is wired, proceed to step 7.
7. Check that the corresponding output LED has changed from flashing to permanently ON.
8. Reset DIP-3 to OFF.
Important: Set the channel selector on the new sensor/controller to the same channel as
the defective sensor/controller that is replaced
replacing units