Relay test for a speed controlled condenser circuit pump
Line Connector Output
Function
Marking
Additional information
7700
V
QX13
Condenser circuit pump Q9
Q9
7710
y
UX1
Output test UX1
UX1
When the test is switched
on and the desired speed is
selected on line 7710, the
pump should start to run.
● Check that speed control
works correctly by
repeating the test with
different speed settings on
line 7710 (for example, to
100%, 50%, and 0%).
Relay test for a speed controlled brine circuit pump
Line Connector Output
Function
Marking
Additional information
7700
U
QX12
Brine circuit pump Q8
Q8
7716
y
UX2
Output test UX2
UX2
When the test is switched
on and the desired speed is
selected on line 7716, the
pump should start to run.
● Check that speed control
works correctly by
repeating the test with
different speed settings on
line 7716 (for example, to
100%, 50%, and 0%).
M8009 2147EN
35 (74)
Summary of Contents for Lampoassa RE 28-48
Page 1: ...M8009 2147EN 25 October 2021 Installation and operation manual RE 28 48 RE 56 96...
Page 2: ......
Page 45: ...RE 04 dimensions single unit configuration Two units M8009 2147EN 43 74...
Page 46: ...RE 04 dimensions two unit configuration 44 74 M8009 2147EN...
Page 61: ...7 4 EN 14285 Technical data sheets RE 28 RE 28 Technical data sheet ver 1 M8009 2147EN 59 74...
Page 62: ...RE 33 RE 33 Technical data sheet ver 1 60 74 M8009 2147EN...
Page 63: ...RE 38 RE 38 Technical data sheet ver 1 M8009 2147EN 61 74...
Page 64: ...RE 42 RE 42 Technical data sheet ver 1 62 74 M8009 2147EN...
Page 71: ...Wilo Stratos 40 1 12 Wilo Yonos MAXO 40 0 5 16 M8009 2147EN 69 74...
Page 77: ......