7
10090943EN
3.3. General
•
burner
types:
• without preheating
Junior Pro 1
J10
J18
Junior Pro 2
J20
J45
J50
• with preheating
Junior Pro 1
LJ10
LJ18
Junior Pro 2
LJ20
LJ45
LJ50
•
the burner can be hinged to both sides
•
the standard burner must be installed in such a position, that the motor shaft lies
horizontally; but the burner must not, however, be installed upside down. In the case the
burner must be installed upside down, a separate installation set with instructions must be
ordered from the manufacturer.
•
burner control unit internally connected
•
safety switch (limit switch) on the hinged burner housing
•
stepless adjustable air regulation
•
oil pump atomizing pressure 800 - 1400 kPa (8 - 14 bar), factory setting approx. 10 bar
•
electrical connection with a plug connector
•
standard equipment for two pipe system
•
recommended nozzle types:
- solid 45° - 60° (Junior Pro 1 J10, J18, LJ10, LJ18)
- solid 60° (Junior Pro 2 J20, J45, J50, LJ20, LJ45, LJ50)
•
NO
x
-class 2
Optional extra
•
boiler dual thermostat
- regulating thermostat max. 95 °C
- limit thermostat 100 °C
•
pocket for thermostat
•
run hour counter
•
deaerator
Tigerloop
•
oil flow meter
•
Oilon Plus filter and deaerator unit:
-
filter
-
deaerator
- pressure gauge
- protective cover
- multi-function meter, optional extra