9
10090943EN
4. Burner
Installation
4.1. Burner
Mounting
The furnace, which has a flame-shaped design, does not require refractory. Boilers without
bottom cooling require refractory to prevent heat from reaching boiler foundations.
The flame must at no point come into contact with the furnace walls. If this cannot be avoided,
such points must be covered with refractory. This applies especially to the refractory at the back
wall of short furnaces.
1 Mounting plate 5 - 7 mm
2 Gasket 3 - 5 mm
3 Thermal insulation
approx. 50 mm
The mounting plate must have either two M10 threaded holes or four M8 threaded holes for the
mounting of the burner according to the drawing.