18
◎
Replacement fan
Applicable COOLCABI
models
Model
Internal fan
External fan
OCA-S2300AC-A200
FM-2300ACIN
FM-2300ACOUT
OCA-S3000AC-A200
FM-3000ACIN
FM-3000ACOUT
6-4 Troubleshooting
Failure
Cause
Remedy
- Internal
temperature
rises too much
- Cool air is not
blown out
- Display shows
High Temp.
Alarm E1 or
Radiation
Error Alarm E3
a.
Circuit breaker tripped
b.
Internal temperature is
lower than the setting
temperature.
c. Less cooling capacity against
the set value.
d.
Ambient temperature is
too high
e.
Internal temperature is
too high.
f.
Filter is dirty
g.
External fan is not running
h.
Internal fan is not running
i.
Poor air circulation
a.
Turn on the breaker
b.
Check the temperature
setting and the internal
temperature.
c.
Set a higher value, or change
the cooling unit with a one
of higher capacity.
d.
This unit is unusable under
a circumstance where the
ambient temperature may
exceed 50
℃
.
e.
This product cannot be
used where temperature
exceeds 45
℃
.
f.
Clean the filter.
g.
Check temperature
setting and the internal
temperature. In case of
fan failure, replace the fan.
h.
To check whether the fan
works properly, execute
forcible cooling
(See 4-4 of page 9).
If it did not run, fan
replacement is necessary.
i.
Remove the problem
referring to the page 3.
- Fall in internal
temperature is too
much
a. Setting temp. is too low
b. Failure in the internal circuit
or the temperature sensor
a.
Change the setting.
b.
Contact the supplier.
-Drainage error
occurred.
(Display shows E6)
Drainage is stagnant.
Check the drain hose
for clogging or bending.
- Too much
condensation
Control panel is not
airtight enough
Seal gaps to
improve airtightness
- Display shows E5 Built-in temperature
sensor breakage
Contact the supplier.
- Display shows E7 Internal fan is not running
Replace the fan.
- Display shows E8 Heat exchanger temperature
sensor failure.
Contact the supplier.
- Display shows SE Memory breakage
Contact the supplier.
- Display shows tE
Contact the supplier.
Note: In case any problem is found during operation, turn off the power and stop using the
product and contact your supplier providing information including the model and the
purchasing date of your unit.
Summary of Contents for COOL CABI OCA-S2300AC
Page 1: ...OCA S2300AC OCA S3000AC...
Page 2: ...2 20 50 85 RH 70...
Page 3: ...3 2 200mm 30 90 90 90 200 200...
Page 4: ...4 P 5 OCA S2300AC A200 OCA S3000AC A200...
Page 5: ...5 OCA S2300AC A200 OCA S3000AC A200...
Page 6: ...6 50cm 50cm 50...
Page 7: ...7 10 AWG24 12 0 2 2 5mm2 6 7 a 240V 1 5A 2 P 11 12 R S T E 1 2 3 AC200V IN...
Page 8: ...8 OCA S2300AC A200 OCA S3000AC A200...
Page 13: ...13 35 5 35 30 4 P 12 3 30 1 30 5 35 30 ON OFF ON OFF 35 30 ON OFF ON OFF...
Page 14: ...14 7 3 5 5 35 30 ON OFF ON OFF 30 35 45 ON OFF ON OFF...
Page 15: ...15 45 P 12 43 P 12 Set 3 P 12 Set 1 P 12 P 12 0 P 12 Set 3 OCA S2300AC A200...
Page 16: ...16 P 12 OFF 1 1 OCA S2300AC OCA S3000AC...
Page 18: ...18 50 45 P 9 P 3 OFF 7 5kW 1 4 P9 4 4...
Page 20: ...20 OCA S2300AC A200 OCA S3000AC A200 1 M8 4 M8 4 M8 4 M8 4 1 5m 2 1 1 1 1...
Page 21: ...21 OCA S2300AC A200 OCA S3000AC A200 2 8 13 2 8 13 2 12 1 12 2 12 1 12...
Page 22: ...22 1 13 64 19 10 4 431 1304 7000 21 TEL 053 522 5572 FAX 053 522 5573 7 2019 5...
Page 27: ...5 Cutouts View from outside the panel OCA S2300AC A200 OCA S3000AC A200...