21
Cool only control:ON-OFF control, P ( PD ) control and PID control can be used for cooling control. Set OUT1
to DIRT (direct action). The other functions for cool only ON-OFF control, cool only P ( PD ) control and cool
only PID control are the same as the descriptions for heat only control except that the output variable (and
action ) for the cool control is inverse to the heat control.
Cool only control:
NOTE : ON-OFF control may result excessive overshoot and undershoot problems in the process. The P (or PD )
control will result in a deviation of process value from the set point. It is recommended to use PID control for the
Heat-Cool control to produce a stable and zero offset process value.
CYC1, CYC2, O1FT, O2FT O1TY & O2TY parameters are set in accordance with the types of
OUT1 & OUT2 installed. CYC1 & CYC2 are selected according to the output 1 type ( O1TY ) & output 2 type ( O2TY )
Generally,
select 0.5 ~ 2 sec. for CYC1;
10 ~ 20 sec;
and
CYC1 is ignored. Similar settings are applied for CYC2 selection.
Other Setup Required :
Cycle Time:
if SSRD or SSR is used for O1TY,
if relay is used for O1TY, select
if linear output is used,
NOTE :
Other Setup Required :
Cycle Time:
You can use the
program for a new process or directly set the appropriate values for PB, TI & TD
according to the historical records for the repeated systems. If the control behavior is still inadequate, then use
to improve the control. See
for manual tuning.
auto-tuning
manual tuning
section 3-12
auto-tuning
manual tuning
section 3-12
CPB Programming : The cooling proportional band is measured by % of PB with range 50~300. Initially set 100% for
CPB and examine the cooling effect. If cooling action should be enhanced then decrease CPB, if cooling action is too
strong then increase CPB. The value of CPB is related to PB and its value remains unchanged throughout the auto-
tuning procedures. Adjustment of CPB is related to the cooling media used. For air used as a cooling media, adjust
CPB to 100(%).For oil is used as a cooling media, adjust CPB to 125(%). For water used as cooling media, adjust
CPB to 250(%).
CPB Programming :
DB Programming: Adjustment of DB is dependent on the system requirements. If more positive value of DB ( greater
dead band between heating and cooling ) is used, an unwanted cooling action can be avoided but an excessive
overshoot over the set point will occur. If more negative value of DB ( greater overlap ) is used, an excessive
overshoot over the set point can be minimized but an unwanted cooling action will occur. It is adjustable in the range
-36.0% to 36.0 % of PB. A negative DB value shows an overlap area over which both outputs are active. A positive DB
value shows a dead band area over which neither output is active.
DB Programming:
Output 2 ON-OFF Control ( Alarm function ):
DE.HI
DE.LO
DB.HI
DB.LO
PV.HI
PV.LO
Figure 3.3
Figure 3.4
The output 2 can also be configured as alarm function. There are 6 kinds
of alarm functions can be selected for output 2, these are:
(deviation high alarm ),
(deviation low alarm ),
(deviation band out of band alarm),
(deviation band in band alarm),
(process high alarm ) and
( process low alarm ). Refer to
and
for the description of deviation alarm and process
alarm with normal alarm mode ( NORM is set for ALMD ).
Output 2 ON-OFF Control ( Alarm function ):
DE.HI
DE.LO
DB.HI
DB.LO
PV.HI
PV.LO
Figure 3.3
Figure 3.4