11
•
Included accessories 1pcs (Details refer to the "Accessories list" file shipped with the inverter/charger.)
2.2.2
Prepare modules
1)
Battery
Recommended wire size of the battery and the circuit breaker is as below.
Model
Battery wire size
Circuit breaker
Ring terminal
UP3000-HM10022
35mm
2
/1AWG
2P—200A
RNB38-8S
UP5000-HM8042
35mm
2
/1AWG
2P—200A
RNB38-8S
Making the battery connection wire
Step1:
Ring terminal 2pcs (included accessories).
Step2:
Battery positive and negative connection wires 2 pcs(red +, black -). The wire length is determined
according to the customer's actual requirement.
Step3:
Strip one end of the battery connection wire for about d mm (size d is determined according to the ring
terminal).
Step4:
Pass the exposed wire through the ring terminal, and secure the wire firmly with a wire clamp.
2)
AC Load
Recommended wire size of the AC load and the circuit breaker is as below.
Model
Load wire size
Circuit breaker
Torque
IC-24/3000/100/80
4mm
2
/11AWG
2P—25A
1.2N.M
IC-48/5000/80/60
6mm
2
/9AWG
2P—40A
1.2N.M
Making the connection wire of the AC load:
Strip the AC load connection wires (3 pcs) for about 10 mm.
Symbols
Abbreviation
Name
Color
L
LINE
Live wire
Brown/black
N
Neutral
Neutral line
Blue
—
Ground line
Yellowish green
3)
PV modules
Recommended wire size of the PV module and the circuit breaker is as below.