3) Connect the battery
WARNING
A circuit breaker must be installed on the battery side. For selection, please refer to chapter
"
".
CAUTION
When wiring the battery, please do not close the circuit breaker and ensure that the
leads of "+" and "-" poles are connected correctly.
A circuit breaker current is 1.25 to 2 times the rated current must be installed on the
battery side away from the battery not longer than 200mm.
Connection sequence of the battery
Step1:
Remove the screw of the inverter/charger positive terminal with a sleeve, the torque of which is 3.5N.M.
Step2:
Connect the ring terminal of the battery connection wire to the inverter/charger's positive terminal.
Step3:
Install the screw and secure it with the sleeve.
Step4:
Connect and secure the negative terminal of the inverter/charger following the step1~step3.
4) Connect the AC load
WARNING
Risk of electric shock! When wiring the AC load, please do not close the circuit breaker
and ensure that the poles leads are connected correctly.
If utility input exists, the inverter/charger must be connected to the ground terminal.
We do not assume any responsibility for the unnecessary danger when the ground
terminal is not connected correctly.
Silk-screen
Abbreviation
Name
Color
L
LINE
Live wire
Brown/black
N
Neutral
Neutral line
Blue
—
Ground line
Yellowish-green