Operation
OPM223/253
54
R253
Enter pre-rinse time
20 s
0 ... 999 s
Rinsing with water takes place.
R254
Enter cleaning time
10 s
0 ... 999 s
Cleaning with cleaning agent and water
takes place.
R255
Enter post rinse
time
20 s
0 ... 999 s
Rinsing with water takes place.
R256
Enter number of
repeat cycles
0
0 ... 5
R253 ... R255 is repeated.
R257
Enter pause time
360 min
1 ... 7200 min
The pause time is the time between two
cleaning cycles (see "Timer function"
section).
R258
Enter minimum
pause time
120 min
1 ... R257 min
The minimum pause time prevents
constant cleaning if an external cleaning
start is present.
R259
Enter number of
cleaning cycles
without cleaning
agent (economy
function)
0
0 ... 9
After cleaning with cleaner, up to 9
cleaning sessions can be carried out
with water only until the next cleaning
session with cleaner takes place.
R2 (6)
Configure
neutralisation
controller
LC PV = limit contactor pH/
ORP (1)
LC C = limit contactor T (2)
PID controller (3)
Timer (4)
Clean = Chemoclean (5)
Neutra controller (6)
Only for A1 = pH.
If neutra controller is selected for Rel1,
only neutra controller is offered for Rel2.
By confirming with ENTER, another
relay function already switched on is
switched off and its settings are reset to
the factory settings.
R261
Switch function of
R2 (6) off or on
Off
On
Coding
Field
Setting range
(Factory settings, bold)
Display
Info
R253
s
PreRinse
20
R254
s
CleanTime
10
R255
s
PostRinse
20
R256
Rep
.
Rate
0
R257
min
PauseTime
360
R258
min
Min
.
Pause
120
R259
EconomyCl
0
R2
Sel
.
Type
Neutr
R261
Function
off