OPM223/253
Operation
37
O312
0/4 mA value:
Enter associated
pH (ORP or
temperature value
pH 2.00
pH -2.00 ... 16.00
-1500 mV
-1500 ... 1500 mV
0.0 %
0.0 ...100.0 %
0.0 C
-20 ... 150.0 C
Here you can enter the measured value
at which the min. current value (0/4 mA)
is applied at the transmitter output.
(Spreading: see Technical data.)
O313
20 mA value:
Enter associated
pH (ORP) or
temperature value
pH 12.0
pH -2.00... 16.00
1500 mV
-1500 mV ... 1500 mV
100.0 %
0.0 ...100.0 %
100.0 C
-20.0 ... 150.0 C
Here you can enter the measured value
at which the max. current value (20 mA)
is applied at the transmitter output.
(Spreading: see Technical data.)
O3 (2)
Simulate current
output
Lin = linear (1)
Sim = simulation
(2)
Tab = table (3)
Simulation is not ended until (1) or (3) is
selected.
For further characteristics, see O3 (1),
O3(3).
O321
Enter simulation
value
Current value
0.00 ... 22.00 mA
Entering a current value results in this
value being directly output at the current
output.
O3 (3)
Enter current output
table (only for Plus
Package)
Lin = linear (1)
Sim = simulation (2)
Tab = table
(3)
Values can also be added or altered at a
later stage. The values entered are
automatically sorted by increasing
current value.
For further characteristics, see O3 (1),
O3 (2).
O331 Select table options
Read
Edit
O332
Enter number of
table value pairs
1
1 ... 10
Enter the number of pairs from the x
and y value (measured value and
current value) here.
O333
Select table value
pair
1
1 ... No. elem.
Assign
O334 Enter x value
pH 0.00
pH -2.00 ... 16.00
0 mV
-1500 ... 1500 mV
0.0 %
0.0 ... 100.0 %
x value = measured value specified by
user.
Coding
Field
Setting range
(Factory settings, bold)
Display
Info
pH
O312
0
/
4 mA
2
.
00
pH
O313
20 mA
12
.
00
O3
Sel
.
Type
sim
O321
mA
Simulat
.
10
.
20
O3
Sel
.
Type
table
O331
Sel
.
Table
read
O332
No
.
Elem
.
1
O333
Sel
.
Elem
.
1
O334
pH
Meas
.
val
.
0
.
00
Summary of Contents for OPM223
Page 2: ......
Page 95: ...OPM223 253 Technical data 95...
Page 100: ...Appendix OPM223 253 100...
Page 103: ...OPM223 253 103...
Page 104: ...BA194e 00 07 09 71106576 Printed in Germany FM SGML 6 0 DT 71106576...