Use and Maintenance Manual
DIAM3200
28
Page 1: ...Use and Maintenance Manual ocem EN 3f5fce93 e8c9 4dd7 bbfa 15aabef6433c Stackable Constant Current Regulator IGBT UT MT 0938_1 0_30 03 2023 EN...
Page 2: ...third parties on each registered trade mark mentioned in this document are the property of their respective owners The copyrights of this manual are the property of OCEM AirfieldTechnology The instruc...
Page 3: ...ral characteristics 11 2 2 Operating principle 12 2 3 Reference standards 13 2 4 Nb of steps 13 2 5 Supply voltage 14 2 6 Nominal power 14 2 7 Wired remote control 14 2 8 Communication network 14 2 9...
Page 4: ...peration mode 30 4 3 Navigation map 31 4 4 Local monitoring 32 4 5 Warning fault and alarm messages 33 4 6 Troubleshooting 34 4 7 Access to the parameters 35 4 8 Edit parameters 36 4 9 Software config...
Page 5: ...sources before performing operations on the device Allow adequate discharging time for any residual energy before accessing the device Use a suitable measuring instrument to check for residual voltage...
Page 6: ...ability of the DSP processor allows it to be adapted to any type of load LED fixtures halogen fixtures electronic converters or combined systems The CCRs DIAM3200 of OCEM Airfield Technology perform a...
Page 7: ...ese precautions safeguard the personal security of everyone who work on and or are in proximity of the equipment and of the relative supply circuits The failure to comply with the instructions in part...
Page 8: ...g out maintenance or repair 1 7 Definition of operator All operations on devices and on its internal parts must be performed by professional staff properly formed and aware of the risks connected with...
Page 9: ...eplace the components in the shortest possible time without prejudice to the fact that for the so called commercial components and more generally for the components supplied by third party manufacture...
Page 10: ...correspondence received by the Supplier or in any case assimilated or gained during the conclusion of the Contract of sale Any right regarding intellectual and industrial property connected to equipme...
Page 11: ...pliant with the rules IEC 61822 Edition 2 0 AENA DIN DNYM PPT 002 05 13 The DIAM3200 constant current regulators described in this manual have been designed to be installed on the levelled floor with...
Page 12: ...field Optional devices perform control and monitoring of the operating parameters disconnection manoeuvres of the output circuit to the load and input overvoltage protection simplifying the operation...
Page 13: ...nfigurable in the range 1 8 6 6 A to meet different end user requirements According to IEC 61822 the nominal output current range is Type 1 from 4 8 to 6 6 A Type 2 from 2 8 to 6 6 A The table provide...
Page 14: ...r through wired connector 32 PIN 2 8 Communication network The constant current regulators can be equipped with different communication interfaces depending on requirements One or more RJ45 or D Sub 9...
Page 15: ...max 6 3 Stacked setting up S2 S3 2 CCR ICS possible connected to lower CCR 3 CCR ICS not possible Particular equipments4 DTxxxx Specifications project identification code 1 Always check the compatibil...
Page 16: ...ates whether the power supply value Ui allows the device to function properly When the input voltage value goes out of the rated input voltage operating range Uin 15 20 and remains outside the range f...
Page 17: ...esigned for airport installations and safety critical systems The cables necessary for the functioning of the unit are not included in the supply It is the customer s responsibility to arrange appropr...
Page 18: ...Page intentionally left blank UT MT 0938_1 0_30 03 2023 EN Use and Maintenance Manual DIAM3200 18...
Page 19: ...the supply circuits and for the series circuits refer to the requirements of the relevant Standards For the conformity of the light fixtures supplied by the constant current regulators through the se...
Page 20: ...and must be requested in the article code when ordering Maintain a free space of at least 20 cm at the rear side of the unit to ensure proper ventilation of the device Before proceeding with the opera...
Page 21: ...ich the device must be integrated before installing the constant current regulator The power supply line must be suitably dimensioned and adequately protected Only use the device in combination with s...
Page 22: ...d check using appropriate instruments that there are no residual energies before accessing the electrical equipment Open the rear panel and make the electrical connection to the prepared power supply...
Page 23: ...s before accessing the electrical equipment Prepare the series circuit cables for connection and connect the terminal to the conductor Remove the transparent protection from the terminals and make the...
Page 24: ...ion for remote control varies depending on the configuration of the device The connections are available on the back of the unit Connect the prepared cables to the respective doors of the device The u...
Page 25: ...fore the circuit changeover occurs in order to prevent transitory overcurrents from drastically reducing the life of the powered lamps The unit must also stop the supply when the selector panels are o...
Page 26: ...document ES MT 0113 accompanying the CUT OUT device Energise the supply line of the unit Act on the main switch and activate the unit The unit activates and the output current value is shown on the d...
Page 27: ...3 accompanying the CUT OUT device Energise the supply line of the unit Act on the main switch and switch on the unit The unit starts and stops within 0 3s after the start of the supply The constant cu...
Page 28: ...Page intentionally left blank UT MT 0938_1 0_30 03 2023 EN Use and Maintenance Manual DIAM3200 28...
Page 29: ...tor powered the display switches on the system is initialized and the device will revert to STOP mode the controller s control system is active but the series circuit is disconnected During operation...
Page 30: ...the LOCAL button P2 to select the local control mode The display shows the current level delivered and the operator can manually select a different level by pressing the B P2 2 and B P2 3 buttons dep...
Page 31: ...23 EN Use and Maintenance Manual DIAM3200 31 4 3 Navigation map During operation the display always shows the output current and a second parameter selectable as desired by the user Bx level of bright...
Page 32: ...s of the main quantities measured by the system Uo output voltage expressed in Vrms Po output power expressed in kVA Ui input voltage expressed in Vrms Earth Fault insulation resistance value expresse...
Page 33: ...faulty not present Regulation error the measured values exceed the limits IBnMIN IBnMAX defined for each available setting B0 B7 Power Drop indicates a sudden drop in output power of more than 10 Temp...
Page 34: ...vice If necessary consult the manual to identify the problem and the possible causes of failure Eliminate the problem and press the RESET button P1 to restore the system A system reset is only possibl...
Page 35: ...Enabling the change function and updating the values is only possible with the system energised in STOP mode To enable access to parameters press the MENU access button P4 press the navigation buttons...
Page 36: ...r access option enabled To modify the parameters press the MENU access button P4 press the navigation buttons P4 2 and P4 3 and select the desired function see parameter diagram press the confirmation...
Page 37: ...configuration values The unit is supplied with a pre set of parameters in accordance with the machine configuration The parameter diagram with suggested configuration values is presented below Please...
Page 38: ...INTENANCE UT MT 0938_1 0_30 03 2023 EN Use and Maintenance Manual DIAM3200 38 Please check the actual configuration of the device Some parameters may not be available if the relevant option is not pre...
Page 39: ...INTENANCE UT MT 0938_1 0_30 03 2023 EN Use and Maintenance Manual DIAM3200 39 Please check the actual configuration of the device Some parameters may not be available if the relevant option is not pre...
Page 40: ...INTENANCE UT MT 0938_1 0_30 03 2023 EN Use and Maintenance Manual DIAM3200 40 Please check the actual configuration of the device Some parameters may not be available if the relevant option is not pre...
Page 41: ...re available for download from the link on the manufacturer s website http www augier com soft ALIZE4100 exe Before installing the software read and accept the licence conditions and check that the mi...
Page 42: ...cessary corrective procedures must be activated to restore and ensure operative safety levels foreseen by the standards Do not let running devices not properly maintained or fixtures presenting signs...
Page 43: ...discharging time at least 5 min and check using appropriate instruments that there are no residual energies before accessing the electrical equipment When necessary perform corrective maintenance pro...
Page 44: ...ain thermal magnetic circuit breaker CB Q1 11 EMC filter 12 power contactor KM 13 power module complete with fans 14 power supply autotransformer 15 wired remote control board IEC AENA optional for mo...
Page 45: ...the event of the supply voltage When switching the unit back on proceed to resolution and restoration of all messages in the memory 4 12 1 Fault of the supply line Problems Possible causes Possible s...
Page 46: ...supply to stop 1 Check the OPEN CIRCUIT parameter setting in the ALARM AND WARNINGS menu If necessary use the ALIZE 4100 software If after trying the proposed solutions the problem persists contact OC...
Page 47: ...STIC function of the ALIZE 4100 software If necessary replace the board The constant current regulator cannot be operated remotely REMOTE mode The remote control interface board protections have tripp...
Page 48: ...cuit If necessary replace the damaged components An error has occurred in the configuration of the tripping thresholds 1 Check the EARTH FAULT DETECTION parameter setting in the WARNING AND ALARMS 2 m...
Page 49: ...l correctly phased If necessary change the position of the connection cables 2 Run the BURNT LAMP learning function again The display shows one of the following messages ALARM BAD Interface The consta...
Page 50: ...esholds provided only AENA specifications 1 If required by the regulatory context the information is to be considered a caution message Check the environmental conditions see AENA specifications The d...
Page 51: ...ADJUSTMENTS AND MAINTENANCE UT MT 0938_1 0_30 03 2023 EN Use and Maintenance Manual DIAM3200 51 Identifying mother board components Identifying measurement board components...
Page 52: ...parts Always check the version of the device you have and any options accessories present Constant current regulator DIAM3200 A Front segregation B Rear segregation Accessories Code Art Fixed wheels...
Page 53: ...38 40 41 02 10 25250 IEC AEN 22 23 24 05 10 25254 IEC AEN 38 40 41 05 10 25251 IEC AEN 22 23 24 06 10 26780 IEC AEN 38 40 41 06 10 25253 2 EMC filter IEC AEN 22 23 24 30 10087 IEC AEN 38 40 41 30 100...
Page 54: ...ADJUSTMENTS AND MAINTENANCE UT MT 0938_1 0_30 03 2023 EN Use and Maintenance Manual DIAM3200 54 Pos Description Product Code Code Art 5 Power module IEC AEN 22 23 24 718 3110 IEC AEN 38 40 41 718 3111...
Page 55: ...1 FU2 always valid 10 27584 8 Membrane keyboard always valid 10 20483 9 Display always valid 30 12449 10 EFD board always valid 30 10029 11 Measurement board always valid 30 08004 12 Interface board a...
Page 56: ...16 Power transformer T1 IEC AEN 22 23 24 02 10 24847 IEC AEN 38 40 41 02 10 26711 IEC AEN 22 23 24 05 10 26712 IEC AEN 38 40 41 05 10 26713 IEC AEN 22 23 24 06 10 26725 IEC AEN 38 40 41 06 10 26726 1...
Page 57: ...Contact us OCEM AT 4 3 39 051 66 56 611 4 4 info ocem com...
Page 58: ...ocem OCEM AT a division of ENERGY TECHNOLOGY S r l Via della Solidariet 2 1 40056 Valsamoggia Bologna Italy Stackable Constant Current Regulator IGBT UT MT 0938_1 0_30 03 2023 EN...