INSTALLATION—PERMANENTLY CONNECTED
The CAC power cord can be removed and permanently connected to a power source. Once the
CAC is installed and secured for a stationary installation, the unit can be permanently wired.
1. Remove the left side panel and locate the power cord/strain relief at the rear of the unit.
2. Disconnect the power cord from the ground lug and terminal strip.
3. Remove the power cord and the strain relief.
4. Install 1/2” conduit and a UL recognized bushing through the 7/8” DIA. CONDUIT PORT, and
secure.
5. Three (3) conductors, a minimum of 14 AWG, are required for LINE, COMMON, and
GROUND, can then be connected to the unit.
6. A dedicated electrical circuit (115 VAC...60HZ...Single Phase) rated @15 amps is needed.
LCDI
POWER
CORD
LEFT SIDE
PANEL
CONDUIT
PORT
CAC1211
COMMON
LINE
GROUND
LUG
7/8” DIA.
CONTROL BOX - FIELD WIRING
USE COPPER
CONDUCTORS ONLY