EÜK screed-covered duct system
Preparations for mounting
4
Preparations for mounting
4.1
Calculation of the duct lengths
During the planning and determination of the effective cable
lengths of the underfloor installation ducts
2
, the following deduc-
tion dimensions should be taken into account.
Note!
The deduction dimensions are always measured from duct stop to
duct stop (see detailed view in Fig. 3).
Article
Type
Deduction
dimension A
Vertical bend
VK...
200 mm
Underfloor junction box/underfloor
device socket
UGD/UZD 250
UGD/UZD 350
280 mm
380 mm
Connection shackle
VL...
10 mm
Fig. 3:
a
A 380
A 280
A VL
UZD
UGD
250
UZD
UGD
350
A 380
10
Deduction dimensions
Legend
a
Distance from socket centre to socket centre
A 280
Deduction dimension to
UGD/UZD 250
A 380
Deduction dimension to
UGD/UZD 350
A VL
Deduction dimension, connection shackle
Example
a
=
2,500 mm
A 250
=
280 mm
A 350
=
380 mm
A VL
=
10 mm