Kalix Sanitisation Procedure
.
TECHNICAL
BULLETIN
OAS0033A
181218
OAS0033A
3
Diagram 5.1
Diagram 5.2
5.
Remove drain plug and Empty Cold tank.
•
Looking down on the unit, (Diagram 6.1) disconnect the cold water inlet as shown.
Diagram 6.1
•
Open the drain valve at the rear of the unit. The drain is located 280mm from the floor
–
ensure that you place a container under the valve prior to opening it. The container must
have a minimum capacity of 2 liters.
•
Re-attach inlet tube and drain valve, once cooling tank is empty.
6.
By-pass any filter system that is installed in the cooler.
•
Disconnect & Dispose of the blue tube from the bulk head fitting at rear of the cooler, to the
inlet side of filter system, and from the outlet side of the filter to the Tee connection located on
the shelf.