O&O LOG-BC Installation And Operation Manual Download Page 13

- 13 -

FOTO   

 

 

 

 

 

 

 

 

Safety input with NC contact.  During closure, when the photocell ray  is interrupted, it immediately opens the gate again.

If this input is kept open by a clock or weekly timer, the automation system closes again after the pause time, if programmed, 

and only once the entrance is clear.

STOP   

 

 

 

 

 

 

 

 

NC safety input. When this is activated it stops the automation instantly and when a start command is then given the gate 

will always open. If a stop command is given during pause time it eliminates automatic re-closing, waiting for a command.

START   

 

 

 

 

 

 

 

NO input, allowing the open and close signals to be sent to the automation system. This input is ignored during the opening cycle.

If this input is commanded continuously, the automation system performs the opening cycle and, if the pause time is pro-

grammed and only once the entrance is clear, the automatic closing cycle.

AP.PD.    

 

 

 

 

 

 

 

The command is accepted only if the barrier is completely closed, and automatic closing is temporarily disabled during the 

opening cycle. Use in accordance with the automatic logic of the start command (DIP 1-2 ON).

APRE   

 

 

 

 

 

 

 

Encoder input SGN-2.

CHIUDE

NO input for closing. To close the automation only if the safety devices have not triggered.

6.2 

M2

 INPUTS CONTROL TERMINAL BLOCK

7. DIP SWITCH CONFIGURATION

 

 

 

 

 

 

Dip switches 1 and 2:  They select the functioning logic

Off-Off:

 Hold-to-run logic.

   

The automation works by keeping the commands pressed, acting on the open or close inputs.

   

The start command opens once and closes once.

Commands via radio in the hold-to-run logic are forbidden by law.

On-Off

:  SEMI-AUTOMATIC (Logic for pulse type collective control)

   

Open command only. To close after opening, press start or close. Pressing during closing cycle reopens 

the barrier.

On-On

:  AUTOMATIC (Logic for pulse type collective control)

   

Open command only. Pressing start when paused closes barrier, pressing while barrier is closing opens 

barrier. Barrier is closed after pause time.

Dip switch 3: Selects pre-flashing function.

Off: 

The pre-flashing function is disabled: the flashing unit is commanded during the manoeuvre.

On:

 The warning lamp flashes for a period from 2 to 10 seconds (settable from trimmer PM1) before all mano-

euvres except barrier inversion triggered by the safety devices.

ST

OP

COM

FOT

O

COM

ST

ART

COM

AP

. PD

COM

APRE

COM

CHIUDE

COM

8. PROGRAMMING

8.2 CHAIN HEIGHT ADJUSTMENT

1) Switch automation system off and on.
2) Set trimmer PM2 (chain dip setting) to the middle setting.
3) Press start and wait. The automation system performs the reset procedure.
4) At the end of the reset procedure, press START again and wait for the closing cycle to conclude. 
5) Adjust trimmer PM2 to set the desired chain height and perform an open cycle and a close cycle to check that the height is correct.

8.1 PRELIMINARY CHECKS

To guarantee the safety of the system, remember  that the automation must be checked according to the risk analysis, therefore the 

installer must install any safety accessories needed and resolve all residue risks and dangers that the machine may cause when it 

works automatically via the remote controls.

Summary of Contents for LOG-BC

Page 1: ...l Via Europa 2 42015 Correggio R E Italy Phone 39 0522 740111 Fax 39 0522 631290 Internet www oeo it E mail oeo oeo it Societ soggetta ad attivit di direzione e coordinamento di BFT S p a Company subj...

Page 2: ......

Page 3: ...6 2 M2 MORSETTIERA DI COMANDO INGRESSI 6 7 CONFIGURAZIONE DEI DIP SWITCH 6 8 PROGRAMMAZIONE 6 8 1 VERIFICHE PRELIMINARI 6 8 2 REGOLAZIONE ALTEZZA ALZACATENA 6 9 REGOLAZIONE DEI TRIMMER 7 10 RICEVENTE...

Page 4: ...cimento dell ostacolo La notevole disponibilit di logiche selezionabili consente di soddisfare anche particolari condizioni operative sugli impianti 1 INTRODUZIONE Alimentazione 230Vac 10 50 60 Hz 100...

Page 5: ...V Ingresso trasformatore a 230V 50 60Hz Collegare il polo di messa a terra presente nell apposito serrafilo Alimentare il motoriduttore tramite il morsetto a 2 vie protetto da fusibile 5x20 da 1 A Uti...

Page 6: ...estando in attesa di comandi START Ingresso N O che consente di inviare il comando di apertura e chiusura all automazione ma viene ignorato durante l apertura Mantenendo comandato questo ingresso l au...

Page 7: ...GNARE IL PRIMO TRASMETTITORE MEMORIZZATO CON IL BOL LINO CHIAVE MASTER Il primo trasmettitore nel caso di programmazione manuale assegna il codice chiave al ricevitore questo codice risulta necessario...

Page 8: ...8...

Page 9: ...i apportare modifiche in qualsiasi momento senza preavviso alcuno 12 RISOLUZIONE DEI PROBLEMI 1 Al termine della manovra di chiusura la catena scende di qualche centimetro Al termine della prima manov...

Page 10: ...INPUTS CONTROL TERMINAL BLOCK 13 7 DIP SWITCH CONFIGURATION 13 8 PROGRAMMING 13 8 1 PRELIMINARY CHECKS 13 8 2 CHAIN HEIGHT ADJUSTMENT 13 9 SETTING THE TRIMMERS 14 10 RADIO RECEIVER 14 10 1 RECEIVER T...

Page 11: ...he obstacle Thanks to the considerable amount of logic available even very particular operating conditions on sytems can be met 1 INTRODUCTION Power 230Vac 10 50 60 Hz 100W SCA output 24Vac 3 W Flashi...

Page 12: ...nge in series any contacts to be connected to the same NC input Arrange in parallel the inputs connected to the same NO input Keep radio control or other control devices out of children s reach in ord...

Page 13: ...inputs The start command opens once and closes once Commands via radio in the hold to run logic are forbidden by law On Off SEMI AUTOMATIC Logic for pulse type collective control Open command only To...

Page 14: ...xit memorizing mode wait for the LED to go off completely or press the key of a remote control that has just been memorized IMPORTANT NOTE ATTACH THE ADHESIVE KEY LABEL TO THE FIRST MEMORISED TRANSMIT...

Page 15: ...15...

Page 16: ...prior notice 12 TROUBLESHOOTING GUIDE 1 The chain drops by a few centimetres at the end of the close cycle At the end of the first close cycle the control unit determines the force necessary to be app...

Page 17: ...19 6 2 M2 BORNIER DE COMMANDE ENTREES 20 7 CONFIGURATION DES COMMUTATEURS 20 8 PROGRAMMATION 20 8 1 CONTR LES PRELIMINAIRES 20 8 2 REGLAGE DE LA HAUTEUR DE LA CHAINE 20 9 REGLAGE DES POTENTIOMETRES 21...

Page 18: ...sance de l obstacle Les nombreuses logiques s lectionnables permettent galement de r pondre des conditions sp cifiques de fonctionnement des in stallations 1 INTRODUCTION Alimentation 230Vca 10 50 60...

Page 19: ...viter des actionnements involontaires de la motorisation 1 2 3 4 5 6 7 8 9 10 11 LIGNE 230V Entr e transformateur 230V 50 60Hz Brancher le p le de mise la terre pr sent sur le serre fil pr vu cet eff...

Page 20: ...alternativement ouverture et fermeture Les normes en vigueur interdisent les commandes via radio en logique de fonctionnement homme pr sent On Off SEMI AUTOMATIQUE Logique collective pour commande imp...

Page 21: ...dre jusqu l extinction totale de la led ou bien appuyer sur la touche d une t l commande peine m moris e NOTE IMPORTANTE MARQUER LE PREMIER EMETTEUR MEMORISE AVEC L ETIQUETTE CLE MA STER Le premier me...

Page 22: ...22...

Page 23: ...la facult d apporter toute mo dification sans pr avis aucun 12 PROBLEMES ET SOLUTIONS 1 Au terme de la man uvre de fermeture la cha ne descend de quelques centim tres Au terme de la premi re man uvre...

Page 24: ...NBRETT 26 6 2 M2 EINGANGSVERWALTUNGSKLEMMENBRETT 27 7 KONFIGURATION DER DIP SWITCH 27 8 PROGRAMMIERUNG 27 8 1 VORBEREITENDE KONTROLLEN 27 8 2 H HENEINSTELLUNG DER KETTE 27 9 TRIMMEREINSTELLUNG 28 10 S...

Page 25: ...d Hinderniserfassung ausgestattet Die Vielzahl an einstellbaren Logiken erlaubt es auch besonderen Einsatzbedingungen an den Anlagen gerecht zu werden 1 EINLEITUNG Versorgung 230Vac 10 50 60 Hz 100W S...

Page 26: ...e von Kindern liegen lassen Sie k nnten die Anlage ungewollt in Gang setzen 1 2 3 4 5 6 7 8 9 10 11 LINIE 230V Eingang Transformator mit 230V 50 60Hz Verbinden die Erdungspol in dem Kabelklemme Getrie...

Page 27: ...wirkt ein ffnen und ein Schlie en Das Gesetz verbietet funkgesteuerte Befehle bei einer Logik Person anwesend On Off HALBAUTOMATISCH Logik f r die kollektive Impulssteuerung Nur ffnungsbefehl Am Ende...

Page 28: ...IGE ANMERKUNG KENNZEICHNEN SIE DEN ALS ERSTEN GESPEICHERTEN SENDER MIT DER SCHL SSELMARKE MASTER Der erste Sender weist bei der manuellen Programmierung dem Empf nger den Schl sselcode zu dieser Code...

Page 29: ...29...

Page 30: ...mpfohlen bei der Installation alle erforderlichen Teile zu verwenden die f r einen sicheren Betrieb gem den geltenden Gesetzen erforderlich sind Zu diesem Zweck sind immer Originalteile von O O zu ver...

Page 31: ...2 BORNERA DE CONTROL ENTRADAS 34 7 CONFIGURACI N DE LOS DIP SWITCH 34 8 PROGRAMACI N 34 8 1 VERIFICACIONES PRELIMINARES 34 8 2 REGULACI N ALTURA CADENA 34 9 AJUSTE DE LOS TRIMMER 35 10 RECEPTORA RADIO...

Page 32: ...nto de obst culos La gran disponibilidad de l gicas seleccionables permite satisfacer tambi n condiciones operativas particulares en las instalaciones 1 INTRODUCCI N Alimentaci n 230Vac 10 50 60 Hz 10...

Page 33: ...l alcance de los ni os para evitar el accionamiento involuntario del automatismo 1 2 3 4 5 6 7 8 9 10 11 L NEA 230V Entrada transformador de 230V 50 60Hz Conectar el polo de puesta a tierra presente e...

Page 34: ...a proh be comandos por v a radio en la l gica de hombre presente On Off SEMIAUTOM TICO l gica para mando de impulsos colectiva Mando de solo apertura al final de la apertura para cerrar es necesario a...

Page 35: ...SOR MEMORIZADO DEBE MARCARSE CON EL ADHESI VO DE LA LLAVE MASTER El primer transmisor en el caso de programaci n manual asigna el c digo clave al receptor este c digo resulta necesario para poder efec...

Page 36: ...36...

Page 37: ...el derecho de aportar modificaciones en cualquier momento sin ning n previo aviso 12 SOLUCI N DE PROBLEMAS 1 Al finalizar la maniobra de cierre la cadena baja varios cent metros Al finalizar la primer...

Page 38: ...O S r l Via Europa 2 42015 Correggio R E Italy Phone 39 0522 740111 Fax 39 0522 631290 Internet www oeo it E mail oeo oeo it NOTE NOTES REMARQUES ANMERKUNGEN NOTAS INSTALLATORE INSTALLER INSTALLATEUR...

Reviews: