NX Lighting Control Panel Relays

INSTALLATION INSTRUCTIONS

INSTALLING INDIVIDUAL RELAYS

The NX Panel can be configured with single and/or double pole mechanically latching relays pre-installed. If the project requires 

additional relays (and space is available in the panel), additional relays can be field installed as shown in Figure 2.

CAUTION! ALWAYS REMOVE POWER FROM THE NX PANEL’S TRANSFORMER PRIOR TO MAKING ANY ELECTRICAL CONNECTIONS 

INSIDE THE PANEL. FAILURE TO DO SO MAY RESULT IN PERSONAL INJURY, DAMAGE TO THE PANEL, AND VOID ITS WARRANTY.

1.  Verify that power is turned off at breaker panel before installing relay in panel.
2.  Remove panel door assembly from panel enclosure.
3.  Locate an open relay position (two adjacent positions for a double pole relay) in the panel and remove the relay guard cover(s).
4.  Insert relay into mounting bracket noting proper orientation of input/output sides. Verify that relay is securely held in  

mounting bracket.

5.  Connect relay input and output as shown in the wiring diagram below. Connect input to panel I/O control card using relay 

connector cable. Attach red lead to red screw and blue wire to blue screw. Slide connector on to header pins of I/O control card. 

Connect line and load leads to relay output.

Figure 2: Relay Wiring Diagrams

SIMLXRL1 - Simplicity LX Single Pole Relay

SIMLXRL2 - Simplicity LX Double Pole Relay

Installation Instructions

Hubbell Building Automation, Inc.

9601 Dessau Road • Building One • Suite 100

Austin, Texas 78754

512-450-1100 • 512-450-1215 Fax

www.hubbell-automation.com

Overview

This document provides instructions for installing and connecting Single and/or Double Pole Relays in the Simplicity LX Series Lighting

Control Panel.

Contents

These instructions include information as follows:

Description

General Precautions

Installation

Precautions

• Read and understand all instructions before beginning installation.

• For installation by a qualified electrician in accordance with National and/or local Electrical Codes and the following instructions.

RISK OF ELECTRICAL SHOCK.

  Turn power off at breaker panel before servicing unit.  Never wire energized electrical components.

Never operate unit with door panel or relay guards removed.

USE COPPER CONDUCTOR ONLY.

• Confirm that device ratings are suitable for application prior to installation.

• Use only approved materials and components (i.e. wire nuts, electrical box, etc.) as appropriate for installation.

NOTICE:

  Do not install if any damage to product is noticed.

Installation

1. Verify that power is turned off at breaker panel before installing relay in panel.

2. Remove panel door assembly from panel enclosure.

3. Locate an open relay position (two adjacent positions for a double pole relay) in the panel and remove the relay guard cover(s).

4. Insert relay into mounting bracket noting proper orientation of input/output sides.  Verify that relay is securely held in mounting bracket.

5. Connect relay input and output as shown in the wiring diagram below.  Connect input to panel I/O control card using relay connector

cable. Attach red lead to red screw and blue wire to blue screw.  Slide connector on to header pins of I/O control card.  Connect line and

load leads to relay output.

Figure 1: Relay wiring diagrams

Load

(to lighting system)

Load, Phase 2

(to lighting system)

Load, Phase 2

(from Circuit Breaker)

Load, Phase 1

(to lighting system)

Load, Phase 1

(to lighting system)

Blue Input Screw

Blue Lead

Red Input Screw

Red Lead

Relay Connector

I/O control

Card Header

(Polarized)

Blue Input Screw

Blue Lead

Red Input Screw

Red Lead

Relay Connector

I/O control

Card Header

(Polarized)

Line

(from Circuit Breaker)

Single Pole Relay

Double Pole Relay

6.  If necessary, reinstall relay guard covers over open relay positions.
7.  Re-install panel door assembly to panel enclosure.
8.  Reapply power to panel.
9.  Verify relay operation by manually switching relay on and off using the manual control switch located on the relay.

SPECIFICATIONS

CONSTRUCTION

Relay Dimensions

• Single Pole - L:106.5mm x W:24.5mm x 

H:60mm

• Double Pole – L:96mm x W:49.5mm x 

H:60mm*

MOUNTING

• Mounts directly to NX Lighting Control 

Panel V2 relay mounting strap

ELECTRICAL

Relay Operating Voltages

• Single Pole (p/n NXP2-RL-SP):

•  General Use: 20A @ 300VAC
•  Tungsten: 2400W @ 120VAC
•  (Standard) Ballast: 20A @ 300VAC
•  Electronic Ballast: 16A @ 277VAC
•  Motor Starting: ½ HP @ 110-125VAC; 

1.5HP @ 220-277VAC

ELECTRICAL (CONTINUED)

Relay Operating Voltages (Continued)

• Double Pole (p/n NXP2-RL-DP)*: 

•  General Use: 20A @ 480VAC
•  Tungsten: 2400W @ 120VAC
•  (Standard) Ballast: 20A @ 480VAC
•  Motor Starting: ½ HP @ 110-125VAC; 

1½ HP @ 220-277VAC

Relay Electrical Ratings

• Rated for minimum 60,000+ operations 

(30,000+ cycles) at full 20A load

• Short Circuit Current Rating (SCCR) of 

14,000A @ 277VAC

• Rated full-life with HID load

Relay Mechanical Ratings

• Rated for minimum 120,000+ operations 

(60,000+ cycles)

OPERATION

• Mechanically latching
• Provides at-a-glance indication of ON or 

OFF relay status

• Includes manual override switch 

(integral to the relay)

OPERATING ENVIRONMENT

•  Indoor use only
• 32° to 112°F (0° to 50°C)
• Relative humidity (non-condensing): 

10% to 90%

CERTIFICATIONS

•  UL Listed
•  CSA Approved

WARRANTY

•  5 year limited warranty
•  See 

HCS Standard Warranty

 for  

additional information

*Double pole relays occupy (2) relay spaces

701 Millennium Blvd. | Greenville, SC 29607 | (864) 678-1000 | hubbellcontrolsolutions.com

Copyright © 2021 Hubbell Control Solutions, a division of Hubbell Lighting, Inc. All rights reserved. All product and company names, logos and product 

identifiers are trademarks ™ or registered trademarks ® of Hubbell Lighting, Inc. or their respective owners. Use of them does not necessarily imply any 

affiliation with or endorsement by such respective owners. 

Reviews: