3

• Locate the power unit away from the general living area in an

accessible location for changing the soil bag and periodically
cleaning the secondary filter.

• When planning, remember the power unit is equipped with 

an inlet to service a garage, basement, utility room, etc.,
wherever it is located.

• Locate the power unit within six feet of a grounded electrical

outlet. The power unit requires a 240vAC, 15 amp circuit with
a NEMA 6-15R receptacle.

• Do not locate the power unit close to a source of extreme

heat (i.e., water heater) or in an area with a high ambient
temperature (i.e., attic, furnace room).

• If the power unit is located in a closet or a small utility room,

make sure the area is well-ventilated (i.e., with door louvers).

• Exhausting the power unit to the outside is recommended for

optimal performance but is not required. The exhaust should
not be vented into a wall, a ceiling or a concealed space in
the house. If the exhaust line is vented outside the home,
Model 393 Wall Cap or a roof vent are recommended.

WARNING: Power unit must not be mounted in a high
ambient temperature area such as attic, furnace room, etc.

TUBING AND WALL INLET LOCATIONS 

1.

Locate inlets on interior walls, choosing central locations
which allow several rooms to be cleaned from a single inlet
using a 30 foot long hose.

2.

The tubing installation should consist of a main trunk line
running from the farthest wall inlet to the power unit
location, with branch lines running to each additional inlet.
Keep all tubing lines as straight as possible and use as few
fittings as possible. Beginning at the area farthest from the
power unit, choose a tentative inlet location. Measure 30
feet from the proposed inlet location to the farthest corner of
the rooms to be cleaned by that inlet to determine if inlet
location is proper.

3.

If working from blueprints (or building plans drawn at 

1

4

" = 1 ft. scale), use a 7

1

2

" chain as your guide to

determine inlet locations.

4.

Move tentative inlet location if necessary. Use the same
procedure to determine each additional inlet location,
always working toward the power unit.

5.

Be sure tubing will not interfere with electrical, plumbing or
other mechanical installations.

6.

Locate inlets within six feet of an electrical receptacle to
allow use of optional current-carrying hose.

7.

Be sure inlets will not be blocked by doors or furniture.

LOCATING THE POWER UNIT

Built-In Appliances. 

You will often

find a hollow space behind built-in
kitchen appliances. If this space lines
up with an obstruction-free interior wall
above or a closet, this might be a key
to your installation. See Figure 5. 
You may also want to consider 
running exposed tubing through
cabinets or cupboards.

Cold-Air Return. 

A cold-air

return often provides a straight
run from basement to other levels
of the house. See Figure 6. 
The ductwork is easily cut for
access. Seal around the tube
when completing the installation.

FIGURE 5

FIGURE 6

LOCATING ACCESS KEYS IN 
EXISTING CONSTRUCTION

Let's say, for example, you have a two-story house and you want

to locate the power unit in the basement. If you can't find interior
walls on both the first and second floors which line up and are free
from obstacles. How do you get from the basement to the attic?

Unless your home is a ranch-style house where a single trunk

line can run directly through the attic or basement, you should first
investigate your house to find the key to running your tubing from
level to level. Look for an accessible area free from obstructions
that will accommodate the 2" tubing.

If you understand how your existing home is constructed, it can

be relatively easy to find access routes to run the tubing. Refer
again to the illustration on page 2 as you consider your home
construction.

Some of the keys you might find in your home are illustrated here.

FIGURE 4

Stacked Closets or Laundry
Chute. 

Many homes will have

an upstairs closet located
directly above a downstairs
closet. It is easy to run the
tubing from one floor level to
another inside these stacked
closets. In these installations
the tubing is often left exposed
inside the closets. See Figure
4. A laundry chute could also
provide access from basement
to upper floors.

TUBING

Summary of Contents for Advantage CV850

Page 1: ...alling the Tubing 5 Wall Inlet Installation Models CI370 360 Wall Inlets 6 Model 330 Wall Inlet 6 Model CI390 Wall Inlet Electrified Inlet 7 POWER UNIT INSTALLATION 8 Dimensional Chart 8 Mounting 8 Tu...

Page 2: ...TRUNK LINE INLET LINE INLET EXHAUST INTAKE POWER UNIT BASEMENT TRUNK LINE FIGURE 2 FIGURE 1 Like the two story house the split level installation commonly calls for a two level trunk line Here the po...

Page 3: ...procedure to determine each additional inlet location always working toward the power unit 5 Be sure tubing will not interfere with electrical plumbing or other mechanical installations 6 Locate inlet...

Page 4: ...lso be nailed to the front edge of the stud See face mounting illustrated For face mounting use locating tabs on bracket for proper alignment 4 Refer to Figure 8 Remove cardboard from plaster guard fr...

Page 5: ...r to Figure 13 Remove burrs from both inside and outside of tubing 10 Before cementing pre assemble section to inlet fitting check for proper length 11 Refer to Figure 14 Apply PVC cement Model 379 to...

Page 6: ...tor cable used to connect the inlet to the power unit does not have a polarity marking and the CI370 is wired backwards no damage will result however the indicator will light RED instead of GREEN when...

Page 7: ...1 2 of this sheathing exposed inside of the outlet box Fold the 6 of black and white wire into the outlet box Leave the wires to be connected by the electrician when plug receptacles are being install...

Page 8: ...on or break down grounding provides a path of least resistance for electric current to reduce the risk of electric shock This appliance is equipped with a cord having an equipment grounding conductor...

Page 9: ...on next page 5 If area is clear cut an inlet opening in the wall approximately 18 above the floor Make sure wall opening and 21 2 tube hole line up Figure 30 6 Cut a length of tubing that will extend...

Page 10: ...29 16 square hole in floor Center line of inlet must be located at least 21 2 from wall to allow cover to be opened when hose is inserted 2 Determine direction of tubing and attach appropriate flange...

Page 11: ...is inserted and switched on if applicable If using CI370 Indicating Inlet be sure LED on inlet is green when hose is inserted switched on If Central Cleaning hose is not available at the time a short...

Page 12: ...not allow limitation on how long an implied warranty lasts so the above limitation may not apply to you NUTONE S OBLIGATION TO REPAIR OR REPLACE AT NUTONE S OPTION SHALL BE THE PURCHASER S SOLE AND E...

Page 13: ...ie 5 Installation des Prises Murales Mod les CI370 et 360 Prises d Aspiration Murales 6 Mod le 330 Prise Murale 6 Mod le CI390 Prise Murale Electrifi e 7 INSTALLATION DU GROUPE D ASPIRATION 8 Tableau...

Page 14: ...cessite commun ment une ligne principale deux niveaux Dans cet exemple le groupe d aspiration est mont dans le garage La tuyauterie d admission expos e monte le long du mur du garage jusqu au grenier...

Page 15: ...vous dirigeant toujours vers le groupe d aspiration 5 Soyez certain que la tuyauterie n interf re pas avec des installations lectriques de plomberie ou d autres installations m caniques 6 Placez les...

Page 16: ...illustration du montage de face Pour le montage de face utilisez les pattes d alignement des supports pour un alignement correct 4 Voyez la figure 8 Enlevez le carton du cadre protecteur Utilisez les...

Page 17: ...coller pr assemblez la section jusqu au raccord de la prise pour v rifier que la longueur soit correcte 11 Voyez la figure 14 Appliquez la colle PCV Mod le 379 l ext rieur du tuyau Couvrez le tube 2 5...

Page 18: ...y aura aucun dommage toutefois l indicateur fournira une lumi re ROUGE plut t que VERTE lorsque le boyau sera ins r dans la prise Pour corriger cette imperfection inversez simplement les deux raccord...

Page 19: ...Incorporez le c ble de 15 24 cm noir et blanc dans la bo te de sortie Laissez les c bles tre connect s par un lectricien lors de l installation des r cepteurs de prises Attention l utilisation d outi...

Page 20: ...reil doit tre mis la terre En cas de d faillance ou de panne la mise la terre constitue une voie de moindre r sistance pour le courant lectrique ce qui r duit le risque d un choc lectrique Cet apparei...

Page 21: ...approximativement 45 cm du sol Assurez vous que l ouverture du mur et le trou de la tuyauterie de 6 35 cm de diam tre sont align s Figure 30 6 Coupez une longueur de tube qui pourra s tendre de l ouve...

Page 22: ...du couvercle au moment de l insertion du boyau 2 D terminez la direction de la tuyauterie et attachez le raccord bride appropri au support de montage avec les quatre 4 vis fournies Assurez vous que l...

Page 23: ...pe d aspiration n est pas disponible ce moment un petit bout de c ble peut servir tablir le contact entre les deux contacts de la prise murale pour vous permettre d activer le groupe d aspiration V ri...

Page 24: ...LA R PARATION PAR NUTONE SA PROPRE DISCR TION DE TOUT PRODUIT OU PI CE D FECTUEUX CONSTITUE LE SEUL REM DE DE L ACHETEUR EN VERTU DE CETTE GARANTIE NUTONE NE PEUT TRE TENUE RESPONSABLE DES DOMMAGES I...

Page 25: ...i n de los enchufes de pared Enchufes de pared modelos CI370 y 360 6 Enchufe de pared modelo 330 6 Enchufe de pared modelo CI390 Enchufe electrificado 7 INSTALACION DE LA UNIDAD DE POTENCIA 8 Diagrama...

Page 26: ...se coloca en el garaje El entubado de entrada corre sin cubrir desde el fondo de la pared del garaje hacia dentro del tico de la secci n a nivel de la tierra Dos l neas secundarias conectan esta part...

Page 27: ...sario Determine la ubicaci n de cada enchufe adcional con el mismo procedimiento siempre en direcci n hacia la unidad de potencia 5 Aseg rese de que el entubado no interfiera con las instalaciones el...

Page 28: ...traci n del montaje superficial Para el montaje superficial use las aletas localizadoras para asegurar el alineamiento correcto del encastramiento 4 V ase la Figura 8 Quite el cart n del marco protect...

Page 29: ...s correcto 11 V ase la Figura 14 Aplique cemento para PVC modelo 379 al exterior del entubado Cubra el entubado hasta 2 5 cm del extremo Cu dese de no poner cemento al interior del tubo 12 V ase la Fi...

Page 30: ...embargo el indicador se iluminar en ROJO en vez de VERDE al insertar la manguera en el enchufe Para remediar esta condici n invierta las conexiones al enchufe CI370 4 Dirija el alambre que sobra por...

Page 31: ...del mismo descubierto dentro de la caja de toma Doble las 15 2 cm de alambre blanco y negro hacia dentro de la caja de toma Deje los alambres para ser conectados por un electricista cuando se instalen...

Page 32: ...rato debe ser conectado a tierra Si funciona de un modo defectuoso o se aver a la conexi n a tierra le proporciona a la corriente el ctrica una v a f cil que reduce el riesgo de choque el ctrico Este...

Page 33: ...la pared a aproximadamente 45 cm del piso Aseg rese de que se alineen la abertura de pared y el agujero de tubo de 6 3 cm Figura 30 6 Corte un largo de entubado que se extender desde la abertura de e...

Page 34: ...cuando se inserte la manguera 2 Determine la direcci n del entubado y sujete el accesorio con bridas apropiado a la abrazadera de montaje con cuatro 4 tornillos proporcionados Aseg rese de que la brid...

Page 35: ...anguera Si la manguera de aspiraci n central no est disponible al momento se puede usar un pedazo corto de alambre en los contactos en la pared para activar la unidad de potencia Inspeccione cada ench...

Page 36: ...imitaci n arriba indicada puede que no se aplique a Ud LA OBLIGACI N DE NUTONE DE REPARAR O REEMPLAZAR A SU OPCI N SER EL NICO Y EXCLUSIVO RECURSO QUE TENDR EL COMPRADOR BAJO ESTA GARANT A NUTONE NO S...

Reviews: