XBC+ with Ecosmart Connect (C) Control
Installation Manual
9.10 Modular Jack Network
9.11 Terminal Network
65
66
Modular Jack Network
Terminal Network
Controller
3-way female RJ12 adaptor
3-way female RJ12 adaptor
RJ12 Sensor jack
Cable Type: Pre-fabricated 3 twisted pair with RJ12 Plugs, 26AWG
Room Module
Room Module
RJ12 Plug
RJ12 Plug
Room Module
Sensor, SA Bus (RJ-12 Modular Jack)
6
5
4
3
2
1
Power (15 VDC)
Power (15 VDC)
Bus and Power Common
Bus and Power Common
SA Bus -
SA Bus +
Controller
SA Bus Screwed
Terminal (Brown)
Cable Type: Plain-ended shielded 2 twisted pair 22AWG
Room Module
Room Module
Screwed Terminal
Room Module
Screwed Terminal
Screwed Terminal