XBC75 & 85 (AS Control)
Installation Manual
9.11 Touch Screen Display (PMX10)
31
PMX10 Touch Screen Control
Below is an optional control solution ancillary for your application. For
the full range and technical details, please contact Nuaire.
Local operator unit for monitoring and operation of ONE PX compact
or PX modular automation station.
•
High-grade display with adjustable contrast.
•
Easy operation with a push-dial, giving direct access to the
required plant information.
•
Choice of generic view or "Favourites" view for operation and
display of plant functions (alarm handling, time schedules,
calendars, set point adjustments, display of measured values, etc.).
•
System date and time setting
•
Optimized for use in a fixed location
The PXM10 (9" x 5") unit is suitable for mounting in control panel fronts
or vertical panels (e.g. remote operating panels or similar units). The
unit is also suitable for DIN rail snap mounting.
10.0 MAINTENANCE
It is important that maintenance checks are recorded and that the
schedule is always adhered to, in all cases, the previous report should
be referred to.
Before commencing work, make sure that the unit and Nuaire
control are electrically isolated from the mains supply.
In some
Ecosmart units and in some third party controls, variable speed drives
(inverters) are used to provide fan speed control. After the fan is
isolated, allow at least 5 minutes for the capacitors in the inverter to
discharge before commencing any work on the unit.
10.1 Routine Maintenance
•
Clean all areas of unit and treat any areas of corrosion.
•
Check all access doors for leakage and if necessary locks should be
adjusted and any replacement gasket materials should be replaced
as required.
•
Any drain trays should be cleaned and repaired if necessary.
10.2 Every 3 Months
•
Check filters and change/clean if required, failure to do so may
impair the performance and energy efficiency of this unit.
Typically filters should be changed when the filters experience a
125 Pa increase above the clean filter resistance for the largest
commissioned airflow rate.
•
Ensure condensate drains are cleaned clear and that water can
flow freely from unit.
•
Check fin coil banks and heat exchangers. If necessary clean with a
soft brush or vacuum. Check for signs of contamination.
10.3 Annually
•
Thoroughly inspect the unit and its components for corrosion,
acting immediately to treat/restore any damaged areas.
•
All electrical terminals within the unit should be tightened.
•
C
heck all earth connections.
•
Check control dampers blades.
•
Check operation of damper actuators and linkages and adjust as
necessary.
•
Coil faces should be inspected and any dust removed.
•
Check any thermal wheel belt, motor, bearings, seals and if
necessary clean with a soft brush or vacuum cleaner.
11.0 WARRANTY
A 5
year warranty on Ecosmart Control models, Basic Control models
have a 2 year warranty. The warranty starts from the day of delivery and
includes parts and labour for the first year. The remaining period covers
replacement parts only.
This warranty is void if the equipment is modified without
authorisation, is incorrectly applied, misused, disassembled, or not
installed, commissioned and maintained in accordance with the details
contained in this manual and general good practice.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Conditions of Sale. Customers purchasing from
outside of the UK should contact Nuaire International Sales office for
further details.
Failure to maintain the unit as recommended will invalidate the
warranty.
12.0 END-OF-LIFE AND RECYCLING
Where possible Nuaire use components which can be largely recycled
when the product reaches its end-of-life:
•
Fans, motors, controls, actuators, cabling and other electrical
components can be segregated into WEEE recycling streams.
•
Sheet metal parts, aluminium extrusion, heating/cooling coils and
other metallic items can be segregated and fully recycled.
•
EPP, plastic ducting, nylon corner pieces, plastic heat exchangers,
packaging material and other plastic components can be
segregated into mixed plastic and widely recycled.
•
Cardboard packaging, wood, used filters and other paper
components can be largely recycled or fully processed in energy
from waste centres.
•
Remaining Items can be further segregated and processed in
accordance with the zero waste hierarchy. Please call After Sales
Support for further information on items not listed above.
Ensure that Nuaire product is made safe from any electrical / water
/ refrigerant supplies before dismantling commences. This work
should only be undertaken by a qualified person in accordance with
local authority regulations and guidelines, taking into account all
site based risks.