NuAire MRXBOXAB-ECO2-AESW Installation And Maintenance Manual Download Page 7

7

nuaire.co.uk 

029 2085 8400

04. 11. 19. Leaflet Number  671859

Installation and Maintenance

MRXBOXAB-ECO2-AESW Mechanical Ventilation Unit with Heat Recovery

+

-

Post commissioning remove
adhesive backing and seal 

Power Fan

Failure

+

-

Ventilation Controls

- +

+

- +

-

Speed 1 

- +

Speed 2 

Speed 3

Supply  Extract  Supply  Extract  Supply  Extract

Humidity adjustment

6.0 COMMISSIONING

IMPORTANT

The filters fitted inside the unit are protected with a plastic film. 

Prior to commissioning remove the covers (figs. 15 & 16), take off the 

film and replace.

1. For the required air flow rates please refer to the design specification 

for the property, follow 2.4, or refer to building regulations ADF 

2010.

2. The unit is supplied with independent control for both normal and 

boost airflows (see fig. 18). 

3. Correct commissioning is essential to ensure the ventilation air flow 

rates are met. It also ensures the unit is not over ventilating and 

causing excessive power consumption. 

4. Commissioning should be carried out in accordance with building 

regulations document “Domestic ventilation compliance guide”. 

www.planningportal.gov.uk/building regulations/approved 

documents/partf/associated

 

A calibrated moving vane anemometer and hood will be required to 

carry out commissioning.

5. Adjustment valves should be locked in place to prevent further 

adjustment. 

6. Once commissioned the home owner / tenant should be informed 

that the unit should not be adjusted as it will have a detrimental 

effect on the indoor air quality and could result in condensation and 

mould growth. The clear panel covering the control has an adhesive 

panel which should be exposed and sealed post commissioning to 

prevent tampering.

7. Speed 1 is limited to never exceed speed 2, when commissioning 

speed 2 should always be set first.

Figure 18.  Detail of unit control 

on front panel

 (standard 

configuration only).

6.1 Humidity adjustment

This product contains an internal humidity sensor fitted into the air-

flow extracting from the wet rooms. When the unit senses that the 

humidity exceeds the set point the unit will boost to that set by the 

commissioned boost speed. The set point can be found on the front 

of the unit (see fig. 18) and is at its least sensitive when turned fully 

clockwise. Note that the sensor is measuring humidity from all the wet 

rooms at the same time and should not be relied on to solely boost 

the unit. Additional switch should be used local to the wet rooms (see 

wiring diagrams).

Nuaire recommend that filters are inspected every 6 months and 

replaced every 12 months. A flashing LED (section 7.0) will indicate that 

a filter change is required. This indication repeats every 12 months and 

will turn off automatically after 5 Days.
Remove the filter covers on the front panel of the unit by gripping the 

two circular tabs either end of the filter covers and pulling away from 

the unit. The filter can now be extracted by pulling the removal loop on 

the front edge of the filter. Once the filters have been inspected return 

or replace them as necessary. 
Inspect the heat exchanger every 5 years. Generally check for damage 

and security of components. Refit cover.

7.0 STATUS INDICATION

The status of the unit is indicated by a series of LED’s on the front cover. 

The variants are listed below.

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

IMPORTANT

Isolation - Before commencing work make sure that the unit, 

switched live and control are electrically isolated from the mains 

supply and switched live supply.

8.0 INTEGRAL AUTOMATIC HX BYPASS

Intake and extract temperatures are monitored at the point the 

airflows enter the unit, if the range falls within the set parameters the 

bypass damper is opened automatically to target an indoor comfort 

temperature all year round.

8.1  Summer / Winter Switch

When the switch position is set to Summer the integral automatic 

summer bypass is fully operational, in the alternative Winter position 

the HX bypass is disabled to ensure the unit is constantly in heat 

recovery mode.

8.2 Frost Protection

In the event of the intake air temperature at the unit dropping below 

the predetermined set point (-5°C as standard) the supply fan will 

reduce to minimum speed, once the temperature rises above the set 

point the fan will return to its commissioned speed.
Please note this mode will only activate after ten days of continuous 

run time. If commissioning of the unit is outside of this time frame 

please notify the after sales department prior to site visit.

9.0 MAINTENANCE

Note: The display on the unit control panel will not indicate when a 

higher speed setting has been triggered by an external source, such 

as an ES-PIR2 etc.

Summary of Contents for MRXBOXAB-ECO2-AESW

Page 1: ...n with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person for their safety Children should be supervised so that they do not play with the appliance 2 1 Transportation fixings To prevent damage during transportation the product is shipped with securing fixings the...

Page 2: ...ical example of a cupboard mounted unit Standard unit fixed to a stud partition with the MDF panel fixed behind the plasterboard 2 5 Condensate Drain The MVHR unit inside the enclosure is fitted with a straight coupling to allow 21 5mm overflow pipe not supplied to be attached using solvent cement the pipe should be passed through the flexible adhesive backed cover plate before the solvent cement ...

Page 3: ...outside of the outside air inlet duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended Ideally 125mm diameter or 220 x 90mm rectangular ducting should be used Refer to dwelli...

Page 4: ...step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For further information refer to Domestic Ventilation Compliance Guide www planningportal gov uk buildingregulations approved documents partl compliance ...

Page 5: ... duct 4 0 DUCTING ARRANGEMENTS STANDARD CONFIGURATION Figure 12 Typical ducted arrangement for a wall mounted unit using circular ducting Figure 13 Typical ducted arrangement for a wall mounted unit using rectangular ducting Air supply to lounge in ceilings via AirValve Extract air from kitchen bathroom in ceilings via AirValve Exhaust air from kitchen bathroom to outside via louvre grille Minimum...

Page 6: ...ions in fig 14 are factory fitted The unit is pre wired with a 2 metre fly lead Fuse 2A MAINS 230V 50Hz light Room Light switch Double Pole N L 3 Pole isolator Kitchen switch Blue Brown Black Optional 3 speed switch Supply cord from unit Grey Green yellow Fuse 2A MAINS 230V 50Hz Room lights Light Double switches Pole N L 3 Pole isolator Kitchen switch Blue Green yellow Brown Black Supply cord from...

Page 7: ...or is measuring humidity from all the wet rooms at the same time and should not be relied on to solely boost the unit Additional switch should be used local to the wet rooms see wiring diagrams Nuaire recommend that filters are inspected every 6 months and replaced every 12 months A flashing LED section 7 0 will indicate that a filter change is required This indication repeats every 12 months and ...

Page 8: ...our for the first year and parts only for the remaining 4 years This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissioned and maintained in accordance with the details contained in this manual and general good practice The product warranty applies to the UK mainland and in accordance with Clause 14 of our Cond...

Reviews: