Installation and Maintenance

MRXBOXAB-ECO2-AESW Mechanical Ventilation Unit with Heat Recovery

2.6 Extract/Input Areas

The unit is designed to extract air from all wet rooms e.g. bathroom, 

kitchen, en-suite, utility room (with sink).  WC’s do not need to be 

ventilated if openable windows are fitted.
Supply air should be to all habitable rooms e.g. bedrooms and lounge. 

Extract / input grilles should be adjustable valve types (not supplied). 

External grilles are to have a minimum free area of 12,250 mm

2

.

2.7 Ducting

Before commencing ducting installation reference should be made 

to building regulations document “Domestic ventilation compliance 

guide”. This document supports ADF2010 and details installation, 

testing and commissioning of all ventilation systems.
If the enclosure is to be used in conjunction with an ancillary 

distribution box (MRXBOX-DB2) refer to additional assembly 

instructions supplied with the MRXBOX-DB2 as requirements will 

differ.
Otherwise fit 4x 125mm diameter plastic spigots with the self-tapping 

screws supplied to the spigot fixings plates found on the top panel of 

the enclosure, a bead of silicone should be applied to the groove of 

spigot fixing plate to prevent leakage (see fig. 3).
It is recommended that rigid ducting be used at all times. Flexible 

ducting has a very high resistance and it is impossible to calculate how 

much resistance will be on a system if used.
If used the flexible ducting must be kept to a minimum and should 

always be pulled taut. A maximum of 300mm should be used on each 

leg.
To prevent condensation on the outside of the outside air inlet duct and 

the air outlet duct from the unit, these ducts should be insulated.
Ducting must be installed in such a way that resistance to airflow is 

minimised. Bends should be kept to a minimum.
A minimum distance of 300mm between the appliance and any bends 

in ductwork is recommended.
Ideally 125mm diameter or 220 x 90mm rectangular ducting should be 

used. (Refer to dwelling design drawing, figure 10a and 10b on page 5 

for further information).
Ducting joints must be sealed with silicone type sealant and shall be 

adequately and reliably fixed to the appliance.

2.8 Ventilation Flow Rates

Table 1. ADF 2010 - Extract ventilation rates.

Table 2. Whole dwelling ventilation rates.

Notes:
1. In addition, the minimum ventilation rate should be no less than 

0.3 l/s per m2 of internal floor area.  (This includes all floors, e.g. 

for a two-story building add the ground and first floor areas).
2. This is based on two occupants in the main bedroom and a single 

occupant in all other bedrooms. This should be used as the default 

value. If a greater level of occupancy is expected add 4 l/s per 

occupant.

IMPORTANT

Any air intake terminal MUST be installed in accordance with 

the appropriate regulation.

As a guide, the BS5440 series of British Standards deals with this issue 

and currently states that an air intake must be at a minimum distance 

of 300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this standard 

when installing ‘through the wall’ supply air ducting.

Room

Min high rate

Min low rate

Kitchen

13 l/s

Total extract rate 

should be at least 

the whole dwelling 

ventilation rate given 

in table 2.

Utility Room

8 l/s

Bathroom

8 l/s

Sanitary 

Accommodation

6 l/s

Number of bedrooms in dwelling

1

2

3

4

5

Whole dwelling 

ventilation rate 

(l/s)

1,2

13

17

21

25

29

Summary of Contents for MRXBOXAB-ECO2-AESW

Page 1: ...n with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person for their safety Children should be supervised so that they do not play with the appliance 2 1 Transportation fixings To prevent damage during transportation the product is shipped with securing fixings the...

Page 2: ...ical example of a cupboard mounted unit Standard unit fixed to a stud partition with the MDF panel fixed behind the plasterboard 2 5 Condensate Drain The MVHR unit inside the enclosure is fitted with a straight coupling to allow 21 5mm overflow pipe not supplied to be attached using solvent cement the pipe should be passed through the flexible adhesive backed cover plate before the solvent cement ...

Page 3: ...outside of the outside air inlet duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended Ideally 125mm diameter or 220 x 90mm rectangular ducting should be used Refer to dwelli...

Page 4: ...step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For further information refer to Domestic Ventilation Compliance Guide www planningportal gov uk buildingregulations approved documents partl compliance ...

Page 5: ... duct 4 0 DUCTING ARRANGEMENTS STANDARD CONFIGURATION Figure 12 Typical ducted arrangement for a wall mounted unit using circular ducting Figure 13 Typical ducted arrangement for a wall mounted unit using rectangular ducting Air supply to lounge in ceilings via AirValve Extract air from kitchen bathroom in ceilings via AirValve Exhaust air from kitchen bathroom to outside via louvre grille Minimum...

Page 6: ...ions in fig 14 are factory fitted The unit is pre wired with a 2 metre fly lead Fuse 2A MAINS 230V 50Hz light Room Light switch Double Pole N L 3 Pole isolator Kitchen switch Blue Brown Black Optional 3 speed switch Supply cord from unit Grey Green yellow Fuse 2A MAINS 230V 50Hz Room lights Light Double switches Pole N L 3 Pole isolator Kitchen switch Blue Green yellow Brown Black Supply cord from...

Page 7: ...or is measuring humidity from all the wet rooms at the same time and should not be relied on to solely boost the unit Additional switch should be used local to the wet rooms see wiring diagrams Nuaire recommend that filters are inspected every 6 months and replaced every 12 months A flashing LED section 7 0 will indicate that a filter change is required This indication repeats every 12 months and ...

Page 8: ...our for the first year and parts only for the remaining 4 years This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissioned and maintained in accordance with the details contained in this manual and general good practice The product warranty applies to the UK mainland and in accordance with Clause 14 of our Cond...

Reviews: