ES-OPUSDC

Installation Manual

1.2 Important Information

This manual contains important information on the safe and 
appropriate assembly, transport, commissioning, operation, 
maintenance, disassembly and simple troubleshooting of the product.

While the product has been manufactured according to the accepted 
rules of current technology, there is still a danger of personal injury or 
damage to equipment if the following general safety instructions and 
the warnings contained in these instructions are not complied with.

Read these instructions completely and thoroughly before 
working with the product.

Keep these instructions in a location where they are accessible 
to all users at all times.

Always include the operating instructions when you pass the 
product on to third parties.

1.3 Personal Protective Equipment

The following minimum Personal Protective Equipment (PPE) is 
recommended when interacting with Nuaire product:

Protective Steel Toed Shoes - 

when handling heavy objects.

 

Full Finger Gloves (Marigold PU800 or equivalent) - 

when 

handling sheet metal components. 

Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent) 

- when conducting light work on the unit requiring tactile 
dexterity. 

Safety Glasses

 - when conducting any cleaning/cutting operation 

or exchanging filters. 

Reusable Half Mask Respirators 

- when replacing filters which 

have been in contact with normal room or environmental air.

Nuaire would always recommend a site specific risk assessment by a 
competent person to determine if any additional PPE is required. 

2.0 INTRODUCTION

The Nuaire range of low power duct mounted extract fans have been 
specifically designed to ventilate areas such as toilets, bathrooms, small 
offices, etc. The range consists of units for four duty ranges, 40 l/s, 60 
l/s, 75 l/s and 110 l/s maximum extraction.

The 40 l/s and 60 l/s products are available as single fan or twinfan 
variants, twinfan units are duty sharing. The 75 l/s and 110 l/s products 
are dual fan only (both fans run simultaneously).

All units incorporate speed control for both low and high speed, along 
with adjustable run-on facility and allow connection of Ecosmart 
sensors (PIR, humidistat etc).

The unit discharges through 100mm diameter outlet spigot. Air enters 
the unit through 3 off 100mm diameter spigots, the central spigot is 
supplied open and the other two supplied closed but are easy to open 
(Figure 7).

The motor is of the DC variant, fitted with self lubricating ball bearing 
and locked rotor protection.

The unit is supplied with a quick release fan mounting bracket which 
allows for installation in any configuration.

2.1 Code Description

1

2

-

3

ES-OPUSDC

40

-

2M

   

1. Range:  

 

ES-OPUSDC 

(Low Power Duct Mounted  

 

 

 

Extract Fans wIth Ecosmart Control)

2. Unit Size:  

 

40 

=

 

40 l/s

 

 

  60 

=

 

65 l/s

 

 

  75 

=

 

75 l/s

 

 

  110 

=

 

110 l/s

3. Fan Arrangement: 

= Single Fan (40 & 60 Duty Only) or 

 

 

 

        Dual Fan (75 & 110 Duty Only) 

  

 

2M 

= Twin Fan (40 & 60 Duty Only)

General View Of Unit

Extract to outside

Extract from 
bathroom 
for example. 

Extract 
from WC 
for example.

3.0 MECHANICAL INSTALLATION

Installation must be completed by competent persons, in accordance 
with good industry practice and should conform to all governing and 
statutory bodies i.e. IEE, CIBSE, etc.

The unit is designed to be ceiling/wall mounted in any plane, with the 
access panel for the wiring and controls on the underside. The fan must 
be fitted indoors, away from any direct sources of heat, water spray or 
moisture generation.

A clear working space is required around the installed unit to 
allow the cover to be removed and provide sufficient access for 
maintenance.

The integral mounting bracket supplied with the unit can be 
offered up to position on the ceiling or wall (Figures 2 and 4).

The fixing points for the bracket should then be marked and the 
bracket installed with two screws ensuring that the bracket is 
secure on the ceiling or wall. 

Offer the unit into position inside the bracket ensuring the access 
cover is face down, and locate the bracket into the moulded 
bracket holders on the case sides (Figure 3).

Various spigot positions can be utilised as required to suit the system 
ductwork and extract grilles. The unit is supplied with one spigot open 
and two ’closed’ as knockouts when delivered but they can be opened 
using a hacksaw (Figure 7).

Summary of Contents for ES-OPUSDC Series

Page 1: ...able guards If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The replacement cord must be of the same t...

Page 2: ...fans run simultaneously All units incorporate speed control for both low and high speed along with adjustable run on facility and allow connection of Ecosmart sensors PIR humidistat etc The unit disc...

Page 3: ...ntrol Panel Mounting Bracket Clip Mounting Bracket Screws Into Ceiling 3 Wall Mounted Unit Horizontal Mounting Bracket Screws Into Wall Air extract from WC for example Grille available as an optional...

Page 4: ...d EMC engineering practice any sensor cables or switched live cables should not be placed within 50mm of other cables or on the same metal cable tray as other cables 4 1 Electrical Information Unit Si...

Page 5: ...tection These contacts are rated at 5A resistive 0 5A inductive 4 3 3 Run Connections These contacts are closed when the fan is running 4 3 4 Fault Connections No Fault Contacts are closed Fault Conta...

Page 6: ...er pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compone...

Page 7: ...ould not be placed within 50mm or on the same metal cable tray as 230V switched live lighting or power cables and any cables not intended for use with this product In addition to the particular requir...

Page 8: ...8 06 10 20 Document Number 671139 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk ES OPUSDC Installation Manual NOTES...

Reviews: