Installation Manual

Typical Wet Coil Pipe Termination Arrangement

4.0 ELECTRICAL INSTALLATION

Cautionary Notes:

Ecosmart controls use ‘burst fire’ control technology to manage 
the heater output. Due to the high absorbed currents on electric 
heaters there may be voltage drops experienced in the electrical 
system that may have an adverse effect on lighting etc.

There are no inrush starting currents quoted because the Ecosmart 
control incorporates a soft starting speed control feature.

The inverters are pre-set to match the fan heaters and control 
requirements. Under normal circumstances it should not be 
necessary to adjust them.

Pay particular attention to the model type, recorded on the 
product rating plate and connect as follows.

The electrical wiring must be carried out by a competent person 
and the unit must be provided with means of local isolation (by 
others) for maintenance purposes. A suitable isolator is available 
from Nuaire as a separate option.

This product must be earthed.

4.1 Electrical Information

Unit Model

FLC  

Fan Only

Electric Heater  

(Max Power)

FLC 

Heater

ESBHEX1, ESBHS1-L

4.9 A

N/A

N/A

ESBHS1-E

4.9 A

18kW

25A

ESBHEX2, ESBHS2-L

7.3 A

N/A

N/A

ESBHS2-E

7.3 A

24kW

33A

ESBHEX3, ESBHS3-L

5.0 A

N/A

N/A

ESBHS3-E

5.0 A

27kW

38A

ESBHEX4, ESBHS4-L

7.0 A

N/A

N/A

ESBHS4-E

7.0 A

36kW

50A

ESBHEX5, ESBHS5-L

8.5 A

N/A

N/A

ESBHS5-E

8.5 A

54kW

75A

ESBHEX6, ESBHS6-L

8.5 A

N/A

N/A

ESBHS6-E

8.5 A

54kW

75A

ESBHEX7, ESBHS7-L

11.4 A

N/A

N/A

ESBHS7-E

11.4 A

54kW

75A

4.2 Wiring Diagrams

4.2.1 ESBHS(1-2), ESBHEX(1 -2) 

 
 
 

Wiring Diagram - ESBHS(1-2), ESBHEX(1 -2)

Connections 

to Damper

N

L

SL

DP

CL

N

RET

Remove this link wire if: 

NET connections for 

ECOSMART devices

1. a switched live signal is connected.

2. A ES-PIR, ES-TC or BMS signal is connected.

Max     SL run on

Min         

Trickle

Test

1

0        

Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx

Ecosmart

signal

Heat demand  

L
N
E

Earth

Controller

Speed  

Run signal

Fault signal

FAULT     RUN

HEAT

DAMPER 

DEMAND

230V 50Hz  

1ph mains

0V

0-10V

BMS signal

Summary of Contents for Ecosmart Boxer ESBH Series

Page 1: ...parts Duct runs terminating close to the fan must be adequately protected by suitable guards This appliance should not be used by children or persons with reduced physical sensory or mental capabilit...

Page 2: ...ring tactile dexterity Safety Glasses when conducting any cleaning cutting operation or exchanging filters Reusable Half Mask Respirators when replacing filters which have been in contact with normal...

Page 3: ...odular Unit Arrangement 2 3 Dimensions Weights Full details with project specific documents and drawings are available from the Nuaire Technical Estimating Department 2 4 Handling Upon receipt of the...

Page 4: ...and secured via the studs and nuts provided Access to each securing point is by removal of the access doors on each section Each joint must be appropriately sealed to ensure weathering and to prevent...

Page 5: ...ns of local isolation by others for maintenance purposes A suitable isolator is available from Nuaire as a separate option This product must be earthed 4 1 Electrical Information Unit Model FLC Fan On...

Page 6: ...AND ON OFF AUTO HEATER COOL Cooling signal demand Frost alarm signal DX1 coil Signal for if fitted DX2 coil Signal for if fitted 25 30 2 5 Set air off of LPHW coil temperature 0V 0 10V BMS signal 4 2...

Page 7: ...ons for ECOSMART devices 1 a switched live signal is connected 2 A ES PIR ES TC or BMS signal is connected Max SL run on Min Trickle Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx...

Page 8: ...emand signal Earth Run signal Fault signal FAULT RUN HEAT DAMPER DEMAND L3 L2 L1 N E 3ph N mains 400V 50Hz 5 6 3 2 1 4 U V W E L3 L1 L2 U V W L3 L2 L1 15 13 14 12 9 7 5 8 6 10 11 15 12 14 13 CONTACTER...

Page 9: ...400V 50Hz 3ph N mains 5 3 6 1 2 4 U V W E L3 L2 L1 U V W L3 L2 L1 15 14 12 13 9 8 7 6 5 11 10 15 13 14 12 CONTACTER A1 A2 ON OFF AUTO HEATER COOL Cooling signal demand Frost signal alarm DX1 coil Sign...

Page 10: ...his will cancel the delay 16 Damper Connections OP Drive Open Spring Close Drive Open Drive Close S4 S6 230V motor 230V motor A fan starting delay of 1 minute is imposed to enable the damper to open T...

Page 11: ...nnector 5 1 1 Test Button The test button allows the blower within the unit to be checked for its operation If the fan is running already press the button once to stop the fan press again to switch on...

Page 12: ...nit should be tightened Check all earth connections Check control dampers blades Check operation of damper actuators and linkages and adjust as necessary Coil faces should be inspected and any dust re...

Page 13: ...energy from waste centres Remaining Items can be further segregated and processed in accordance with the zero waste hierarchy Please call After Sales Support for further information on items not list...

Page 14: ...nd steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature air...

Page 15: ...15 22 09 20 Document Number 671188 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk ESBH Installation Manual NOTES...

Page 16: ...16 22 09 20 Document Number 671188 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk ESBH Installation Manual NOTES...

Reviews: