Nuaire Group BPC MRXBOX95-WM1 Installation And Maintenance Manual Download Page 3

3

09. 06. 16. Leaflet Number 671684

Installation and Maintenance

The WM1 Wall Mounted Range of Units

2.3 Condensate Drain

1. The condensate must be discharged under a water level in a

U-trap drainpipe or an alternative drain method which acts as an
airlock. 

2. This condensate discharge connection is suitable for 21.5mm dia. 

overflow pipe. Solvent cement should be used to make the joint. 

3. If using a U-trap please ensure the U-trap has been filled to a

suitable level of water to avoid any air locks.

4. If the condensation pipe is fitted in an unheated space the pipe

should be in insulated to prevent freezing. 

Nuaire recommend MVHR-DRAIN be used as the primary 
condensate take-off. (see figure 8b and 8C.

2.4 Extract/input areas

The unit is designed to extract air from all wet rooms e.g. bathroom,
kitchen, en-suite, utility room (with sink). 
WC’s do not need to be ventilated if openable windows are fitted.

Supply air should be to all habitable rooms e.g. bedrooms and lounge.
Extract / input grilles should be adjustable valve types (not supplied).
External grilles to have a minimum free area of 12,250 sq mm.

2.5 Ducting

Before commencing ducting installation reference should be made to
building regulations document “Domestic ventilation compliance
guide”. This document supports ADF2010 and details installation,
testing and commissioning of all ventilation systems.

It is recommended that rigid ducting be used at all times. 
Flexible ducting has a very high resistance and it is impossible to 
calculate how much resistance will be on a system if used.

If used the flexible ducting must be kept to a minimum and should
always be pulled taut. A maximum of 300mm should be used on each
leg.

To prevent condensation on the outside of the outside air inlet duct
and the air outlet duct from the unit, these ducts should be 
insulated. 

Ducting must be installed in such a way that resistance to airflow is
minimised. Bends should be kept to a minimum.

A minimum distance of 300mm between the appliance and any
bends in ductwork is recommended.

Ideally 150mm diameter or 204 x 60mm rectangular ducting should
be used. (Refer to dwelling design drawing, figure 9a and 9b on 
page 5 for further information).

Ducting joints must be sealed with silicone type sealant and shall be
adequately and reliably fixed to the appliance.

2.6 Ventilation flow rates

Table 1.

ADF 2010  – Extract ventilation rates

Room

Min high rate

Min low rate

Kitchen

13 l/s

Utility room

8 l/s

Bathroom

8 l/s

Sanitary 
accommodation

6 l/s

Table 2.

Whole dwelling ventilation rates

Number of bedrooms in dwelling

1

2

3

4

5

Whole

13

17

21

25

29

dwelling 
ventilation 
rate l/s

1, 2

Notes:

1,

In addition, the minimum ventilation rate be should be not less

than 0.3 l/s per m

2

of internal floor area. 

(This includes all floors, e.g. for a two-story building add the
ground and first floor areas).

2,

This is based on two occupants in the main bedroom and a 

single occupant in all other bedrooms. This should be used as the
default value. If a greater level of occupancy is expected add 4 l/s
per occupant.

Figure 7a. Wet option.
Condensate pipe 
connection to unit and 
a typical example of 
a “U” trap drainpipe.

(Standard configuration
only).

Figure 7b. MVHR-DRAIN option. 
Condensate drain, uninsulated drain 
pipe with min 5

o

fall running to SVP.

Min 5

o

Drop

Collar

Total extract rate should be
at least the whole dwelling
ventilation rate given in
table 2.

To SVP 

“T” piece 

MVHR Drain 

To unit 

To CONTRAP 

Figure 7c. 

IMPORTANT: When using a “T” Piece to connect the CONTRAP

drainage and the MVHR drain pipework the MVHR drain must always be
fitted before the “T” Piece to prevent condensate from feeding back
into the MVHR system. 

Any air intake terminal MUST be installed in accordance with

 

the appropriate regulation.

As a guide, the BS5440 series of British Standards deals with

 

this issue and currently states that an air intake must be at a

 

minimum distance of 300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this

 

standard when installing ‘through the wall’ supply air ducting.

Summary of Contents for BPC MRXBOX95-WM1

Page 1: ... the pre drilled holes in the bracket and install with screws by others ensuring the interlock side is at the top fig 3 Figure 3 Fixing the mounting bracket to the wall 2 Install the unit on the wall by ensuring the bracket fixed to the rear of the unit interlocks over the wall mounted bracket fig 4 Figure 4 Mounting the unit on the wall mounted bracket Note Care must be taken to ensure the unit i...

Page 2: ...Figure 5 Typical example of a cupboard mounted unit Standard unit fixed to a block work wall Option 2 Wall Mounting If it is not practical to use a solid wall the MVHR unit should be fixed to a stud partition with a 25mm minimum thickness MDF panel solidly fixed behind the plasterboard If fixing to a stud wall the MDF panel should extend width wise over a minimum of 3 vertical studs with centres o...

Page 3: ...pt to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended Ideally 150mm diameter or 204 x 60mm rectangular ducting should be used Refer to dwelling design drawing figure 9a and 9b on page 5 for further information Ducting joints must be sealed with silicone type sealant and shall be adequately and reliably fixed to the appliance 2 6 Ventilation flow...

Page 4: ...ly as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high extract rate for the sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows n the maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note...

Page 5: ...upply duct Air supply to lounge via Air Valve in ceilings Extract air from kitchen bathroom via Air Valve in ceilings Air supply to bedrooms via Air Valve in ceilings Top of ceiling void Top of ceiling void Nuaire wall mounted unit Air supply to bedrooms via Air Valve in ceilings Nuaire wall mounted unit MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running to SVP MVHR DRAIN ...

Page 6: ...ure 10 The IDC plug in connectors are provided for the connection of compatible sensors NOTE Do not run the data cable in the same conduit as the mains cable and leave a 50mm separation with any power cables Fuse 2A MAINS 230V 50Hz Room light Light switch Double Pole N L Fuse 2A MAINS 230V 50Hz Room lights Light switches Double Pole N L 3 Pole isolator 3 Pole isolator Kitchen switch Kitchen switch...

Page 7: ...ngportal gov uk building regulations approved documents partf associated A calibrated moving vane anemometer and hood will be required to carry out commissioning 5 Adjustment valves should be locked in place to prevent further adjustment 6 Once commissioned the home owner tenant should be informed that the unit should not be adjusted as it will have a detrimental effect on the indoor air quality a...

Page 8: ...ectrically competent person When ordering spare parts please quote the serial number of the unit and the ARC number of the purchase if possible This information will be available on the fan label 11 0 Warranty The 5 year warranty starts from the day of delivery and includes parts and labour for the first year and parts only for the remaining 4 years This warranty is conditional on planned maintena...

Page 9: ...lings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Customer Details Customer Name Address Telephone Number Date of Installation Name of Lead Contractor Design Project Number It should be noted that this guidance is not intended to replace product manufactur...

Page 10: ...or to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow and least resistance Bends should have a minimum radius at least the same as the diameter of the ducting used Refer to Figure 1 if using flexible ducting Have the fans and ducting placed in unheated vo...

Page 11: ...ry unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Have approved acoustic anti vibration mountings been used Note Special attention is needed to avoid transmission and stress to duct joints Has the unit been installed in a position that will permit acce...

Page 12: ... or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been provided to enable the unit to be isolated for maintenance purposes Has the unit been fused in accordance with its power rating SECTION 2 COMMISSIONING GUIDANCE ...

Page 13: ...ution grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Set normal daytime air flow on extract points starting at location furthest from unit Set normal daytime air flow on input points starting at location furthest from unit Step 1 Step 2 Step 3 Step 4 Ste...

Page 14: ...he customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised not to seal natural air flows from room to room e g avoid door seals and thick pile carpets Has the customer been advised not to alter settings post commissioning Has the customer been advised to cl...

Reviews: