background image

Page 13

NOL Compact Modulating

•

Turning to the air cam (fig. 2 opposite), rotate

the thumbscrews in or out so that they give

a reasonable amount of adjustment in each

direction. Adjust the flexible cable (at either

end if necessary) until the air inlet damper is

fully closed (i.e. until all the slack is taken up

on the cable).

•

Now adjust the thumbscrews to give a small

opening of the air damper at low flame.

•

Uncover and replace the photocell. Reset the

sequence  control  and  allow  the  burner  to

start.  Immediately  the  burner  starts,  switch

the hand/auto selector switch to the ‘hand’

position  and  hold  low  flame  until  the

appliance  is  ready  to  accept  high  flame.

During this period, check and adjust the low

flame oil throughput.

•

Check the flame visually. If the flame is dirty,

adjust  the  air  cam  thumbscrews  until  the

flame becomes clean.

•

After a suitable delay, inch the camshaft to

the high flame position (i.e. through 180°) by

using  the  RWF40  control  in  manual  mode

(see page 11). Adjust the air cam profile by

means  of  the  thumbscrews  until  the  air

damper  is  sufficiently  open  to  give  clean

combustion. At this stage it will be found that

all of the thumbscrews between low and high

position will require adjusting so as to avoid

over stressing the cam profile band.

Once this has been done, there should be a fairly

smooth profile between low and high positions.
Ensure that the flame is visually clean throughout

the modulation range at all times.
Check the oil consumption. If this is not correct for

the full burner rating, the oil cam must be adjusted

as follows.
(a)

Inch the burner to low flame and note the

spill pressure.

(b)

To  increase  the  minimum  rate,  adjust  as

shown in fig. 1.

(c)

Adjust the cam to give more eccentricity for

more oil at high flame, and visa versa.

(d)

Return  to  the  minimum  setting  and

compensate for any changes.

(e)

Inch the burner to high flame and again check

the oil flow.

Continue to repeat (a) to (d) until the high flame

oil rate is correct.
When a satisfactory flame is achieved, again check

the line and spill pressures.

•

Inch  the  camshaft  back  to  the  low  flame

position.  The  oil  consumption  rate  should

now be between 35 and 50% of the rated

maximum.

•

Measure the flue gas composition and adjust

the combustion air volume as necessary.

•

Check  the  burner  performance  throughout

the  range  adjusting  the  air  cam  profile  as

necessary to give a clean and efficient flame.

When a satisfactory setting has been achieved, lock

the air cam thumbscrews with the grubscrews fitted

in  the  side  face  of  the  cam  body.  Refit  the

Modulating unit access cover.
If  the  burner  control  panel  is  inclusive  of  Low 

Excess low and High Water interlocks and alarms,

test that these function correctly. Ensure that the

boiler feed pump switchgear provided in the panel

is operating satisfactorily.
Adjust  the  modulating  control  to  the  required

pressure/temperature.
Allow  the  boiler  to  attain  the  correct  working

pressure/temperature  and  adjust  the  on/off  and

limit instruments to the desired values.
Return the RWF40 to automatic mode. The plant

is  now  under  the  control  of  the  pressure/

temperature controllers for modulation and the on/

off and high limit instruments for control.
Finally check all ancillary controls and equipment

such as damper interlocks etc.

R

OUTINE

  M

AINTENANCE

 

OF

  NOL

M

ODULATING

  B

URNERS

General

It is vitally important that personnel responsible for

the day to day operation and maintenance of the

plant are instructed by the commissioning engineer

on the basic function of the burner as well as the

need for routine maintenance and daily checking

of burner operations.
Final  adjustments,  which  will  have  been  made

during  the  commissioning,  must  be  recorded  on

the 

Commissioning Sheet 

at the back of this manual

and  in  the  appliance 

logbook

.  A  copy  of  the

commissioning data 

must

 be sent to the appliance

manufacturer.
The burner should be kept clean inside and out. It

will be more reliable, and if an oil leak occurs it

will be spotted more readily.

Summary of Contents for NOL

Page 1: ...Page 1 NOL Compact Modulating HANDBOOK Series NOL fully automatic oil burner Models NOL Compact Modulating Class D Oil ...

Page 2: ...ents 6 Plant Room Ventilation 6 Existing Appliances 7 Combustion Chamber Conditions 7 INSTALLATION 7 General 7 Fitting to the Appliance 7 Oil Supply Connections 7 Electrical Power Connection 7 BURNER AIR CONTROLS 7 Air Diffuser 7 BURNER OIL CONTROLS 7 Oil Nozzle 7 Oil Control Train 7 Modulating Unit 7 BURNER OIL SYSTEM 8 ELECTRICAL CONNECTIONS 9 OPERATION 10 COMMISSIONING 10 IMPORTANT SAFETY 10 EM...

Page 3: ...res average water temperature and CO2 or O2 concentration ROUTINE MAINTENANCE OF NOL MODULATING BURNERS 13 General 13 Daily Checks 14 Photoelectric Cell 14 Replenishing the Fuel Supply 14 Boiler Combustion Surface 14 FAULT FINDING 14 If the Burner Fails to Start 14 If the burner is found at lockout red lockout lamp illuminated 14 Flame Occurs Followed by Immediate Lockout 14 The Burner Starts With...

Page 4: ...NOL Compact Modulating Page 4 BURNER COMPONENT IDENTIFICATION Standard Burner Arrangement Shown All dimensions are mm 851 5 352 7 21 ...

Page 5: ... 4 7 6 0 3 4 7 5 4 7 5 4 7 8 3 0 4 4 4 5 2 5 0 3 8 3 0 5 L O N 5 6 4 1 2 7 0 3 4 0 8 4 0 8 4 0 8 4 4 5 2 5 0 3 8 2 0 6 L O N 0 4 4 4 7 6 0 3 4 7 5 4 7 5 4 7 8 3 0 4 4 4 5 2 5 0 3 4 3 0 6 L O N 0 4 4 4 7 6 0 3 4 0 8 4 0 8 4 7 8 3 0 4 4 4 5 2 5 0 3 8 3 0 6 L O N 5 6 4 1 2 7 0 3 4 0 8 4 0 8 4 0 8 4 4 5 2 5 0 3 8 3 5 8 L O N 5 6 4 1 2 7 0 3 4 7 3 5 0 8 4 0 8 4 0 8 2 5 0 3 M E T I N O I T P I R C S E D...

Page 6: ... complete the manual Literature on proprietary components is available on request SITE CONDITIONS AND SERVICES Fuel Storage and Handling The requirements of BS2869 will ensure that the fuel is suitable Under sustained cold and exposed conditions class D grade of fuel should be stored and supplied to the burner at a minimum temperature of 5 C 41 F Fuel Supply The oil line should consist of metallic...

Page 7: ...facturers instructions BURNER AIR CONTROLS A motorised cable driven air flap controls the air for combustion It is located inside the air inlet Air Diffuser The air diffuser creates a pressure drop to ensure good fuel air mixing and flame stability BURNER OIL CONTROLS Oil Nozzle The oil nozzle is of the spill back type and is fitted to the front end of the inner assembly and located in the flame t...

Page 8: ... 77 M E T I N O I T P I R C S E D 1 h c t i w S e r u s s e r P 2 e v l a V l o r t n o C l l i p S 3 e v l a v k c e h c n r u t e R n o N 4 e g u a G e r u s s e r P d e e F 5 e g u a G e r u s s e r P l l i p S 6 e v l a V f f O t u h S e g u a G 7 k c o l B d l o f i n a M r e n r u B 8 d e e F e v l a V y t e f a S C N 9 n r u t e R e v l a V y t e f a S C N 0 1 p m u P l i O 1 1 e l z z o N ...

Page 9: ...6833 1 3 6 86 62 7 6833 7 7 K 7 7 7 7 3 1 32 5 7 51 211 7 216 9 3 1 3 8 6 32 5 7 51 211 7 216 9 851 5 7 50 1 675 3 237 21 5 029 3 1 3 8 6 ELECTRICAL CONNECTIONS M E T I N O I T P I R C S E D 2 F t n e m u r t s n I t i m i L e c n a i l p p A 1 H l a n g i S t l u a F r e n r u B 2 H l a n g i S g n i t a r e p O r e n r u B 1 N t n e m u r t s n I f f O n O e c n a i l p p A 1 P n u R s r u o H g...

Page 10: ...l burner commissioning Nu way can accept no responsibility for consequential loss damage or personal injury which results from a failure to follow the commissioning instructions provided or from commissioning procedures being undertaken by unqualified personnel EMERGENCY INSTRUCTIONS NOL Modulating burners are designed and constructed to meet current legislation When used in accordance with the in...

Page 11: ...id on the modulating cam box unit Switch on the burner at the control panel The modulating unit camshaft should now rotate to the high flame setting and the combustion air motor will start the air pre purge phase Allow the fan motor to run up to speed switch off the burner and check the fan rotation Anti clockwise as viewed from the motor side as the fan slows down Remove and cover the photoelectr...

Page 12: ... Plunger Locking Screws Profile Band Cam Lever Operating Cable Adjuster Locking Screws Profile Adjuster Retaining Saddle Cable Adjuster Oil Cam A Air Cam B Oil Cam View On A Air Cam View On B View of Servomotor from underside cover removed showing position of disengagement lever Rotation for High Flame position Cams shown in the Low Flame Position Fig 1 Fig 2 Spill Pressure Reduce Increase ...

Page 13: ...oil flow Continue to repeat a to d until the high flame oil rate is correct When a satisfactory flame is achieved again check the line and spill pressures Inch the camshaft back to the low flame position The oil consumption rate should now be between 35 and 50 of the rated maximum Measure the flue gas composition and adjust the combustion air volume as necessary Check the burner performance throug...

Page 14: ...d before proceeding further On steam boilers check that the water level interlocks are in the made position If the burner is found at lockout red lockout lamp illuminated Reset the burner and observe the starting sequence Make reference to the Sequence Diagram and Timing Charts for the Flame Failure controls on page 15 for further information Check the fan motor overload and reset if necessary Fla...

Page 15: ...he lockout window should also be noted prior to resetting the burner Refer to theSequence Diagram and Timing Chart below PLEASE NOTE When the control box goes to lockout it is generally performing the function it is designed for Burner Control Program Burner operational sequence based on the Landis staefa LAL1 25 Control box Note Timings are for operation on a 50 hz electrical supply only D O I R ...

Page 16: ...lled shut down or after each mains failure the se quence switch always runs through to the start position whereby only terminals 7 9 10 and 11 receive voltage in accordance with the control pro gram It is only then that the control unit programs a fresh burner start up Note Do not press the lockout reset button or remote reset switch for more than 10 seconds RWF40 MODULATING CONTROL Basic display ...

Page 17: ...ted range of that parameter All other parametrs must remain as supplied Note The detector range parameters SCL SCH are given as C for Hot Water temperature and bar for Steam pressure F W R 0 4 RECOMMENDED SETTINGS r e t e m a r a P y a l p s i D t o H r e t a W m a e t S l a n o i t r o p o r P d n a b 1 b P 0 1 1 e v i t a v i r e D e m i t t D 0 1 5 e m i t t e s e R t R 0 5 0 2 r o t a u t c A ...

Page 18: ...handbook Should it become necessary to order replacement parts it is important to quote the burner model specification and serial numbers to ensure correct expedition of your order Nu way Ltd is able to offer on site Commissioning Service and Repair through its wordwide network of authorised distributors and sales offices Please contact the Nu way Service Department for further information BURNER ...

Page 19: ...TPUT Kg h 0 5 10 15 20 TOTAL RESISTANCE mbar 50 100 150 200 240 NOL18 38 NOL18 34 NOL35 34 NOL35 38 NOL30 25 NOL50 38 NOL60 38 NOL85 38 NOL100 38 NOL50 28 NOL50 34 NOL60 34 NOL60 NOL35 25 28 Burner outputs are based on a gross calorific value of class D fuel of 12 66 kW Kg Graphs produced in accordance with BS EN 267 ...

Page 20: ...R r o t c i r t s e R 1 1 e l z z o N l i O R E N R U B A Ø B Ø C Ø D Ø R E N R U B A Ø B Ø C Ø D Ø 4 3 8 1 L O N 8 7 1 5 6 1 2 5 1 5 6 1 8 2 0 5 L O N 0 2 2 7 9 1 8 7 1 6 0 2 8 3 8 1 L O N 8 7 1 5 6 1 2 5 1 5 6 1 4 3 0 5 L O N 0 2 2 7 9 1 8 7 1 6 0 2 5 2 0 3 L O N 8 7 1 5 6 1 2 5 1 E N O N 8 3 0 5 L O N 0 2 2 7 9 1 8 7 1 6 0 2 5 2 5 3 L O N 8 7 1 5 6 1 0 4 1 E N O N 8 2 0 6 L O N 0 2 2 7 9 1 8 7 ...

Page 21: ...8 2 0 3 5 3 6 6 0 2 5 1 5 2 0 3 L O N 0 0 8 2 5 1 7 1 6 3 6 1 5 1 5 2 5 3 L O N 0 0 8 2 5 1 7 1 6 3 6 1 5 1 4 3 5 3 L O N 0 0 8 2 0 3 5 3 6 6 0 2 5 2 8 3 5 3 L O N 0 0 8 2 0 4 5 4 5 8 5 2 5 2 8 2 0 5 L O N 0 0 8 2 0 3 5 3 6 6 0 2 5 2 4 3 0 5 L O N 0 0 8 2 0 4 5 4 5 8 5 2 5 2 8 3 0 5 L O N 0 0 8 2 5 5 7 5 3 1 1 2 3 5 2 8 2 0 6 L O N 0 0 8 2 0 4 5 4 5 8 5 2 5 2 4 3 0 6 L O N 0 0 8 2 0 4 5 4 5 8 5 2 ...

Page 22: ...__________ Rating ________________ Spec No ______________ Serial No _______________ Nozzles ______________ Oil Pump _____________ Commissioning date __________________ Guarantee Expiry Date ________________________ Oil type ____________________________ s l i a t e D n o i t s u b m o C w o L e m a l F t n i o P 2 t n i o P 3 t n i o P 4 t n i o P 5 h g i H e m a l F O C 2 N e k o m S O C p m e T t...

Page 23: ... g n i c i v r e S e h t y b d e t e l p m o c e b o t e r a w o l e b s l i a t e d e h T t n e m t s u j d a e c i v r e s h c a e g n i w o l l o f d e n g i s d n a d e t e l p m o c e b o t t e e h s s i h T e t a D e c i v r e S f O s l i a t e D e r u t a n g i S ...

Page 24: ... WAY LIMITED P O Box 1 Vines Lane Droitwich Worc WR9 8NA England Telephone 01905 794331 e mail info nu way co uk Fax Office 01905 794017 Parts Components 01905 795829 NOL Modulating PM65 Revision 101201B BS EN ISO 9001 CERT No FM00921 ...

Reviews: