background image

Page 11

NOL Compact Modulating

•

Check  that  all  relevant  documentation  is

available including, where appropriate:

•

The  agreed  plant  performance

specifications.

•

Plant drawings and pipework layouts.

•

Electrical logic and wiring diagrams.

•

Certificates  confirming  satisfactory

completion  of  procedures  such  as

soundness testing and electrical safety

tests.

•

Commissioning,  operating  and

maintenance instructions for the plant.

•

Establish  that  the  operation  of  plant  other

that  being  commissioned  will  not  have  an

adverse effect on the operation of the plant

to be commissioned and similarly, that the
operation of the plant to be commissioned

will  not  have  and  adverse  effect  on  other

plant.
Confirm that the operation of adjacent plant

and machinery will not constitute a hazard

to the personnel involved in commissioning.

Pre-firing Checks

With the oil and power switched off, carry out the

following checks.

•

Check the nozzle size and position relative

to  the  diffuser  plate.  (The  burner  head

dimensional details are given on page 20).

•

Check that the electrode positions and H.T.

leads are correct.

•

Check the fan motor overload settings.

•

If  the  appliance  is  a  boiler,  check  that  the

water level is correct, the controlling valves

are open and that the water pumps are in

working order.

•

If  a  flue  damper  is  fitted,  check  that  it  is

correctly interlocked to the burner or fixed

in the fully open position.

•

Ensure that there is a good oil supply to the

burner pump. Bleed one or two gallons from

the flexible to eliminate any pipe scale and

air from the system.

•

Check  that  the  oil  supply  is  of  the

recommended temperature and pressure.

•

Bleed  the  burner  pump  manually  by

removing the right hand ¼” BSP plug in the

top of the pump until air free oil flows.

•

Switch on the electricity supply to the burner.

•

Remove  the  access  lid  on  the  modulating

cam box unit.

•

Switch on the burner at the control panel.

The  modulating  unit  camshaft  should  now

rotate  to  the  high  flame  setting,  and  the

combustion air motor will start the air pre

purge phase.

•

Allow  the  fan  motor  to  run  up  to  speed,

switch  off  the  burner  and  check  the  fan

rotation (Anti clockwise as viewed from the

motor side) as the fan slows down.

•

Remove and cover the photoelectric cell with

a clean lint free cloth, switch on the burner,

and  allow  it  to  run  through  to  lockout.

During this run check that the ignition spark

is occurring, and note the spill and line oil

pressures  at  the  moment  of  ignition.  Reset

the sequence control and repeat the run if

necessary  to  check  these  functions.  If

necessary,  adjust  the  spill  pressure  to  the

correct  figure  according  to  the  nozzle

specification  and  the  line  pressure  at  the

burner pump to 27.8 bar (400 psi).

THE  BURNER  IS  NOW  READY  TO  BE

COMMISSIONED.

Manual Operation

Check  that  the  RWF40  controller  is  configured

correctly (refer to page 17). Press and hold the ‘EXIT’

key  until  the  ‘manual  operation’  indicator

illuminates.  The  modulating  motor  can  now  be

inched using the ‘increase’ & ‘reduce’ buttons on

the controller face. Press and hold the ‘EXIT’ key

until the ‘manual operation’ indicator extinguishes

to return to automatic mode

Commissioning the Burner

New  burners  are  generally  supplied  against  the

firing specification of the appliance. In this case the

system  and  spill  pressures  may  be  pre set  and

require checking and minor adjustments only. The

following  section  describes  how  to  set  up  the

modulating cam box unit from a ‘scratch’ situation.
The  modulating  cam  layshaft  can  be  rotated  by

hand by using the gearbox disengagement lever in

the drive servomotor.

•

Ensuring  that  the  modulating  cam

arrangement  is  in  the  low  flame  position,

adjust the oil cam (see fig. 1 on page 12) so

that  it  gives  approximately  1.5mm  throw

(3mm stroke) and lock in position.

•

Check to ensure that the spill valve push rod

bears lightly against the oil cam.

Summary of Contents for NOL

Page 1: ...Page 1 NOL Compact Modulating HANDBOOK Series NOL fully automatic oil burner Models NOL Compact Modulating Class D Oil ...

Page 2: ...ents 6 Plant Room Ventilation 6 Existing Appliances 7 Combustion Chamber Conditions 7 INSTALLATION 7 General 7 Fitting to the Appliance 7 Oil Supply Connections 7 Electrical Power Connection 7 BURNER AIR CONTROLS 7 Air Diffuser 7 BURNER OIL CONTROLS 7 Oil Nozzle 7 Oil Control Train 7 Modulating Unit 7 BURNER OIL SYSTEM 8 ELECTRICAL CONNECTIONS 9 OPERATION 10 COMMISSIONING 10 IMPORTANT SAFETY 10 EM...

Page 3: ...res average water temperature and CO2 or O2 concentration ROUTINE MAINTENANCE OF NOL MODULATING BURNERS 13 General 13 Daily Checks 14 Photoelectric Cell 14 Replenishing the Fuel Supply 14 Boiler Combustion Surface 14 FAULT FINDING 14 If the Burner Fails to Start 14 If the burner is found at lockout red lockout lamp illuminated 14 Flame Occurs Followed by Immediate Lockout 14 The Burner Starts With...

Page 4: ...NOL Compact Modulating Page 4 BURNER COMPONENT IDENTIFICATION Standard Burner Arrangement Shown All dimensions are mm 851 5 352 7 21 ...

Page 5: ... 4 7 6 0 3 4 7 5 4 7 5 4 7 8 3 0 4 4 4 5 2 5 0 3 8 3 0 5 L O N 5 6 4 1 2 7 0 3 4 0 8 4 0 8 4 0 8 4 4 5 2 5 0 3 8 2 0 6 L O N 0 4 4 4 7 6 0 3 4 7 5 4 7 5 4 7 8 3 0 4 4 4 5 2 5 0 3 4 3 0 6 L O N 0 4 4 4 7 6 0 3 4 0 8 4 0 8 4 7 8 3 0 4 4 4 5 2 5 0 3 8 3 0 6 L O N 5 6 4 1 2 7 0 3 4 0 8 4 0 8 4 0 8 4 4 5 2 5 0 3 8 3 5 8 L O N 5 6 4 1 2 7 0 3 4 7 3 5 0 8 4 0 8 4 0 8 2 5 0 3 M E T I N O I T P I R C S E D...

Page 6: ... complete the manual Literature on proprietary components is available on request SITE CONDITIONS AND SERVICES Fuel Storage and Handling The requirements of BS2869 will ensure that the fuel is suitable Under sustained cold and exposed conditions class D grade of fuel should be stored and supplied to the burner at a minimum temperature of 5 C 41 F Fuel Supply The oil line should consist of metallic...

Page 7: ...facturers instructions BURNER AIR CONTROLS A motorised cable driven air flap controls the air for combustion It is located inside the air inlet Air Diffuser The air diffuser creates a pressure drop to ensure good fuel air mixing and flame stability BURNER OIL CONTROLS Oil Nozzle The oil nozzle is of the spill back type and is fitted to the front end of the inner assembly and located in the flame t...

Page 8: ... 77 M E T I N O I T P I R C S E D 1 h c t i w S e r u s s e r P 2 e v l a V l o r t n o C l l i p S 3 e v l a v k c e h c n r u t e R n o N 4 e g u a G e r u s s e r P d e e F 5 e g u a G e r u s s e r P l l i p S 6 e v l a V f f O t u h S e g u a G 7 k c o l B d l o f i n a M r e n r u B 8 d e e F e v l a V y t e f a S C N 9 n r u t e R e v l a V y t e f a S C N 0 1 p m u P l i O 1 1 e l z z o N ...

Page 9: ...6833 1 3 6 86 62 7 6833 7 7 K 7 7 7 7 3 1 32 5 7 51 211 7 216 9 3 1 3 8 6 32 5 7 51 211 7 216 9 851 5 7 50 1 675 3 237 21 5 029 3 1 3 8 6 ELECTRICAL CONNECTIONS M E T I N O I T P I R C S E D 2 F t n e m u r t s n I t i m i L e c n a i l p p A 1 H l a n g i S t l u a F r e n r u B 2 H l a n g i S g n i t a r e p O r e n r u B 1 N t n e m u r t s n I f f O n O e c n a i l p p A 1 P n u R s r u o H g...

Page 10: ...l burner commissioning Nu way can accept no responsibility for consequential loss damage or personal injury which results from a failure to follow the commissioning instructions provided or from commissioning procedures being undertaken by unqualified personnel EMERGENCY INSTRUCTIONS NOL Modulating burners are designed and constructed to meet current legislation When used in accordance with the in...

Page 11: ...id on the modulating cam box unit Switch on the burner at the control panel The modulating unit camshaft should now rotate to the high flame setting and the combustion air motor will start the air pre purge phase Allow the fan motor to run up to speed switch off the burner and check the fan rotation Anti clockwise as viewed from the motor side as the fan slows down Remove and cover the photoelectr...

Page 12: ... Plunger Locking Screws Profile Band Cam Lever Operating Cable Adjuster Locking Screws Profile Adjuster Retaining Saddle Cable Adjuster Oil Cam A Air Cam B Oil Cam View On A Air Cam View On B View of Servomotor from underside cover removed showing position of disengagement lever Rotation for High Flame position Cams shown in the Low Flame Position Fig 1 Fig 2 Spill Pressure Reduce Increase ...

Page 13: ...oil flow Continue to repeat a to d until the high flame oil rate is correct When a satisfactory flame is achieved again check the line and spill pressures Inch the camshaft back to the low flame position The oil consumption rate should now be between 35 and 50 of the rated maximum Measure the flue gas composition and adjust the combustion air volume as necessary Check the burner performance throug...

Page 14: ...d before proceeding further On steam boilers check that the water level interlocks are in the made position If the burner is found at lockout red lockout lamp illuminated Reset the burner and observe the starting sequence Make reference to the Sequence Diagram and Timing Charts for the Flame Failure controls on page 15 for further information Check the fan motor overload and reset if necessary Fla...

Page 15: ...he lockout window should also be noted prior to resetting the burner Refer to theSequence Diagram and Timing Chart below PLEASE NOTE When the control box goes to lockout it is generally performing the function it is designed for Burner Control Program Burner operational sequence based on the Landis staefa LAL1 25 Control box Note Timings are for operation on a 50 hz electrical supply only D O I R ...

Page 16: ...lled shut down or after each mains failure the se quence switch always runs through to the start position whereby only terminals 7 9 10 and 11 receive voltage in accordance with the control pro gram It is only then that the control unit programs a fresh burner start up Note Do not press the lockout reset button or remote reset switch for more than 10 seconds RWF40 MODULATING CONTROL Basic display ...

Page 17: ...ted range of that parameter All other parametrs must remain as supplied Note The detector range parameters SCL SCH are given as C for Hot Water temperature and bar for Steam pressure F W R 0 4 RECOMMENDED SETTINGS r e t e m a r a P y a l p s i D t o H r e t a W m a e t S l a n o i t r o p o r P d n a b 1 b P 0 1 1 e v i t a v i r e D e m i t t D 0 1 5 e m i t t e s e R t R 0 5 0 2 r o t a u t c A ...

Page 18: ...handbook Should it become necessary to order replacement parts it is important to quote the burner model specification and serial numbers to ensure correct expedition of your order Nu way Ltd is able to offer on site Commissioning Service and Repair through its wordwide network of authorised distributors and sales offices Please contact the Nu way Service Department for further information BURNER ...

Page 19: ...TPUT Kg h 0 5 10 15 20 TOTAL RESISTANCE mbar 50 100 150 200 240 NOL18 38 NOL18 34 NOL35 34 NOL35 38 NOL30 25 NOL50 38 NOL60 38 NOL85 38 NOL100 38 NOL50 28 NOL50 34 NOL60 34 NOL60 NOL35 25 28 Burner outputs are based on a gross calorific value of class D fuel of 12 66 kW Kg Graphs produced in accordance with BS EN 267 ...

Page 20: ...R r o t c i r t s e R 1 1 e l z z o N l i O R E N R U B A Ø B Ø C Ø D Ø R E N R U B A Ø B Ø C Ø D Ø 4 3 8 1 L O N 8 7 1 5 6 1 2 5 1 5 6 1 8 2 0 5 L O N 0 2 2 7 9 1 8 7 1 6 0 2 8 3 8 1 L O N 8 7 1 5 6 1 2 5 1 5 6 1 4 3 0 5 L O N 0 2 2 7 9 1 8 7 1 6 0 2 5 2 0 3 L O N 8 7 1 5 6 1 2 5 1 E N O N 8 3 0 5 L O N 0 2 2 7 9 1 8 7 1 6 0 2 5 2 5 3 L O N 8 7 1 5 6 1 0 4 1 E N O N 8 2 0 6 L O N 0 2 2 7 9 1 8 7 ...

Page 21: ...8 2 0 3 5 3 6 6 0 2 5 1 5 2 0 3 L O N 0 0 8 2 5 1 7 1 6 3 6 1 5 1 5 2 5 3 L O N 0 0 8 2 5 1 7 1 6 3 6 1 5 1 4 3 5 3 L O N 0 0 8 2 0 3 5 3 6 6 0 2 5 2 8 3 5 3 L O N 0 0 8 2 0 4 5 4 5 8 5 2 5 2 8 2 0 5 L O N 0 0 8 2 0 3 5 3 6 6 0 2 5 2 4 3 0 5 L O N 0 0 8 2 0 4 5 4 5 8 5 2 5 2 8 3 0 5 L O N 0 0 8 2 5 5 7 5 3 1 1 2 3 5 2 8 2 0 6 L O N 0 0 8 2 0 4 5 4 5 8 5 2 5 2 4 3 0 6 L O N 0 0 8 2 0 4 5 4 5 8 5 2 ...

Page 22: ...__________ Rating ________________ Spec No ______________ Serial No _______________ Nozzles ______________ Oil Pump _____________ Commissioning date __________________ Guarantee Expiry Date ________________________ Oil type ____________________________ s l i a t e D n o i t s u b m o C w o L e m a l F t n i o P 2 t n i o P 3 t n i o P 4 t n i o P 5 h g i H e m a l F O C 2 N e k o m S O C p m e T t...

Page 23: ... g n i c i v r e S e h t y b d e t e l p m o c e b o t e r a w o l e b s l i a t e d e h T t n e m t s u j d a e c i v r e s h c a e g n i w o l l o f d e n g i s d n a d e t e l p m o c e b o t t e e h s s i h T e t a D e c i v r e S f O s l i a t e D e r u t a n g i S ...

Page 24: ... WAY LIMITED P O Box 1 Vines Lane Droitwich Worc WR9 8NA England Telephone 01905 794331 e mail info nu way co uk Fax Office 01905 794017 Parts Components 01905 795829 NOL Modulating PM65 Revision 101201B BS EN ISO 9001 CERT No FM00921 ...

Reviews: