Nu-Way MOL 3400-410 Installation & Maintenance Manual Download Page 22

ROUTINE MAINTENANCE OF MOL BURNERS

 

General 

It is vitally important that personnel responsible for the day to day operation and maintenance of the plant 
are instructed by the commissioning engineer on the basic function of the burner, as well as the need for 
routine maintenance and daily checking of burner operations. 
Final adjustments, which will have been made during the commissioning, must be recorded on the 

Commissioning Sheet

 at the back of this manual and in the appliance 

log book

.  A copy of the 

commissioning data 

must

 be sent to the appliance manufacturer. 

The burner should be kept clean inside and out.  It will be more reliable, and if an oil leak occurs it will be 
spotted more readily. 
 

Daily Checks

 

Inspect the burner daily to check if there is any variation from the correct operating sequence, as follows: 
Check the oil pressure on the nozzle line gauge.  This should be 27.8 bar (400 psi).  If the oil pressure is 
low, then check the oil supply system, stop/fire valves, ring main pumps, etc. 
Check the spill pressures.  If these are low it may indicate that the oil nozzle filter is clogged. 
If there is an inspection window on the appliance through which the ignition spark and flame can be 
observed, ignition and flame should be inspected and any irregularities that are observed should be 
rectified, i.e. nozzle/electrodes cleaned and any deposits removed from the inside of the flame tube and 
diffuser. 
 

Replenishing the Fuel Supply

 

It is usual practice to shut boiler(s) off whilst delivery of fuel is being made and allow approximately 30 

minutes for any sediment to settle before restarting the burners. 
 

Boiler Combustion Services

 

Keep the boiler combustion surfaces and flueways clean.  Any accumulation of soot will decrease the 
efficiency of the boiler and increase the flue gas exit temperature.  Always cover up the burner during 
boiler cleaning operations. 
 

Inner Assembly Removal – High/Low Burners

 

The inner assembly, comprising the nozzle block and diffuser plate, can be removed through the burner 
casing.  First switch off the electricity supply to the burner, remove the burner casing top cover (eight 
screws). 
Disconnect the Allen screw securing the outer manifold to the inner manifold, located on the right-hand 
side of the burner casing.  

Note that these two manifolds are sealed together by ‘O’ rings.

 

The solenoid valves, pressure gauges, etc, are now released  from the outside of the burner casing.  They 
may be supported, while the burner inner assembly is removed, by entering the Allen screw through  the 
outer manifold into the (tapped) boss provided for the purpose in the burner casing immediately below the 
normal manifold location. 
Remove the two nuts securing the inner manifold to the inside of the burner casing. 
By grasping the inner assembly pipes the complete inner assembly/diffuser can be withdrawn from the 
casing. 
The diffuser plate is mounted on a bracket clamped to the nozzle assembly. 
The front of the nozzles should be set approximately 12mm (½”) behind the diffuser face. 
The diffuser should be set 102mm (4”) back from the front of the flame tube.  The position can be 
adjusted if necessary.  If the burner has one low flame nozzle (the upper one) the ignition electrodes are 
set on this nozzle.  If there are two low flame nozzles the ignition electrode should be set over the top       
left-hand nozzle (as viewed from the front, or boiler side of the burner). 
 
 
 

MOL 3400-4100  Issue 2   10/08 

 

 

 

 

 

 

                                    Page 21

 

Summary of Contents for MOL 3400-410

Page 1: ...Installation Maintenance Manual MOL 3400 4100 Oil Burner Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Page 2: ...RNER CONTROL OPERATION MODULATING HIGH LOW 12 BURNER CONTROLS 13 Oil Pumping Units 13 Modulating Unit 13 COMMISSIONING GENERAL 14 Safety and Emergency Notes 14 Inspection 14 Pre Firing Checks 15 COMMI...

Page 3: ...hese engineers should also be CORGI registered Nu way cannot be held responsible for any consequential damage loss or personal injury as a result of customers failing to follow these instructions or a...

Page 4: ...ended for general assessment of the overall sizes of the burners and should not be used without reference to our engineering department for inclusion in drawings for installation purposes Certified di...

Page 5: ...MOL 3400 4100 Issue 2 10 08 Page 4 BURNER AND COMPONENT IDENTIFICATION FOR MODULATING BURNERS All dimensions are in mm 6 3 4 1 4 9 10 11 13 7 8...

Page 6: ...ck Release Connection 11 Burner Head Return Oil Quick Release Connection 12 Fan Inspection Cover 13 Ignition Transformer Burner Mounting Details On request MOL modulating burners can be supplied in th...

Page 7: ...0 kW 3 x 40 Amp 26 35 Amp 6mm2 MOL 4100 36 6 Amp 7 5 kW 3 x 20 Amp 11 16 Amp 4mm2 MOL 4100 41 6 Amp 11 0 kW 3 x 32 Amp 19 27 Amp 6mm2 MOL 4100 44 6 Amp 15 0 kW 3 x 40 Amp 26 35 Amp 6mm2 Pumping Unit d...

Page 8: ...ng burner can provide a turndown range of up to 3 1 The High Low version will be limited to a maximum of 2 5 1 Fuels MOL burners covered in this manual are designed to fire distillate fuel SITE CONDIT...

Page 9: ...the total swept volume of the burner oil pumps connected to the supply system All oil supply pipes must be constructed and installed to comply with local conditions and appropriate codes of practice a...

Page 10: ...and washers provided The pumping unit is supplied as a separate component to modes 1 and 2 and is inclusive of flexible pipes to make all the necessary oil connections Mode 3 On request MOL modulatin...

Page 11: ...nimum 19mm and pressure rated for 42 kg cm2 600 psi All burners require a pump inlet pressure of 0 35 to 0 70 kg cm2 5 to 10 psi If a shut off valve is fitted in the inlet line a pressure relief valve...

Page 12: ...burner component and pumping unit drawings on pages 4 13 Connect the oil supply to the burner pumping unit with reference to the oil system diagrams and pumping unit drawings on pages 10 19 Electrica...

Page 13: ...29 of this handbook When the boiler control calls for heat the burner modulating unit will travel to the high flame position and interlock the control circuit An air pre purge will take place at this...

Page 14: ...urner nozzle A return line from the back of the nozzle is connected to a spill regulating valve which regulates the oil pressure at the nozzle according to the position of an internal piston which is...

Page 15: ...hat all manual fuel isolation valves are operable fully closed and leak tight Make all personnel involved in the commissioning aware of the location of the emergency fuel and electricity isolation poi...

Page 16: ...to run through to lockout During this run check that the ignition spark is occurring and note the spill and line oil pressures at the moment of ignition Reset the sequence control and repeat the run...

Page 17: ...mper is fully closed i e until all the slack is taken up on the cable Note Cams one and two control the high cam one and low cam two limits of the mechanism These are factory set and should not requir...

Page 18: ...MOL 3400 4100 Issue 2 10 08 Page 17 MODULATING UNIT Cams shown in the Low Flame Position...

Page 19: ...ing the inching switch Slowly turn the air pressure switch adjusting dial clockwise until the flame is extinguished The burner will go to lockout Turn the dial one division anticlockwise and reset the...

Page 20: ...rt its cycle again It should lock out five seconds after the low flame solenoid valve is energised The air regulator should now be set to give a CO2 reading of 10 11 with a smoke number of 0 1 HIGH FL...

Page 21: ...gineer shall prepare a report which shall contain the following 1 Details of any modifications made to the system together with revised drawings if necessary 2 Customer and plant details including any...

Page 22: ...the burners Boiler Combustion Services Keep the boiler combustion surfaces and flueways clean Any accumulation of soot will decrease the efficiency of the boiler and increase the flue gas exit tempera...

Page 23: ...nozzle is cleaned using non abrasive materials never use anything which may scratch the finely finished surfaces of the nozzle Nozzle life is approximately 5000 hours operation after which wear will...

Page 24: ...the pre heater hot oil filter ensure that there is sufficient oil in the storage tank bleed the oil pump in case it is partially air locked Check to ensure that all stop fire valves in the supply line...

Page 25: ...BURNER HEAD DETAILS ELECTRODE SETTING MOL 3400 4100 Issue 2 10 08 Page 24 MODULATING HIGH LOW 6 3 8 13...

Page 26: ...re the reverse of the quoted rotation The Oil Pump is completely pre piped as part of the pumping or pumping and heating set Should the Oil Pump performance become suspect then a replacement unit shou...

Page 27: ...pump with positive feed pressure an external bypass has to be made between the return port and the suction port Media The pump specification stipulates mineral based fuel oil or media of a correspond...

Page 28: ...ly create a dangerous situation If a burner becomes troublesome then the assistance of a qualified engineer should be obtained To assist in his diagnosis notes should be made detailing the events lead...

Page 29: ...witch or a contact has not been closed between control box terminals 12 and 4 or 4 and 5 Shut down of start up sequence because the OPEN signal has not been supplied to control box terminal 8 by the s...

Page 30: ...be made in small increments with time given to see how the burner is reacting to the changed parameter Press and hold the PGM button down until the green set point figure changes to an AL the larger...

Page 31: ...ition Fuel supply problem YELLOW NO FLAME End Lockout Solenoid valve defective Photocell dirty Photocell or circuit faulty YELLOW WITH FLAME End Locknut No voltage at terminal 20 When a burner failure...

Page 32: ...e of the hexagonal nut section of the nozzle body as shown opposite Should any doubts arise concerning the suitability or performance of the burner nozzle please contact the Nu way Technical departmen...

Page 33: ...elect a burner with a higher fan static pressure than would normally be chosen if the appliance has a high starting resistance Similarly when firing a reverse pass boiler up to 2 MW with a combustion...

Page 34: ...erial No ________________ Burner Type ___________________ Rating ____________________ Spec No _________________ Serial No _______________ Nozzles ___________________ Oil Pump ________________ Commissi...

Page 35: ...NOTES...

Page 36: ...NOTES...

Page 37: ...Enertech Limited P O Box 1 Vines Lane Droitwich Worcestershire WR9 8NA Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Reviews: