26 Adjustment tables
The values given in the tables are only setting values for start-up. The necessary system adjust-
ment must be newly determined in the case of deviating data such as boiler output, calorific value
and altitude.
A correction is required in any case.
The maximal burner output can only be achieved in mixing head position 0. Due to the variable mixing head
position, the operating behaviour of the burner can be optimized for different heat generators..
MGN800-LN M3D
Natural gas LL: H
i,n
= 9,3
[
kWh/m
3
]
Burner output
[kW]
Boiler output
η
= 92%
[kW]
Air flap
position
[ ° ]
Burner
head
position
[mm]
Gas nozzle
pressure
[mbar]
Gas flow rate
[m
3
/h]
St. 2
St. 1
St. 2
St. 2
P 9
St. 1
P 1
St. 2
St. 1
St. 2
St. 1
300
150
276
34
12
0
2.1
0.8
33.3
16.6
500
250
460
44
30
0
6.0
1.4
55.4
27.7
700
350
644
60
37
0
11.1
3.0
77.6
38.8
811
450
746
90
42
0
15.0
5.0
89.9
49.9
MGN800-LN M3D
Natural gas E: H
i,n
= 10,4
[
kWh/m
3
]
Burner output
[kW]
Boiler output
η
= 92%
[kW]
Air flap
position
[ ° ]
Burner
head
position
[mm]
Gas nozzle
pressure
[mbar]
Gas flow rate
[m
3
/h]
St. 2
St. 1
St. 2
St. 2
P 9
St. 1
P 1
St. 2
St. 1
St. 2
St. 1
300
150
276
34
12
0
1.6
0.6
29.7
14.9
500
250
460
44
30
0
4.7
1.1
49.6
24.8
700
350
644
60
37
0
8.7
2.3
69.4
34.7
811
450
746
90
42
0
11.7
3.9
80.4
44.6