5
E
.
1
3
.1
1
.0
6
•
G
.
2
1
.0
9
.1
1
10 Mounting the gas jacket on the boiler
Use adhesive to affix the gas-jacket gasket to the
gas jacket.
The boiler connection plate has to be prepared in ac-
cordance with the sizes as stated in „9. Boiler connec-
tion dimensions“. You can use the gas-jacket gasket as
a template.
Using an 8 mm socket-head wrench, secure the gas
jacket to the boiler with the 4 M 10 fastening screws
and washers. The air pressure connection for the gas
train must be positioned at the top.
11 Mounting the burner housing on the gas jacket (service position)
Position the burner housing in the gas-jacket hinge
and secure it with a rod. The burner is now in the ser-
vice position.
Make sure that the gasket is correctly seated
between the gas jacket and the burner housing.
Swing the burner closed and insert the second secu-
ring rod into the hinge. Tighten the screw at the top to
secure the burner in position.
12 Electrical connection
Always set the main switch to "Off" and remove
the fuse before connecting the cables or removing
electrical components.
The burner must be connected to the electricity supply
in accordance with the wiring diagram. This wok must
be performed by trained, qualified electricians. The
supply cable to the burner must be of the flexible type.
Air pressure connection
B
Summary of Contents for MGN 1350 M3D DLU
Page 21: ......